ecobee Technologies, ULC
`v.
`EcoFactor, Inc.
`U.S. Patent No. 8,596,550
`IPR2022-00969 and IPR2022-00983
`
`EcoFactor’s Hearing Demonstratives
`August 18, 2023
`
`
`
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
`
`
`
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`0
`
`DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`ECOBEE Exhibit 1024
`ECOBEE v. ECOFACTOR
`IPR2022-00969 and IPR2022-00983
`
`

`

`Instituted Grounds – ‘983 IPR
`
`» Ground 1: Claims 1-16
`Allegedly Obvious over Ehlers ‘330 in view of
`Wruck
`» Ground 1: Claims 9-16
`Allegedly Obvious over Ehlers ‘330 in view of
`Wruck and Harter
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`1
`
`

`

`Instituted Grounds – ‘969 IPR
`
`» Ground 1: Claims 17-23
`Allegedly Obvious over Ehlers ‘330 in view of
`Wruck
`» Ground 1: Claims 17-23
`Allegedly Obvious over Ols in view of Boait and
`Wruck
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`2
`
`

`

`Overview of Argument
`
`• Petitioner Mischaracterizes Wruck.
`•
`The “Delta Value” Is Not Explained In Wruck
`• Petitioner’s Evidence is Merely Conclusory Statements
`
`• Because of this Mischaracterization:
`• Wruck (with Ehlers or Ols and Boait) Does Not Disclose a Comparison of
`an Automated Setpoint with a Scheduled Setpoint
`There is No Motivation to Combine Wruck with Ehlers or with Ols and
`Boait
`
`•
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`3
`
`

`

`Overview of Argument
`
`• Petitioner Fundamentally Misunderstands the Teachings of
`Ehlers ’330
`• Claims 1, 9, and 17 Are Not Invalid
`•
`Ehlers and Wruck Do Not Disclose “using the stored data to predict a rate of
`change of temperatures inside the structure in response to at least changes
`in outside temperatures.”
`Ehlers and Wruck Do Not Disclose “calculating with one or more computer
`processors, scheduled programming of the thermostatic controller for one or
`more times based on the predicted rate of change, the scheduled
`programming comprising at least a first automated setpoint at a first time.”
`
`•
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`4
`
`

`

`Overview of Argument
`
`• Ols, Boait, and Wruck Do Not Invalidate Claims 17-23
`• No Motivation to Combine Ols and Boait
`• Ols and Boait Do Not Disclose “using the stored data to predict a rate of
`change of temperatures inside the structure in response to at least changes
`in outside temperatures.”
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`5
`
`

`

`‘550 Patent
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`6
`
`

`

`‘550 Patent
`
`U.S. Patent No. 8,596,550
`(“’550 Patent”)
`
`Title:
`“System, Method and Apparatus for
`Identifying Manual Inputs to and
`Adaptive Programming for a
`Thermostat”
`
`Issue Date:
`December 3, 2013
`
`Ex. 1001
`
`EcoFactor, Inc.
`
`
`
`
`
`
`
`
`
`
`
` DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`7
`
`

`

`Challenged Independent Claim 1
`
`Ex. 1001, col. 8:7-30
`
`* * *
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`8
`
`

`

`Challenged Independent Claim 9
`
`Ex. 1001, col. 8:50-9:6
`
`* * *
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`9
`
`

`

`Challenged Independent Claim 17
`
`* * *
`
`Ex. 1001, col. 9:26-10:18
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`10
`
`

`

`Cited Prior Art
`
`
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`11
`
`

`

`Ehlers ‘330
`
`U.S. Patent App. Pub. No.
`2004/0117330 (“Ehlers ‘330”)
`
`Title:
`“System and for Controlling Usage of
`a Commodity”
`
`Pub. Date:
`June 17, 2004
`
`Ex. 1004
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`12
`
`

`

`Wruck
`
`U.S. Patent App. Pub. No.
`2005/0040250 (“Wruck”)
`
`Title:
`“Transfer of Controller
`Customizations”
`
`Date:
`February 24, 2005
`
`Ex. 1005
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`13
`
`

