throbber
IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 19, NO. 5, SEPTEMBER 2004
`
`1323
`
`Flexible Control of Small Wind Turbines With
`Grid Failure Detection Operating in
`Stand-Alone and Grid-Connected Mode
`
`Remus Teodorescu, Senior Member, IEEE, and Frede Blaabjerg, Fellow, IEEE
`
`Abstract—This paper presents the development and test
`of a flexible control strategy for an 11-kW wind turbine with
`a back-to-back power converter capable of working in both
`stand-alone and grid-connection mode. The stand-alone control
`is featured with a complex output voltage controller capable of
`handling nonlinear load and excess or deficit of generated power.
`Grid-connection mode with current control is also enabled for
`the case of isolated local grid involving other dispersed power
`generators such as other wind turbines or diesel generators.
`A novel automatic mode switch method based on a phase-locked
`loop controller is developed in order to detect the grid failure or re-
`covery and switch the operation mode accordingly. A flexible dig-
`ital signal processor (DSP) system that allows user-friendly code
`development and online tuning is used to implement and test the
`different control strategies.
`The back-to-back power conversion configuration is chosen
`where the generator converter uses a built-in standard flux vector
`control to control the speed of the turbine shaft while the grid-side
`converter uses a standard pulse-width modulation active rectifier
`control strategy implemented in a DSP controller. The design of
`the longitudinal conversion loss filter and of the involved PI-con-
`trollers are described in detail. Test results show the proposed
`methods works properly.
`Index Terms—Digital signal processor (DSP) control, grid
`failure, grid monitoring, phase-locked loop (PLL), renewable
`energy, wind turbine.
`
`I. INTRODUCTION
`
`T HE USE OF squirrel-cage induction generators (SCIG)
`
`for direct grid-connection wind energy conversion systems
`(WEC) is well established. With the last advances in power
`electronics, the use of variable-speed SCIG with a double stage
`ac–dc–ac power conversion has become quite attractive [1], in
`both low power and very high power levels [1]. Increased energy
`production at low wind, elimination of the excitation capacitor
`bank, and especially the possibility for stand-alone operation
`mode can thus be achieved at the expense of a back-to-back con-
`verter with a flexible control [2].
`Small efficient wind turbines (WT) in the range of 11 kW as
`depicted in Fig. 1 can be used to supply private houses or farms
`in remote locations in developing countries where low-cost ac-
`cess to the electrical power grid is impractical. The trend is that
`
`Manuscript received June 1, 2004; revised July 21, 2004. This work was sup-
`ported by the Danish Research Agency, Danish Technical Research Council
`through the Project “Reliable Grid Condition Detection” 2058–03–0003. Rec-
`ommended by Associate Editor F. Z. Peng.
`The authors are with the Institute of Energy Technology, Power Electronics
`Systems Section, Aalborg University, Aalborg 9220, Denmark (e-mail:
`ret@iet.aau.dk; fbl@iet.aau.dk).
`Digital Object Identifier 10.1109/TPEL.2004.833452
`
`they should be able to work in stand-alone mode but also con-
`nected to isolated local loads/grid in parallel with other gen-
`erators such as other wind turbines, photovoltaic generators,
`or diesel generators in the so called hybrid generator systems
`(HGS). Thus some new challenges on the control side of these
`WT occurred like reasonable voltage regulation in stand-alone
`mode with nonlinear load, grid-connection mode enabled, and
`automatic detection of grid failure. But in order to achieve these
`goals, relative complex control strategies need to be developed.
`Also grid failure detection and an automatic mode switching are
`required.
`A seamless transfer method from grid-connected to stand-
`alone and vice versa for critical loads is described in [3] where
`an extra static switch is required. The algorithm matches the
`magnitude and phase of the inverter voltage and the grid voltage
`at the time of disconnecting or reconnecting to the grid to min-
`imize any sudden voltage change across the load.
`A phase-locked loop (PLL) technique is commonly used in
`grid-connected converters mainly for grid-synchronization [5],
`[6]. In this paper, a novel PLL-based method for grid failure
`detection and automatic mode switching is proposed where the
`phase difference between the grid and the inverter is used to
`determine grid failure and restoring.
`The flexible control strategy featuring stand-alone mode
`and grid-connected control as well as the automatic mode
`switching strategy has been developed, implemented and tested
`for a 11-kW WT. The control strategy has been implemented
`on a development platform based on a dSPACE digital signal
`processor (DSP) controller [4] that allows flexible code devel-
`opment in Simulink and online tuning and monitoring. Thus a
`relative short development time is achieved.
`Both operation modes as well as the involved current and
`voltage controllers design are described in detail. Also, the de-
`sign of the longitudinal conversion loss (LCL) filter together
`with experimental results obtained with a drive-train emulating
`the 11-kW wind turbine are presented.
`
`II. CONCEPTS FOR STAND-ALONE WIND TURBINES
`The most common configurations of power converters for
`stand-alone SCIG WT are depicted in Fig. 2.
`The diode rectifier topology in Fig. 2(a) can only be used in
`one quadrant, it is simple and it is not possible to control it.
`This configuration is especially suitable for fixed-speed wind
`turbines and requires a capacitor bank between the generator
`and the diode rectifier in order to magnetize the induction gen-
`erator.
`The back-to-back voltage source converter is a bidirectional
`power converter consisting of two conventional voltage source
`
`0885-8993/04$20.00 © 2004 IEEE
`
`Vestas Ex 1010-p. 1
`Vestas v GE
`
`SGRE EX1045.0001
`SGRE v. GE, IPR2022-01279
`
`

