A Contactless Power Supply
`for Photovoltaic Power Generation System
`Eun-Soo Kim1, Sung-In Kang1, Kwang-Ho Yoon1, Yoon-Ho Kim2
`1Jeonju University, 1200, Hyoja-dong, Wansan-gu, Jeonju, South Korea, E-mail:eskim@jj.ac.kr
`2Chung-Ang University, 221, Heukseok-Dong, Dongjak-Gu, Seoul, South Korea, E-main:yhkim@cau.ac.kr
`
`Abstract - Among the alternative energy sources, the solar
`energy is recognized as an important energy source and its
`application is increasing. Especially in future, the hybrid solar
`energy generation system with battery and fuel cell will be widely
`used as an independent distributed power generation system. In
`this paper, a solar power hybrid home generation system using a
`contactless power supply (CPS) that can transfer an electric power
`without any mechanical contact is proposed. The proposed system
`consists of a ZVS boost converter, a half bridge LLC resonant
`converter and contact-less transformer.
`
`I.
`
`INTRODUCTION
`
`Among the alternative energy sources, the solar energy
`generation is recognized as an important energy source and its
`application is increasing. The solar generation system interfaced
`with power utility system includes DC/DC converters and
`inverters. Normally a boost type DC/DC converter is used to
`step up the input voltage. Then the inverter is used to convert dc
`to 60 Hz ac voltage to interface with power utility and this ac
`power is converted back to dc again to be interfaced with
`various home electric systems [1]. Recently, the solar hybrid
`system with battery is widely used as an independent distributed
`power generation system. If this solar energy is converted to the
`conventional utility system, then the whole energy transfer
`system is very complicate and inefficient. In future, as shown in
`Fig 1(a), it is expected that DC power service will be widely
`used for hybrid home power generation system using solar and
`fuel cell. However, such configuration of DC power service will
`cause the surge and spark voltage when the switch is turned on
`and off for connecting and disconnecting the load. To avoid
`surge voltage and risky situation, DC link voltage for DC
`power service must be limited to be used under 50VDC.
`To solve these problems, in this paper, a hybrid home power
`generation system using contactless power supply is proposed as
`shown in Fig 1(b). The proposed system consists of a ZVS
`boost converter, a half-bridge LLC resonant converter and
`contactless
`transformer.
` However, since
`the contactless
`transformer has normally large air-gap, while the leakage
`inductance increases and magnetization inductance decreases.
`This causes low power conversion efficiency.
`To overcome such problems, a series resonant converter is
`widely used [2].
`
`(a)
`
`(b)
`Fig. 1 Hybrid Photovoltaic power generation system for DC power service
`(a) The conventional DC power service using hybrid power generation system
` (b) The proposed hybrid photovoltaic power generation system
`using contactless power supply
`
`However, the series resonant converter for the contactless
`power supply generally operates with higher switching
`frequency than resonant frequency to achieve soft switching
`under continuous resonant current mode. In this case, the main
`
`978-1-4244-1874-9/08/$25.00 ©2008 IEEE
`
`1910
`
`Authorized licensed use limited to: Tamas Szepesi. Downloaded on January 20,2022 at 11:10:49 UTC from IEEE Xplore. Restrictions apply.
`
`Ex.1014
`APPLE INC. / Page 1 of 4
`
`

`

`(a)
`
`AuxLjω
`
`SCj/1 ω
`
`1lLjω
`
`2 LjN ω
`
`2l
`
`2RN
`
`eq
`
`mLjω
`
` (b)
`Fig. 2 Half-bridge LLC resonant converter using a contactless transformer (a)
`and its equivalent circuit (b)
`
`In this paper it is assumed that the winding turns-ratio
`(N=n1/n2) is equal to '1'. From Fig. 2(b), resonant frequency (fr)
`when equivalent load resistance (Req) is in short and corner
`frequency (fo) when it is open, can be obtained.
`
`f
`
`r
`
`=
`
`π2
`
`1
`⋅
`CL
`eq
`
`f
`
`o
`
`=
`
`1
`+
`
`⋅
`C)L
`m
`