`

`Ols
`
`U.S. Patent No. 8,374,725 (“Ols”)
`
`Title:
`“Climate Control”
`
`Date:
`February 12, 2013
`
`Ex. 1006
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`14
`
`

`

`Boait
`
`U.K. Patent App. Pub. No.
`2432016 (“Boait”)
`
`Title:
`“Transfer of Controller
`Customizations”
`
`Date:
`February 24, 2005
`
`Ex. 1007
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`15
`
`

`

`Petitioner Mischaracterizes the
`Teachings of Wruck
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`16
`
`

`

`Petitioner Mischaracterizes the Teachings of Wruck
`
`Petitioner states that:
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`983 IPR – Pet at 39.
`969 IPR – Pet. at 44.
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`17
`
`

`

`“Delta value” is Only Disclosed in Table 28
`Highlighted portion is the only reference to “Delta Value” in the entire
`Wruck disclosure.
`
`• Wruck has 48 Figures and
`260 paragraphs across over
`35 pages
`• No discussion about what
`“Delta value” means or how
`it is calculated.
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`Ex. 1005, Table 28 ¶110.
`IPR 983 – POR at 39.
`969 IPR – POR at 42
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`18
`
`

`

`“Delta value” is Only Disclosed in Table 28
`
`Wruck at ¶110:
`
`Ex. 1005, Table 28, ¶110
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`19
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`

`

`Petitioner Mischaracterizes the Teachings of Wruck
`
`• Petitioner’s Expert, Dr. Auslander,
`could not identify any support from
`the Wruck specification to support
`his position. Ex. 2008, 23:1-9
`• EcoFactor’s expert, Dr. Palmer,
`made clear “Delta value” could be
`any number of things.
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`Ex. 1022, 135:18-136:6
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`20
`
`

`

`Prior Art Does Not Disclose “compar[ing] the one or more automated setpoints
`associated with said scheduled setpoint programming with said actual setpoint
`programming”
`
`• Claim 1e; Claim 9e; Claim 17j:
`“the one or more computer processors configured to
`compare the one or more automated setpoints
`associated with said scheduled setpoint programming
`with said actual setpoint programming”
`Ex. 1001, col. 8:21-24, 57-59; col. 9:36-10:2.
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`21
`
`

`

`Wruck and Ehlers Do Not Disclose “compar[ing] the one or more automated
`setpoints associated with said scheduled setpoint programming with said
`actual setpoint programming”
`
`• There is no automated setpoint in Wruck
`• Only evidence is “Delta value” is Table 28
`• Wruck has 48 Figures, 260 paragraphs across over 35 pages
`• Only one single reference to “Delta value”
`• Not one discussion of what “Delta value” is or how it is obtained
`• Only Dr. Auslander’s conclusory opinions with the benefit of the claims
`of the ‘550 patent in front of him
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`983 IPR – POR at 38-42; Sur-reply at 17-21.
`969 IPR – POR at 41-45; Sur-reply at 17-21.
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`22
`
`

`

`“Delta value” is Only Disclosed in Table 28
`Highlighted portion is the only reference to “Delta Value” in the entire
`Wruck disclosure.
`
`• Wruck has 48 Figures,
`260 paragraphs across over
`35 pages
`• No discussion about what it
`means or how it is
`calculated.
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`Ex. 1005, Table 28 ¶110.
`983 IPR – POR at 39.
`969 IPR – POR at 42.
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`23
`
`

`

`No Motivation to Combine Ehlers and
`Wruck Or Ols, Boait and Wruck
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`24
`
`

`

`No Motivation to Combine Ehlers and Wruck
`
`Petitioner states that:
`
`Dr. Auslander states that “Wruck does just that.”
`
`But Wruck Does Not Do This.
`•
`No teaching in Wruck of Comparing
`Two Setpoints
`No teaching in Wruck of What “Delta
`value” means or how it is calculated
`No teaching in Wruck of calculating a
`setpoint
`
`•
`
`•
`
`• Tellingly, Petitioner’ Reply Does Not Address
`EcoFactor’s Arguments Regarding No
`Motivation to Combine Wruck with either
`Ehlers or Ols and Boait
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`983 IPR – Pet. at 20-21, Ex. 1002, ¶ 65.
`969 IPR – Pet. at 19; Ex. 1002, ¶ 64.
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`25
`
`Petitioner states that:
`
`