`

`1324
`
`IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 19, NO. 5, SEPTEMBER 2004
`
`can be obtained by properly connecting the output terminals of
`the converter to the input terminals. Some advantages of the ma-
`trix converters are less thermal stress of the semiconductors for
`a low output frequency compared with the back-to-back solu-
`tion and the absence of the dc-link capacitor that may increase
`the efficiency and the lifetime. As drawbacks can be mentioned:
`the intrinsic limitation of the output voltage, the unavailability
`of a true bi-directional switch and there is no decoupling be-
`tween the input and the output of the converter as for the case
`of back-to-back converter and this may lead to some instability
`issues.
`A comparative study regarding different power converter
`technologies that can be used in wind turbine applications [9]
`concluded that the back-to-back converter is the least trou-
`blesome configuration mainly because it can use commercial
`converters at the generator side.
`
`III. SYSTEM DESCRIPTION
`
`The power configuration of the developed system is depicted
`in Fig. 3. It consists in a three-phase squirrel-cage induction gen-
`erator, a generator converter to control the speed of the shaft, a
`dc-link with breaking chopper, a full-bridge grid converter with
`LCL filter, in-rush resistors, and the three-phase 400-V/50-Hz
`grid.
`A flexible test and development platform has been built using
`a variable-speed drive to emulate the wind turbine mechanical
`characteristics.
`The control diagram of this platform is shown in Fig. 4 where
`the control of the wind turbine emulator is also shown.
`for
`Three
`commercial
`frequency
`inverters
`rated
`18.5 kVA/400 V are used. The first one of the type Dan-
`foss VLT5022 is feeding a 15-kW induction motor in order
`to emulate the wind turbine shaft and uses a standard scalar
`open-loop torque control.
`The second converter of type Danfoss VLT5022 Flux is used
`as generator converter and uses the built-in standard vector flux
`control to regulate the speed of the generator and provide the
`magnetizing flux for the induction generator.
`The last one is using only the power stage of a Danfoss VLT
`5022 inverter and is controlled by the dSPACE controller. It is
`used as grid converter and is connected to the grid through an
`LCL filter and employs a
`-axis control strategy for control-
`dq
`ling the active and reactive power independently. In-rush resis-
`tors are used to limit the dc-link capacitors charging current at
`startup (see Fig. 3).
`Both grid-connected and stand-alone mode for the grid con-
`verter have been implemented using the dSPACE controller. A
`mode switch can switch between the two operation modes auto-
`matically depending on the presence of the grid, as it is shown
`in VII.
`
`A. Wind Turbine Emulator
`The wind speed is calculated as an average value of the
`fixed-point wind speed over the whole rotor, and it takes the
`tower shadow and the rotational
`turbulences into account.
`The wind turbine mechanical shaft is emulated using a stan-
`dard six-pole 15-kW/400-V squirrel-cage induction motor
`controlled by a commercial frequency inverter operated in
`open-loop torque control mode. The aerodynamic model of the
`wind turbine rotor is based the
`curve as shown in Fig. 5.
`Cq->.
`
`Vestas Ex 1010-p. 2
`Vestas v GE
`
`Fig. 1. Small 11-kW GAIA (Denmark) wind turbine for households and
`remote location.
`
`Fig. 2. Stand-alone wind turbine configurations with squirrel-cage induction
`generators:
`(a) diode bridge rectifier and voltage source inverter,
`(b)
`back-to-back voltage source converter, and (c) matrix converter.
`
`inverters as shown in Fig. 2(b). To achieve full control of the
`output, the dc-link voltage must be boosted to a level higher than
`the amplitude of the isolated grid voltage. The power flow of
`the grid side converter is controlled in order to keep the dc-link
`voltage constant, while the control of the generator side is set
`to suit the magnetization demand and the reference speed or
`torque. A technical advantage of this topology is the capacitor
`decoupling between the grid converter and the generator con-
`verter. Besides affording some protection, this decoupling offers
`separate control of the two converters, allowing compensation
`of asymmetry both on the generator side and on the grid side,
`independently. Though, the dc-link capacitor is bulky and ex-
`hibits relative reduced lifetime.
`The matrix converter solution as shown in Fig. 2(c) should
`be an all silicon solution with no passive components in the
`power circuit [7], [8]. The basic idea of this converter is that
`the desired input current, output voltage and output frequency
`
`SGRE EX1045.0002
`
`