`2
`
`L(
`l
`
`1
`
` (2)
`
` (3)
`
`When an equivalent load resistance (Req) is in short, the
`equivalent leakage inductance (Leq) is expressed as
`
`L(L
`1
`l
`
`m
`
`L
`
`eq
`
`=
`
`+
`L
`l
`
`+
`LL)L
`2
`2
`l
`l
`+
`L
`
`m
`
`2
`
`m
`
` (4)
`
`Normalized frequency (fn = fs/fr) is a ratio between switching
`frequency (fs) and resonant frequency (fr).
`A is ratio between magnetization inductance (Lm) and primary
`side
`leakage
`inductance (Ll1).
` B
`is a ratio between
`magnetization inductance (Lm) and secondary side leakage
`inductance (Ll2). Q is a load quality factor.
`
`switches can achieve zero voltage switching (ZVS), but it has
`disadvantage that the secondary side diode converter cannot
`achieve zero current switching. Furthermore, due to the higher
`switching frequency operation than resonant frequency, it has
`low voltage gain and high power loss since a large primary side
`circulating current flows.
`Thus, in this paper, a contactless power supply using
`contactless transformer and half-bridge LLC resonant converter
`that achieves ZVS operation of main switches and ZCS
`operation of secondary side diodes is proposed. Since the
`proposed contactless power supply using LLC converter
`operates with lower switching frequency than the resonant
`frequency, it can achieve high voltage gain, which, in turn,
`offers low turns ratio for the transformer and high efficiency due
`to discontinuous resonant current.
`Based on the theoretical analysis and simulation results, the
`80W prototype is built and applied to the solar power generation
`system. The final experimental results are described.
`
`II. CHARACTERISTIC ANALYSIS OF HALF-BRIDGE LLC
`RESONANT CONVERTER
`
`The conventional series resonant inverter that is applied to the
`contactless transformer generally operates with higher switching
`frequency than the resonant frequency. However, in this paper,
`the resonant converter that operates with lower switching
`frequency than the resonant frequency is proposed for the
`contactless power supply. In this case, it has advantages that the
`problems of the conventional series resonant converter can be
`improved and high system efficiency can be obtained. Fig. 2(a)
`shows a structure of the contactless transformer that is applied
`to the half-bridge LLC converter. The primary side is a
`magnetic core but secondary side is an air-core. Large air-gap is
`made between the two sides. The large air-gap transformer has
`smaller magnetizing inductance and lower coupling coefficient
`(k) due to increase of primary and secondary side leakage
`inductances. In this type of transformers, it has some difficulty
`in transferring energy from primary side to secondary side due
`to the large magnetization current. Fig. 2(a) shows main circuits
`of a half-bridge resonant LLC converter and Fig. 2(b) shows its
`equivalent circuit. In Fig. 2(b), Vab is the terminal voltage of the
`half-bridge converter. C and Ll1 are primary side series capacitor
`and series leakage inductance respectively, Lm is magnetization
`inductance, and Ll2 and Req are secondary side leakage
`inductance and equivalent load resistance converted to the
`primary side respectively. The equivalent load resistance (Req)
`includes rectifier diode, capacitor filter and resistance.
`
` (1)
`
`R
`
`L
`
`8 π
`
`2
`
`R
`eq
`
`=
`
`f =
`n
`
`f
`f
`
`r
`
`1911
`
` (5)
`
`Authorized licensed use limited to: Tamas Szepesi. Downloaded on January 20,2022 at 11:10:49 UTC from IEEE Xplore. Restrictions apply.
`
`Ex.1014
`APPLE INC. / Page 2 of 4
`
`

`

`l1=
`Lm/LA
`
`l 2=
`Lm/LB
`
`
`Q
`
`=
`
`π2
`Lf
`eq
`r
`R
`
`eq
`
` (6)
`
` (7)
`
`constant 12VDC output using 84VDC output voltage of the
`ZVS boost converter.
`
`
` (8)
`
`
`Fig. 4 Main circuit of the contactless power supply
`for photovoltaic power generation system
`
`
`Table 1 shows the specifications and measured parameters of
`the designed system. Fig. 5(a) and Fig. 5(b) show experimental
`output waveforms with output power 80W, 7.2W respectively.
`
`
`
`
`Using equation (1) ~ (8), voltage gain (M) between input and
`output voltage can be expressed as given by
`
`
`M
`
`=
`
`1
`
`−+
`(A
`
`2
`
`)
`
`⋅
`
`A(
`
`+
`
`1
`f
`
`n
`
`1
`
`1
`
`B
`+
`B
`
`+
` (jQ)
`
`
`
`1
`
`+
`
`)(B
`
`f
`
`n
`
`−
`
` (9)
`
`1
`f
`
`n
`
`)
`
`Fig. 3 shows voltage gain characteristics with respect to fn and
`Q when the A and B are 0.384 and 0.00918, respectively. Fig. 3
`shows that the voltage gain characteristics of the proposed
`contactless power supply system are similar to that of the
`conventional LLC resonant converter. This means that the
`proposed system that operates lower switching frequency has
`similar voltage gain characteristics while it has advantages in
`achieving ZVS operation of the main switches and ZCS
`operation of the secondary side rectifier diodes. Thus the half-
`bridge LLC resonant converter applied to the contactless
`transformer has advantages in that it can achieve high efficiency
`characteristics and low output voltage noise.
`
`
`n1/n2=
`17/5=3.4
`
`22.54uH
`
`50nF
`
`51.95uH
`
`19.74uH
`
`25.6nH
`
`TABLE 1
` Specifications and measured parameters of half-bridge LLC resonant converter
`using a contactless transformer
`Transformer
`turn ratio(N)
`Equivalent leakage
`inductance(Leq)
`Resonant
`capacitor(C)
`Magnetic
` inductance(Lm)
`Primary side leakage
`inductance(Ll1)
`Secondary side leakage
`inductance(Ll2)
`
`Input
`voltage(Vin)
`Output
`voltage(Vo)
`Output
`power(Po)
`Resonant
`frequency(fr)
`Switching
`frequency(fs)
`Coupling
`coefficient (k)
`
`84VDC
`
`12VDC
`
`80W
`
`150kHz
`
`100~150kHz
`
`0.828
`
`
`
`
`
`Fig. 3 Voltage gain characteristics of half-bridge LLC resonant converter using a
`contactless transformer
`
`
`III. EXPERIMENTAL RESULTS
`
`Fig. 4 shows a main circuit of the contactless power supply
`for the photovoltaic home power generation system. The solar
`cell output voltage is boosted to constant 84VDC. The
`implemented LLC resonant converter is controlled to be
`
`(a)
`
`
`
`Authorized licensed use limited to: Tamas Szepesi. Downloaded on January 20,2022 at 11:10:49 UTC from IEEE Xplore. Restrictions apply.
`
`1912
`
`Ex.1014
`APPLE INC. / Page 3 of 4
`
`