`

`Ehlers ‘330 and Wruck (and Harter )
`Do Not Render Obvious Claims 1-23
`969 IPR Ground 1
`•
`983 IPR Grounds 1 and 2
`•
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`26
`
`

`

`Petitioner Misunderstands the Teachings of Ehlers ‘330
`
`“Thermal Gain Rate” ≠ “Rate of Change in Temperature”
`
`•
`
`The “Thermal Gain Rate” Is Not The Same as a “Rate of Change
`in Temperature”
`•
`The phrase “thermal gain rate” is well understood by a POSITA as
`the rate at which energy is absorbed.
`The phrase “rate of change of temperature” is well understood to
`mean the specific change of temperature over a specific time period.
`
`•
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`983 IPR - POR at 12; Sur-reply at 4-5.
`969 IPR – POR at 14; Sur-reply at 4.
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`27
`
`

`

`Petitioner Misunderstands the Teachings of Ehlers ‘330
`Takes Fig. 3D Out of Context
`
`•
`•
`•
`
`Left Hand Label Indicates “Indoor Setpoint”
`Requires 128 minutes for Readings
`If read literally, Ehlers ‘330’s
`description would indicate that the
`thermal gain rate would be a
`continuously increasing value between
`72 and 80 (units unspecified).
`But this is not consistent with other
`discussions in Ehlers ‘330.
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`983 IPR - POR at 13-14; Sur-reply at 5-6.
`969 IPR – POR at 14-15; Sur-reply at 6-7.
`Ex. 1004, Fig. 3D.
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`28
`
`

`

`Petitioner Misunderstands the Teachings of Ehlers ‘330
`Fig. 3E Provides Necessary Context
`
`•
`•
`•
`
`Left Axis labeled “HVAC Runtime”
`Right Axis labeled “Thermal Gain Rate Per Hour”
`Horizontal Axis labeled “Intervals of Time–Hour
`Intervals”
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`983 IPR - POR at 14-16; Sur-reply at 6-8.
`969 IPR – POR at 15-17; Sur-reply at 7-9.
`Ex. 1004, Fig. 3E.
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`29
`
`

`

`Petitioner Misunderstands the Teachings of Ehlers ‘330
`Fig. 3G Provides Necessary Context
`
`• Same labels as Fig. 3E
`•
`Fig. 3G has nearly the same thermal
`gain plot as Fig. 3E, but allows indoor
`temperature to change by up to 3
`Degrees F.
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`983 IPR - POR at 16-18; Sur-reply at 8-9.
`969 IPR – POR at 17-19; Sur-reply at 9.
`Ex. 1004, Fig. 3G.
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`30
`
`

`

`Petitioner Misunderstands the Teachings of Ehlers ‘330
`Figs. 3E and 3G Provide Necessary Context
`
`•
`Fig. 3G superimposed on Fig. 3E
`• Same thermal gain rates but very
`different HVAC run % rates
`• Under Petitioner’s interpretation, the
`temperature would be increasing for
`both by 1-3 degrees per hour
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`983 IPR - POR at 18-19; Sur-reply at 9-10.
`969 IPR – POR at 19-21; Sur-reply at 9-12.
`Ex. 1004, Figs. 3E and 3G.
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`31
`
`

`

`Prior Art Does Not Disclose “using the stored data to predict a rate of change of
`temperatures inside the structure in response to at least changes in outside
`temperatures”
`
`• Claim 1c; Claim 9c; Claim 17f:
`“using the stored data to predict a rate of change of
`temperatures inside the structure in response to at least
`changes in outside temperatures”
`
`Ex. 1001, col. 8:13-15, 57-59; col. 9:36-10:2.
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`32
`
`