`

`TEODORESCU AND BLAABJERG: FLEXIBLE CONTROL OF WIND TURBINES WITH GRID FAILURE DETECTION
`
`1325
`
`SCIG
`
`Generator converter
`
`DC-link
`
`DC-Chopper
`
`Grid converter
`
`LCLFilter
`
`In-rush resistors Grid
`
`Ca
`
`Ca
`
`+
`VDc Raamp
`
`u
`
`V-
`
`J
`
`L1
`
`K1
`
`w
`
`R;nrush
`
`RD
`
`cFm
`
`B
`o-Q
`
`C
`o-Q
`
`Fig. 3. Power configuration of the 11-kW variable-speed wind generator.
`
`dSPACE Digital Controller/Control Panel
`
`v.,,
`
`Maximum Power Tracking
`Qopt :;;f(v"')
`
`r· = T
`1-----m-~_.o_-_o..c."''-+-~
`
`+, Wind Turbine Emulator
`
`Tmca,n=nop1 = f(Qopt)
`
`Generator Control
`
`Grid Converter Control
`
`v· d
`
`IM15kW/
`400V
`
`0.08 - - - - - - - - - - - - - - - - - - - - - - -~
`________ : ______ ----: ________ _: c~rn~~-(~_aptl_j __ ------- :---- __ ---:- ______ _
`
`0.07
`
`00 0.06
`
`-~ 0.05
`·u
`~ 0 u
`Q)
`::J
`E"
`0
`I-
`
`0.04
`
`0.03
`
`0.02
`
`0.01
`
`,
`
`I
`
`I
`
`I
`
`I
`
`I
`
`--------r- -------r---------,----------.---------,--------- ---------r-
`'
`'
`'
`'
`'
`'
`'
`'
`'
`'
`'
`'
`'
`'
`'
`'
`'
`'
`'
`'
`'
`'
`'
`'
`'
`'
`'
`'
`'
`'
`'
`'
`
`--------~--------t---------!---------1--------- ---------~--------t
`
`Grid
`converter
`
`2
`
`4
`
`10
`8
`6
`Tip speed ratio A
`
`12
`
`14
`
`16
`
`LCL Filter
`
`Fig. 5. C  performance curve for the wind turbine. C is the torque
`Q
`Q
`coefficient.
`
`The wind turbine emulator uses a scalar open-loop torque
`controlled induction motor where the torque reference is chosen
`to be
`
`T* = Tmax,!1=!1opt
`
`(3)
`
`grid/
`isolated grid
`
`Fig. 4. Block diagram of the flexible development platform for the wind
`turbine with 11-kW generator.
`
`in order to extract the maximum power from the wind turbine at
`a given wind speed.
`
`The tip speed ratio
`
`is calculated as
`
`(1)
`
`is the
`
`R
`
`is the blade radius, and
`
`n
`is the shaft speed,
`where
`wind speed.
`The
`curve is very useful in modeling the torque pro-
`duction of the wind turbine at different wind speeds. Choosing
`the optimal
`for the maximum torque coefficient
`, max-
`imum power can be extracted by setting the reference speed and
`torque for the turbine emulator [1]
`n
`- Aopt. Vex,
`R
`opt -
`
`l p1r R 5CQ,max
`2
`
`>,~pt
`
`(2)
`
`where
`
`for the maximum torque coefficient
`is the optimal
`as depicted in Fig. 5, and
`is the the air density.
`p
`
`B. Generator Control
`The generator control is working in closed-loop speed control
`mode where the speed reference converter is chosen to be equal
`with the optimal speed in order to extract the maximum power
`from the wind turbine at a certain wind speed
`
`(4)
`
`C. Grid Converter Control
`The wind turbine grid converter can operate in both grid-con-
`nected control mode and stand-alone control mode.
`Grid-Connected Control Mode: In grid-connected control
`mode, basically all the available power that can be extracted
`from the wind turbine is transferred to the grid. Additionally,
`reactive power compensation is possible if required. The
`control structure for grid-connected control mode [10] is shown
`in Fig. 6. Standard PI-controllers are used to regulate the grid
`-synchronous frame in the inner control
`currents in the
`dq
`
`Vestas Ex 1010-p. 3
`Vestas v GE
`
`SGRE EX1045.0003
`
`

`

`1326
`
`IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 19, NO. 5, SEPTEMBER 2004
`
`loops and the dc-voltage in the outer loop. A decoupling of
`the cross-coupling is implemented in order to compensate the
`couplings due to the output filter [10], [11]. The reference
`current in the -axis of the current loop is typically set to zero in
`q
`order to achieve zero phase angle between voltage and current
`and so unity power factor can be achieved.
`The output of the current controllers sets the voltage reference
`for a standard space vector modulation (SVM) that controls the
`switches of the grid converter via a fiber optic link. Synchronism
`with grid is achieved by using a phase-locked loop (PLL) as
`described in [5] and [6]. The principle of the PLL is depicted in
`Fig. 7. The input signals are
`
`sin(l,)
`
`cos(l,) = J( 2
`V::2 )
`vx + y
`
`(5)
`
`where
`are the grid voltage
`and
`is the grid phase angle,
`-reference frame. The philosophy
`components in stationary
`xy
`of the PLL is that the sinus of the difference between grid phase
`0
`and the inverter phase angle
`can be reduced to zero
`angle
`using a PI-controller, and thus locking the grid inverter phase to
`the grid, knowing that for small arguments
`
`. (
`sm "(-
`
`0) ~ "1 - 0 = 6..0.
`-
`,
`
`(6)
`
`The output of the PI controller is the inverter output frequency
`that is integrated to obtain the inverter phase . In order to im-
`0
`prove the dynamic response at startup, the nominal frequency of
`is feed-forwarded to the output of the PI-controller.
`the grid
`can be used for
`In Section VII, it will be described how the
`6..0
`detecting the presence or disappearance of the grid in order to
`automatically switch between grid-connected and stand-alone
`control mode.
`Stand-Alone Control Mode: In stand-alone control mode, no
`grid exists so the output voltages need to be controlled in terms
`of amplitude and frequency and thus, the reactive and, respec-
`tively, active power flow is controlled [1]. In the case of unbal-
`ance between the generated and the load-required power, adjust-
`ment of the speed of the generator can regulate the produced
`power in a limited range. The potential excess of power will
`by starting the
`be quickly dissipated in the damp resistor
`Rv
`chopper control (see Fig. 4).
`The control structure for stand-alone control mode is depicted
`in Fig. 8 and it consists of output voltage controller, dc-link
`voltage controller, damping chopper control, and current lim-
`iter.
`The output voltage controller is aiming to control the output
`voltage with a minimal influence from the shape of the nonlinear
`load currents or load transients. A standard PI controller oper-
`ating in the synchronously rotating coordinate system where
`is kept to zero is used. The dc-voltage PI controller maintains
`the dc voltage to the reference.
`The dc-link voltage controller is acting only when the dc-link
`is below the reference and it lowers the voltage reference of the
`
`Voc'C..j... _____ _
`
`Fig. 6. Control structure for grid-connected control mode of operation.
`
`Fig. 7. PLL structure used to synchronize the inverter voltage with the grid.
`
`de-link voltage controller
`
`Fig. 8. Control structure for stand-alone mode of operation.
`
`main voltage controller in order to avoid inverter saturation. For
`fast response there is a direct forward connection to the voltage
`controller output.
`When the dc-link is higher than the reference, the damping
`chopper control is activated and discharges the energy in excess
`stored in the dc-link and thus reduces the dc-link voltage. The
`control is linear and increases the duty-cycle as a function of
`the overvoltage size. In the case of an over-production, the level
`of produced power can be reduced also by changing the shaft
`speed in the allowed speed range.
`When the load current exceeds the rated current, the current
`limiter will decrease the output voltage reference in the allowed
`range, and for fast response there is a direct forward connection
`to the voltage controller output. This situation can occur if at a
`certain load, the generated power decreases due to lower wind
`or during overloading.
`
`Vestas Ex 1010-p. 4
`Vestas v GE
`
`SGRE EX1045.0004
`
`