`

`Prior Art Does Not Disclose “us[ing] the stored data to predict changes in
`temperature inside the structure in response to at least changes in outside
`temperatures.”
`
`• Petitioner continues its error of conflating “thermal gain rate” with “rate of
`changes in temperature.”
`• But as noted, they are not the same.
`
`•
`
`The HVAC system being turned ON and functioning will not necessarily
`affect the thermal gain rate, as illustrated in Fig. 3E and Fig. 3G, discussed
`above, while it will significantly impact the rate of change of temperature.
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`983 IPR – POR at 21-22.
`969 IPR - POR at 23-24.
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`33
`
`

`

`Ehlers ‘330 Does Not Predict Changes in Inside Temperature
`Based on Changes in Outside Temperature
`
`•
`
`• Calculating a setpoint is not a prediction, it is developing an instruction for the
`control system.
`•
`A setpoint is a prediction only insofar as one might expect that when a thermostat
`receives a setpoint it will eventually control the HVAC system to achieve that
`temperature.
`In Ehlers ‘330, the user selecting the set point as well as providing “the number of
`degrees from the set point that the customer would make available to the system
`3.08.”
`•
`Based on this, the HVAC system is operated.
`•
`Not predicting a change in inside temperature based on change in outside temperature
`but merely setting a recovery time.
`983 IPR – POR at 26-27; Sur-reply at 15-16.
`969 IPR - POR at 28-29; Sur-reply at 15-16.
`Ex. 1004, ¶255.
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`34
`
`

`

`Ehlers ‘330 Does Not Predict Changes in Inside Temperature
`Based on Changes in Outside Temperature
`
`•
`
`• Calculating a recovery time is not a prediction of inside temperature based on
`changes in outside temperature.
`•
`It is merely a calculation when the HVAC system is ON and functioning.
`Ehlers ‘330 controlling inside temperature to balance occupant comfort with “energy
`savings” is not a prediction of “inside temperature based on changes in outside
`temperature.”
`•
`HVAC runtime in Figs. 3E and 3G will keep inside temperature flat.
`•
`Thus, the thermal gain rate is not a prediction of how inside temperature will behave.
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`983 IPR – POR at 24-26; Sur-reply at 12-14.
`969 IPR - POR at 26-28; Sur-reply at 12-14.
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`35
`
`

`

`Ehlers ‘330 Does Not Predict Changes in Inside Temperature
`Based on Changes in Outside Temperature
`
`• No disclosure in Ehlers ’330 of how to
`calculate ”thermal gain rate.”
`• Petitioner and Expert provide no
`support for conclusory statements
`about teachings of Ehlers ‘330.
`• At best, shows changes in
`temperature for a single, specific
`outside temperature.
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`983 IPR – POR at 27-28.
`969 IPR - POR at 29-30.
`Ex. 1004, Fig. 3D.
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`36
`
`

`

`Petitioner’s Interpretation of Ehlers ‘330 Is Incorrect
`Under Petitioner’s Interpretation, there would be a temperature increase
`of approximately 42 degrees in one 24-hour period.
`
`983 IPR – POR at 27-29; 969 IPR - POR at 29-31; Ex. 1004, Figs. 3E and 3G.
`The increase in operational runtime of the HVAC system is necessary
`to counteract the increase in thermal gain (energy absorbed by the structure)
`in order to maintain the same inside temperature consistent with the fixed setpoint.
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`37
`
`

`

`Ehlers ‘330 Does Not Predict Changes in Inside Temperature
`Based on Changes in Outside Temperature
`
`• Ehlers ’330 describes only user provided setpoints and variance.
`• Variance only used based on economic incentives.
`
`983 IPR – POR at 27-28; Sur-reply at 14-15.
`969 IPR - POR at 29-30; Sur-reply at 14-15.
`Ex. 1004, ¶256.
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`38
`
`

`

`Ehlers ‘330 Does Not Predict Changes in Inside Temperature
`Based on Changes in Outside Temperature
`
`• Ehlers ’330 recovery time is also not a predicted rate of change.
`• No disclosure in Ehlers ‘330 that recovery time is calculated base don changes
`in outside temperature.
`
`983 IPR – POR at 30-31.
`969 IPR - POR at 32-33.
`Ex. 1004, ¶246.
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`39
`
`

`

`Ehlers ‘330 Does Not Calculate a Setpoint Based on a Predict
`Rate of Change
`
`• Ehlers ’330 ramping in not a predicted rate of change.
`• Nothing indicates it is based on outside temperatures.
`• No disclosure of calculating intermediate setpoints in Ehlers
`• Rather, the system determine when to move from one setpoint
`provided by a customer to another setpoint provided by a
`customer.
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`983 IPR – POR at 33-35; Sur-reply at 14-16.
`969 IPR - POR at 35-37; Sur-reply at 14-16.
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`40
`
`

`

`Ehlers and Wruck Do Not Disclose “calculate scheduled setpoint programming …
`based on the predicted rate of change, the scheduled programming comprising one or
`more automated setpoints”
`
`• Claim 1d; Claim 9d; Claim 17g:
`“calculate scheduled setpoint programming of the
`programmable communicating thermostat for one or
`more times based on the predicted rate of change, the
`scheduled programming comprising one or more
`automated setpoints”
`
`Ex. 1001, col. 8:16-20, 8:60-64; col. 10:3-8
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`41
`
`

`

`Ehlers ‘330 Does Not Calculate a Setpoint Based on a Predict
`Rate of Change
`
`• Petitioner relies on the three automated setpoints identified
`previously for claim elements Claim 1c; Claim 9c; Claim 17f.
`
`• But as stated previously, none of these three are automated
`setpoints
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`983 IPR – POR at 31-34; Sur-reply at 14-16.
`969 IPR - POR at 34-37; Sur-reply at 14-16.
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`42
`
`

`

`Ehlers ‘330 Does Not Calculate a Setpoint Based on a Predict
`Rate of Change
`
`• Ehlers ’330 describes only user provided setpoints and variance.
`• Variance only used based on economic incentives.
`
`983 IPR – POR at 31; Sur-reply at 14-16.
`969 IPR - POR at 34; Sur-reply at 14-16.
`Ex. 1004, ¶256.
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`43
`
`

`

`Ehlers ‘330 Does Not Calculate a Setpoint Based on a Predict
`Rate of Change
`
`• Ehlers ’330 recovery time is also not a predicted rate of change.
`• No disclosure in Ehlers ‘330 that recovery time is calculated based on changes
`in outside temperature.
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`983 IPR – POR at 30-31.
`969 IPR - POR at 32-33.
`Ex. 1004, ¶246.
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`44
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`

`

`Ehlers ‘330 Does Not Predict Changes in Inside Temperature
`Based on Changes in Outside Temperature
`
`•
`
`•
`
`•
`
`Ehlers ’330 ramping in not a
`predicted rate of change.
`Nothing indicates it is based on
`outside temperatures.
`No disclosure of calculating
`intermediate setpoints in Ehlers
`•
`Rather, the system determines
`when to move from one setpoint
`provided by a customer to another
`setpoint provided by a customer.
`
`Ex. 1004, ¶325.
`
`983 IPR – POR at 27-28; Sur-reply at 14-15.
`969 IPR - POR at 29-30; Sur-reply at 14-15.
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`45
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`

`

`Ols, Boait, and Wruck
`Do Not Render Obvious Claims 17-23
`969 IPR Ground 2
`•
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`46
`
`

`

`No Motivation to Combine Ols and Boait
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`47
`
`

`

`No Motivation to Combine Ols and Boait
`Analysis Never Addresses Why A POSITA Would Make This Combination.
`
`• Ols is directed to a zone
`temperature-control system that
`controls dampers and registers to
`direct airflow.
`Boait describes controlling a
`central heating system that uses
`water or steam to control
`temperature.
`
`•
`
`969 IPR – POR at 46-49.
`
`969 IPR – Pet. at 52.
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`48
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`

`

`No Motivation to Combine Ols and Boait
`Dr. Palmer’s Testimony Does Not Support Combination
`
`•
`
`•
`
`969 IPR – Reply at 20.
`Petitioner cites to Dr. Palmer’s
`testimony.
`But Dr. Palmer’s testimony does
`not support this.
`• When asked about “types of
`heating and cooling equipment”
`he said the opposite.
`
`Ex. 1023 - Palmer Dep 141:2-16
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`49
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`