`

`TEODORESCU AND BLAABJERG: FLEXIBLE CONTROL OF WIND TURBINES WITH GRID FAILURE DETECTION
`
`1327
`
`loc,11 ( _ _ . , 1'11,d_, ~ .... _[dill!' -
`f\
`
`• . • tU c. .. -. •• •• • ••
`
`""'
`
`I
`ml <"
`x x
`i 0
`. ,o . ·»·~-~-----~--
`
`•
`
`•
`
`00
`
`~,._ [dt -
`l,li~ I.I
`
`•
`
`00
`
`D. Control Panel
`The whole control strategy of the wind turbine emulator and
`wind turbine control is implemented in Simulink [12] using a
`DS1103 dSPACE controller. A virtual control panel developed
`in ControlDesk [12] that controls the whole system is shown in
`Fig. 9. As it can be observed, the control layout is divided into
`two parts generator control and grid converter control. In the
`generator control panel, the reference for the generator speed
`and the mechanical power can be set. The speed and torque are
`shown in both graphs and digital displays.
`In the grid-converter control panel the control mode will
`be automatically switched between stand-alone and grid-con-
`nected according to the presence of the grid (see Section VII).
`In grid connection control mode, the references for the active
`and reactive power to be transferred to the grid are given. The
`dc-voltage reference can also be changed in the allowable
`range.
`In stand-alone control mode, the output voltage reference is
`set in terms of RMS value. The dc voltage reference can also be
`changed in the allowable range. Grid currents and voltages are
`displayed in scope-like graphs. Digital displays show the power
`balance, including the dissipated power in the dc chopper, as
`well as the output voltages and currents.
`A test control panel for online tuning of the controllers has
`also been done. It proved to be a very convenient method to
`fine-tune the PI-controllers in the whole system.
`In the following more details on the design of the LCL-filter,
`controllers in the two control modes and the Automatic Mode
`Switching will be explained.
`
`IV. LCL FILTER DESIGN
`The LCL filter gives a better attenuation of the switching
`ripple compared to a classic L filter as it is a third-order filter
`and therefore it can be designed using smaller components.
`The transfer function in the -plane of a single-phase LCL-
`s
`filter (see Fig. 3) with passive damping is shown in (7) at the
`h
`bottom of the page, where
`is the inverter voltage,
`is the
`inverter current,
`is the inverter-side inductance,
`is the
`Le
`grid-side inductance,
`is the filter capacitance, and
`are
`Rv
`the damping series resistors.
`The following design considerations are taken into account
`[10]:
`1) the capacitor value is limited by the tolerable decrease of
`the power factor at rated power (less than 5%). The total
`value of the inductance should be lower than 10% to limit
`the dc-link voltage;
`2) the voltage drop across the filter during operation in order
`to limit the dc-link voltage;
`3) the resonance frequency should be included in a range
`between ten times the line frequency and one half of
`the switching frequency in order not to create resonance
`problems in the lower and higher parts of the harmonic
`
`..,._,.=-=--=-=w.::.•,,Cljoe._=-__ _,1_...,«r,-,=-:•:::-_ __,)11e- -,ontni1Dt.o1c~-
`
`4 & N'>I
`
`s1t""
`
`Fig. 9. ControlDesk panel for testing the wind turbine control strategy both
`stand alone and grid-connected control modes.
`
`spectrum. The passive resistors should be chosen as a
`compromise between the necessary damping and the
`losses in the system.
`The following values for the LCL-filter have been calculated:
`Rv = 4.1 n
`mH,
`mH,
`F, and
`.
`Le= l.5
`Gp = 6µ
`
`V. GRID CONNECTION CONTROL MODE—CURRENT
`CONTROLLER DESIGN
`In order to design the PI current controllers in the syn-
`chronous
`-frame, the transfer function of the filter, con-
`dq
`sidered as the system plant, is discretized using a zero-order
`hold method at a sampling frequency of 8 kHz and it thereby
`becomes
`G( z) = 0.073 52z 2 + 0.077 93z + 0.022 64 _
`z 3 + 0.093 24z 2 - 0.7928z - 0.3004
`An additional delay of one switching period is inserted in the
`model due to the PWM control of the inverter. Then the transfer
`function of the PI-controller is
`
`(8)
`
`(9)
`
`The block diagram of the current control loop is first sim-
`ulated in Simulink using the model from Fig. 10 where one
`sample delay due to the effect of PWM inverter is included.
`A standard criterion to achieve an acceptable step response is
`used for tuning the PI controller [11].
`Fig. 11(a) shows pole-zero plot of open loop system without
`the controller. There are two complex conjugated poles and one
`real pole. Because of complex conjugated poles, compensation
`techniques cannot be used. Instead a pole-zero placement tech-
`nique is used. An integrator time constant
`ms is selected
`as a compromise between good dynamics and still a good noise
`
`H(s) = h(s) =
`Vi(s)
`
`L1Cps 2 + RvCps + l
`L1LeCFs 3 + (RvL1CF + RvLeCF )s 2 + (L1 + Le)s
`
`(7)
`
`Vestas Ex 1010-p. 5
`Vestas v GE
`
`SGRE EX1045.0005
`
`