`

`Ols, Boait, and Wruck Do Not “use the stored data to predict a rate of change
`of temperatures inside the structure in response to changes in outside
`temperatures”
`
`• Claim 17f:
`“use the stored data to predict a rate of change of
`temperatures inside the structure in response to
`changes in outside temperatures”
`
`Ex. 1001, col. 9:36-10:2
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`50
`
`

`

`Ols, Boait, and Wruck Do Not “use the stored data to predict a rate of change
`of temperatures inside the structure in response to changes in outside
`temperatures”
`
`Ols explains that:
`
`969 IPR – Pet at 59
`
`• But none of the various data and
`parameters listed in Ols include changes
`in outside temperature.
`
`969 IPR – POR at 50
`
`Ex. 1006, 11:53-12:34
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`51
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`

`

`Ols, Boait, and Wruck Do Not “use the stored data to predict a rate of change
`of temperatures inside the structure in response to changes in outside
`temperatures”
`
`In my opinion, a POSITA would have understood from these disclosures that, for instance,
`the controller 124 may apply learning algorithms from historical data to take into account
`load conditions that may include outdoor climate conditions, including a change in outside
`temperature. Ols explains that “the outdoor climate conditions are used as factors for
`determining settings and actions,” and that a room load may be high when “for example,
`the sun is shining the room . . . and/or other factors that may be currently present making
`the room difficult to cool.” (Ex. 1006, 19:1-24, 12:14-34). In my opinion, a POSITA would
`have understood that outdoor climate conditions affect the ability to cool a room and could
`be considered in determining the room load. Indeed, the difference between the indoor
`and outdoor temperature was well known in the prior art to affect the rate at which a
`building loses or gains heat. (See, e.g., Ex. 1015, Book p. 200; Ex. 1016, Book p. 281).
`The learning algorithm takes into account the temperature response (or rate of change in
`the temperature) as a result of load and outdoor climate conditions.
`
`• This disclosure is about controlling the system to draw air in from outside into a
`room or dump air to the outside from a room.
`
`969 IPR – Ex. 1002, ¶ 180
`
`969 IPR – POR at 51
`
`Ex. 1006, 19:15-40
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`52
`
`

`

`Ols, Boait, and Wruck Do Not “use the stored data to predict a rate of change
`of temperatures inside the structure in response to changes in outside
`temperatures”
`Petitioner Relies on The Boait Equations.
`
`• Te is the measured external temperature
`• No mention of changes to the external
`temperature
`
`Dr. Palmer agreed:
`
`969 IPR – Pet at 61; Ex. 1007, 20.
`
`Ex. 1022, 159:7-10.
`969 IPR – POR at 53; Sur-reply at 24.
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`53
`
`

`

`Ols, Boait, and Wruck Do Not “use the stored data to predict a rate of change
`of temperatures inside the structure in response to changes in outside
`temperatures”
`New Argument Inconsistent with Disclosure of ‘550 Patent.
`
`969 IPR – Reply at 21; Ex. 1007, 20.
`
`• New argument.
`• Inconsistent with disclosure of ‘550 patent.
`
`969 IPR – POR at 53; Sur-reply at 24-25
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`Ex. 1006, 19:15-40
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`54
`
`

`

`Ols, Boait, and Wruck Do Not “use the stored data to predict a rate of change
`of temperatures inside the structure in response to changes in outside
`temperatures”
`
`969 IPR – Sur-reply at 24-25
`
`Ex. 1001, Figs. 6A and 6B.
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`55
`
`

`

`Ols, Boait, and Wruck Do Not Disclose “calculate scheduled setpoint
`programming … based on the predicted rate of change, the scheduled
`programming comprising one or more automated setpoints”
`
`• Claim 17g:
`“calculate scheduled setpoint programming of the
`programmable communicating thermostat for one or
`more times based on the predicted rate of change, the
`scheduled programming comprising one or more
`automated setpoints”
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`Ex. 1001, col. 10:3-8.
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`56
`
`