`

`1328
`
`IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 19, NO. 5, SEPTEMBER 2004
`
`o .073:52z2+o .07793z+0 .02264
`
`z3+0.09324z2•0 .7928z•0 .3004
`
`Discrete transferf. of plant
`
`0.8
`
`0 .6
`
`0.4
`
`{~ ./
`
`:
`/f.41&4._j
`
`Fig. 10. Simulink model of current control loop in z-domain for the wind
`turbine.
`
`R:>otl00.1s
`
`t~1eot
`. / ,;.:.:_\·:··• \i4:,
`\,;,;;·
`·· .. ,; .. ·.·;.;~;.L:~::~;~(
`
`-0.4
`
`-0 .6
`
`-0.8
`
`-~1
`
`-0.8 -0.6 -0.4 -0.2 0 0.2 0.4 0.6 0.8
`Real Axis
`a)
`
`1
`
`R001Locu1
`
`b)
`
`-08
`
`-0 8 -0.6 -0.4 -0.2 0 0 2 0.4 0.6 0 8
`Real Axis
`
`1
`
`a)
`
`Real Axis
`
`b)
`
`Fig. 11. Pole-zero placement of (a) open-loop system and (b) closed loop
`system for the current controllers in grid-connected control mode.
`
`is selected using root locus method so
`rejection. The gain
`that the dominant poles have a damping of 0.7. In Fig. 11(b),
`the pole-zero placement for optimized closed loop of the control
`is shown. The dominant poles have now a damping of 0.7 at a
`frequency of 580 Hz. The gain of the controller is found to be
`.
`KP
`4.8
`
`VI. STAND-ALONE CONTROL MODE—VOLTAGE
`CONTROLLER DESIGN
`The output voltage controller is aiming to control the output
`voltage with minimal influence of the shape of the nonlinear
`load currents or load transients. The transfer function of the grid
`with a load impedance
`in terms of grid voltage
`and in-
`Ve
`verter voltage
`is representing the plant and can be expressed
`in the -domain as (10) shown at the bottom of the page, where
`s
`is the grid impedance at nominal power.
`Zc
`Synthesis of the voltage regulator is again made in the
`-plane, using a Simulink equivalent model, where the grid
`z
`transfer function has been converted into the
`-plane using
`z
`zero-order-hold method [12]. The switching frequency is
`chosen to be 8 kHz. The pole-zero placement of the plant
`shown in Fig. 12(a) show, that there is a real pole that can be
`compensated by setting the integral time of PI-controller to
`ms. Using the root locus method [12] depicted
`0.306
`T;
`in Fig. 12(b), a gain of
`can be chosen to achieve
`KP
`0.32
`1
`a damping of the loop of
`. From the compensated
`D
`Bode-plot shown in Fig. 12(c), the bandwidth of the voltage
`controller can be determined as the minimum frequency for
`3-dB attenuation or 45 phase [12] as
`Hz.
`131
`
`0
`
`Bode Diagram
`.......... / .. ~~·~~:~ : : : : : ....
`1 F~ (Hz): 2A6
`········••i••·· ~ ( dB t; -3.02 ....
`. 1 : : ~-i r
`;
`~
`.; .. : .. :.: .. :.::• ........... :.
`
`-5
`
`al
`C!!.
`
`-15 ·.f
`IC
`I -20 ···\
`
`.2s~-~~~~~--~~~~~-~~
`
`OfT=,-:=,::;::;:m---r--r-TTTTI~-~
`
`I -90
`ffl -180 !-.. , ..... , .... , ... , __ , __ ,_,_,., ......... , ................ , ., .. , .,,, .......... _, __ • ·I
`
`~ -270 , ................... , .. , .. , .................. , ................ , ............... , ..... , ... , .. ,
`
`10'
`Frequency (Hz)
`c)
`
`10'
`
`Fig. 12. Design of the voltage controller in stand-alone control mode:
`(a) pole-zero map for the plant, (b) root-locus map for closed-loop system, and
`(c) Bode-plot of the closed loop system.
`
`The controller is now tested at very light load conditions (1%
`of nominal load) and a low damping at the resonance frequency
`of the LCL-filter was noticed as shown in Fig. 13(a). The re-
`sponse of the system depicted in Fig. 13(b) shows high oscilla-
`tions due to a high gain.
`Redesigning the controller for light load using the same tech-
`nique (root locus) leads to a lower gain of
`. The
`KP
`0.1
`Bode-plot shown in Fig. 14(a) shows much better attenuation
`at the switching and sampling frequency of 8 kHz and the step
`response depicted in Fig. 14(b) was considered acceptable in
`terms of compromise between the speed and damping of the
`higher order harmonics at low load conditions.
`From the compensated Bode-plot shown in Fig. 14(a), the
`bandwidth of the voltage controller can be obtained as
`Hz. The final parameters for the main output voltage con-
`76.5
`troller are
`,
`ms.
`0.1 I';
`0.3
`
`VII. AUTOMATIC MODE SWITCHING
`
`Switching between stand-alone and grid-connection opera-
`tion modes is done using the difference between the measured
`and the angle
`generated by the phase-
`grid voltage angle
`0
`locked loop (PLL) [5] as control variable (see Fig. 7). When
`(see Fig. 15) is exceeding a certain
`this phase error
`level grid failure is considered and the operation mode is con-
`sequently switched.
`
`(10)
`
`Vestas Ex 1010-p. 6
`Vestas v GE
`
`SGRE EX1045.0006
`
`

`

`TEODORESCU AND BLAABJERG: FLEXIBLE CONTROL OF WIND TURBINES WITH GRID FAILURE DETECTION
`
`1329
`
`Bode Diagram
`
`Step Response
`
`ci -90
`Q)
`'O
`~ -180
`OJ .c
`CL -270
`
`<I)
`
`a)
`
`2
`
`3
`Time (sec)
`
`4
`
`5
`
`6
`X 10-3
`
`b)
`
`Fig. 13. Voltage controller characteristics at 1% load in stand-alone control mode with K = 0:32: (a) Bode plot and (b) step response.
`p
`
`co
`:3.
`Q)
`'O
`
`2 ·c
`::a
`
`C)
`OJ
`
`0
`
`-5
`
`-10
`
`-15
`
`-20
`
`-25
`0
`
`Q)
`
`<I)
`
`ci
`:3.
`., -180
`OJ .c
`CL -270
`
`-90
`
`-360
`
`Bode Diagram
`
`Step Response
`
`:
`System: fz
`:
`..
`.
`:
`,
`...... ; ..... , •.. , .... : .,.,., .......... : ..... Frequency(Hz): 1.64e+003 .... ; .. .
`Magnitude (dB): -9.33
`:
`'
`:
`:
`: : : :
`:
`
`... ,........... +·
`··--( ;·· )j-j-j············(·
`---r·--r-· r · · · -.
`----r---i-- ·-r-r r i··----------:
`······'·····~ ___ : .. --~- ~- ~- ;············;·······; ····:···~--~--~- ~--:-: ........... : .. .
`. ' ' '
`. ' . .
`.
`
`:
`
`........... , ... , ... -f-. System: fz
`! '
`: Frequency (Hz): 76.5
`.. ) ... \ .. ) .• Phase (deg): -45.2
`. '
`... '
`. '
`.. '.
`' ' . '
`'
`'
`' .. '
`' ' .. ---------------------------- --
`' ' . '
`'
`'
`'
`'
`'
`'
`l l ~
`~
`j
`.
`····'··· .. ·· '·'·'· ................. .
`102
`Frequency (Hz)
`
`a)
`
`.,..~-- .. -------,---
`' '
`'
`' '
`'
`' '
`'
`' '
`'
`f~---
`······~---
`
`...............
`' '
`'
`'
`
`0.8
`
`···· •········· ·· ········--·--·(cid:173)
`
`., 0.6
`'O
`::,
`
`~ a.
`E
`<( 0.4
`
`0.2
`
`--------·······
`
`'
`'
`'
`'
`'
`'
`·· ·- ····-··················-···········--········
`.
`.
`'
`'
`'
`'
`'
`'
`'
`'
`'
`'
`'
`'
`'
`'
`'
`'
`'
`'
`'
`'
`'
`
`. ·······1·········l·········1·········\········· ........ .
`
`0.002 0.004 0.006 0.008 0.01
`
`0.012
`
`T ime (sec)
`
`b)
`
`Fig. 14. Voltage controller characteristics at 1% load in stand-alone control mode with K = 0:1: (a) Bode-plot and (b) step response.
`p
`
`q
`
`y
`
`X
`
`Fig. 15. Phase angle detection with PLL in xy-coordinate system.
`
`In grid-connection mode the system is using the PLL-gener-
`ated phase angle that is less noise sensitive than the phase angle
`-components using arctan
`directly calculated from the voltage
`dq
`function [11].
`Fig. 7 depicts the PLL loop principle. A settling time of 20 ms
`was considered in order to get a satisfied high bandwidth of
`
`is
`the PLL controller. When the grid fails, the phase error
`starting to increase and when it exceeds a certain threshold the
`system switches to stand-alone mode. In stand-alone mode the
`is integrated to
`PLL is disabled and the reference frequency
`0
`(see. Fig. 8).
`generate the angle
`The grid-connection to stand-alone transition is demon-
`strated experimentally in Fig. 16 at nominal load of 11 kW. The
`was set to 0.3 radians. Thus
`threshold for the phase error
`110
`an efficient way to detect the grid failure is achieved, and as it
`can be observed, in this case the system continues to operate
`in stand-alone mode.
`In stand-alone operation the system uses its own generated
`voltage phase angle, which is normally different from grid
`phase voltage angle. When the grid is recovered, due to the
`fact that the two voltage systems are not synchronized, a high
`voltage across the LCL filter would cause high currents to flow
`through the inverter. The high currents will trip the inverter
`and the presence of the grid is investigated by measurements.
`If the grid is recovered, the coasted inverter waits for the PLL
`to perform synchronization. The system is then considered
`
`Vestas Ex 1010-p. 7
`Vestas v GE
`
`SGRE EX1045.0007
`
`