`

`Ols, Boait, and Wruck Do Not Disclose “calculate scheduled setpoint
`programming … based on the predicted rate of change, the scheduled
`programming comprising one or more automated setpoints”
`The “directives and settings” are physical configurations, not setpoints.
`
`969 IPR – Pet. at 64.
`• But the omitted portions of the Ols
`quote show that the “directives and
`settings” are physical configurations,
`not setpoints.
`969 IPR – POR at 55; Sur-reply at 26
`
`Ex. 1006, 26:27-48.
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`57
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`

`

`Ols, Boait, and Wruck Do Not Disclose “calculate scheduled setpoint
`programming … based on the predicted rate of change, the scheduled
`programming comprising one or more automated setpoints”
`Text
`
`Ols explains that:
`
`969 IPR – Pet. at 64.
`
`• But this computation is based on the humidity
`values, not on a predicted rate of change.
`• Ols describes looking up the setpoint from data
`tables from the National Oceanic and
`Atmospheric Administration.
`969 IPR – POR at 55-56; Sur-reply at 26
`
`Ex. 1006, 31:20-24.
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`58
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`

`

`Secondary Considerations
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`59
`
`

`

`Secondary Considerations
`
`•
`•
`
`Dr. Auslander was hired as a consultant by EcoFactor. Ex. 2011, 55:24-56:24.
`EcoFactor prepared a document describing work EcoFactor did with the data it
`shared with Dr. Auslander and Dr. Auslander co-wrote the forward to that
`document. Id. at 56:25-57:17
`Dr. Auslander testified “that document is probably the only one I’ve ever
`•
`really written a forward for, other than my own stuff.” Id. at 57:18-23.
`• Dr. Auslander used the EcoFactor data to “develop control systems and
`strategies for controlling structure.” Id. at 57:24-58:6.
`• Dr. Auslander work included looking at “thermal modeling” of structure
`to “create dynamic signatures in a structure … [to] understand how an
`HVAC system interacted with a particular structure.” Id. at 59:10-24.
`969 IPR – POR at 62-63; Sur-reply at 28.
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`EcoFactor, Inc. DEMONSTRATIVE EXHIBIT – NOT EVIDENCE
`
`
`
`
`
`
`
` IPR2022-00969 and IPR2022-00983 | SLIDE
`
`60
`
`

This document is available on Docket Alarm but you must sign up to view it.


Or .

Accessing this document will incur an additional charge of $.

After purchase, you can access this document again without charge.

Accept $ Charge
throbber

Still Working On It

This document is taking longer than usual to download. This can happen if we need to contact the court directly to obtain the document and their servers are running slowly.

Give it another minute or two to complete, and then try the refresh button.

throbber

A few More Minutes ... Still Working

It can take up to 5 minutes for us to download a document if the court servers are running slowly.

Thank you for your continued patience.

This document could not be displayed.

We could not find this document within its docket. Please go back to the docket page and check the link. If that does not work, go back to the docket and refresh it to pull the newest information.

Your account does not support viewing this document.

You need a Paid Account to view this document. Click here to change your account type.

Your account does not support viewing this document.

Set your membership status to view this document.

With a Docket Alarm membership, you'll get a whole lot more, including:

  • Up-to-date information for this case.
  • Email alerts whenever there is an update.
  • Full text search for other cases.
  • Get email alerts whenever a new case matches your search.

Become a Member

One Moment Please

The filing “” is large (MB) and is being downloaded.

Please refresh this page in a few minutes to see if the filing has been downloaded. The filing will also be emailed to you when the download completes.

Your document is on its way!

If you do not receive the document in five minutes, contact support at support@docketalarm.com.

Sealed Document

We are unable to display this document, it may be under a court ordered seal.

If you have proper credentials to access the file, you may proceed directly to the court's system using your government issued username and password.


Access Government Site

We are redirecting you
to a mobile optimized page.





Document Unreadable or Corrupt

Refresh this Document
Go to the Docket

We are unable to display this document.

Refresh this Document
Go to the Docket