`

`1330
`
`IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 19, NO. 5, SEPTEMBER 2004
`
`o.8 _____________ \ __________ _j _____________ l ___________ J _________ := =
`~ ,..
`
`:
`:
`:
`i:
`! ! synchronizing signal

`T ~
`i
`!
`ii
`i
`
`i
`
`o.6
`
`1.2,:-::-:::r-:7==:::::;(cid:173)
`-etheta
`------·-------·-------- ----- PLLe
`:
`:
`: :
`: :
`'
`'
`'
`'
`'
`'
`0.Bf-------+-------1------ ·--------;---,---;--------;-------;--------;-------:-------
`~
`0
`
`\ \ synchr~nizing sign~
`
`,
`
`i iTT i i :
`
`6

`
`~
`
`~ :::'-________________ , ________________ , ____ , __ ,.rr r+ '
`
`0.02
`
`0.03
`
`0.04
`
`0
`
`0.01
`t[s]
`(a)
`
`-0.2'----_L__L,_---'-----'----------'------'------'-----'-----'-----
`-0_02 -0.01
`0
`0.01 0.02 0.03 0.04 0.05 0_06 0.07 0.08
`t[s]
`(a)
`
`-0.01
`
`0
`
`0.01
`t[s]
`(b)
`4 0 0 . - - - - - -~ - -~ -~ - -~ -~ -~
`:
`:
`;
`:-ua
`
`0.02
`
`0.03
`
`0.04
`
`-20
`
`-30 L___L__L,_---'---'---'-----'----~'----~-L,_-'
`-0.02 -0.01
`0
`0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08
`t[s]
`(b)
`
`200
`
`~ 100
`0
`
`~ 0
`::::i
`oi
`::::l-100
`
`-400 L , _ _
`-0.02
`
`_L_ _ _ L,__---'------'--------'--__J
`0_02
`0.03
`0.04
`-0.01
`0.01
`0
`t[s]
`(c)
`
`-400 L___L__L,_---'-----'----------'---'-------'------'----------'-
`-0.02 -0.01
`0
`0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08
`t[s]
`(c)
`
`Fig. 16. Measured grid-connection to stand-alone transition: (a) phase error
`  (etheta) and synchronization signal (PLLe), (b) phase currents, and (c) phase
`voltages;.
`
`falls below the
`synchronized again when the phase error
`threshold and now the inverter is started in grid-connection
`mode, as it can be seen in Fig. 17 where the threshold was
`set again to 0.3 radians.
`A state-machine has been built and implemented in order to
`handle the transition between the three states: idle (I), stand-
`alone (SA), and grid-connected (GC) as depicted in Fig. 18,
`and
`represent the presence and, respectively,
`where
`Va
`/Ve
`nonpresence of the grid voltage condition, PLLe represents the
`..:10 > 0.3 radians
`, TRIP and /TRIP stands for trip
`condition
`signal enabled, and, respectively, not-enabled and START and
`
`Fig. 17. Measured stand-alone to grid-connection transition: (a) phase error
`  (etheta) and synchronization signal (PLLe),

This document is available on Docket Alarm but you must sign up to view it.


Or .

Accessing this document will incur an additional charge of $.

After purchase, you can access this document again without charge.

Accept $ Charge
throbber

Still Working On It

This document is taking longer than usual to download. This can happen if we need to contact the court directly to obtain the document and their servers are running slowly.

Give it another minute or two to complete, and then try the refresh button.

throbber

A few More Minutes ... Still Working

It can take up to 5 minutes for us to download a document if the court servers are running slowly.

Thank you for your continued patience.

This document could not be displayed.

We could not find this document within its docket. Please go back to the docket page and check the link. If that does not work, go back to the docket and refresh it to pull the newest information.

Your account does not support viewing this document.

You need a Paid Account to view this document. Click here to change your account type.

Your account does not support viewing this document.

Set your membership status to view this document.

With a Docket Alarm membership, you'll get a whole lot more, including:

  • Up-to-date information for this case.
  • Email alerts whenever there is an update.
  • Full text search for other cases.
  • Get email alerts whenever a new case matches your search.

Become a Member

One Moment Please

The filing “” is large (MB) and is being downloaded.

Please refresh this page in a few minutes to see if the filing has been downloaded. The filing will also be emailed to you when the download completes.

Your document is on its way!

If you do not receive the document in five minutes, contact support at support@docketalarm.com.

Sealed Document

We are unable to display this document, it may be under a court ordered seal.

If you have proper credentials to access the file, you may proceed directly to the court's system using your government issued username and password.


Access Government Site

We are redirecting you
to a mobile optimized page.





Document Unreadable or Corrupt

Refresh this Document
Go to the Docket

We are unable to display this document.

Refresh this Document
Go to the Docket