`

`IV. CONCLUSION
`
`In this paper, a contactless power supply for a hybrid
`photovoltaic home power supply system is proposed to improve
`the efficiency of the conventional photovoltaic distributed
`power generation system. The prototype has been theoretically
`analyzed and then the 80W prototype has been built.
`The proposed system can reduce switching stress and improve
`system efficiency by ZVS and ZCS operation of switches and
`reducing energy conversion steps. The prototype has been tested
`successfully. The experimental results verified an important
`feature that the proposed system has efficiency over 80% by
`ZVS and ZCS operation, and can save complicate power
`conversion process compared to conventional utility system by
`directly supplying the dc power to the home electric system.
`
`
`
`ACKNOWLEDGMENT
`
`This work was supported by grant No. (R01-2005-000-11173-0)
`from the Basic Research Program of the Korea Science & Engineering
`Foundation
`
`
`
`REFERENCES
`
`[1] Lai, J,-S. "A High-Performance V6 Converter for Fuel Cell Power
`Conditioning System" Vehicle Power and Propulsion, 2005 IEEE
`Conference , sept 2005, pp 624-630.
`[2] Bo H. Cho, Ali Ghahary, " Design of A Transcutaneous Energy
`Transmission System Using A Series Resonant Converter", CH2873-8
`IEEE, pp. 1-8, 1990
`[3] Bo Yang, F.C Lee, A.J. Zhang, “LLC Resonant Converter for Front End
`DC/DC Conversion”, IEEE-APEC2002,Vol. 2, pp.1108-1112, 2002.
`[4] M.K Kazimierczuk, T. Nandakumar, “Class D voltage-switching inverter
`with tapped resonant inductor ” , IEEE Proceeding on Electric Power
`Applications, Vol. 140, pp.172-182, 1988.
`
`
`
`
`
`
`1913
`
`(b)
`Fig. 5 Experimental waveform of the voltage (Vab) and current (IT1) in the
`primary, and of the rectified current (IT2) in the secondary for the half-bridge
`LLC resonant converter using a contactless transformer
`(50V/div., 5A/div., 10A/div., 2us/div.) (a) 80W, (b) 7.2W
`
`
`
`
`Fig. 5 also shows that since the primary current (IT1) is
`lagging to the terminal voltage (Vab), and the secondary side
`rectifier current (IT2) is discontinuous, the main switches operate
`with ZVS and rectifier diodes operate with ZCS. Fig. 6 shows
`system efficiency characteristics with respect to output load
`variations. For the output power range of 7W~80W, the high
`efficiency characteristics over 80% was obtained. Fig. 7 shows
`the LCD TV and DVD player operating by the proposed
`contactless photovoltaic power generation system.
`
`
`86
`
`83
`
`Efficiency(%)
`
`80
`
`10
`
`20
`
`30
`
`40
`
`50
`
`60
`
`70
`
`80
`
`90
`
`Output Power(W)
`
`Fig. 6 Efficiency characteristics of contactless power supply
`
`
`Fig. 7 prototype
`
`
`
`Authorized licensed use limited to: Tamas Szepesi. Downloaded on January 20,2022 at 11:10:49 UTC from IEEE Xplore. Restrictions apply.
`
`Ex.1014
`APPLE INC. / Page 4 of 4
`
`

This document is available on Docket Alarm but you must sign up to view it.


Or .

Accessing this document will incur an additional charge of $.

After purchase, you can access this document again without charge.

Accept $ Charge
throbber

Still Working On It

This document is taking longer than usual to download. This can happen if we need to contact the court directly to obtain the document and their servers are running slowly.

Give it another minute or two to complete, and then try the refresh button.

throbber

A few More Minutes ... Still Working

It can take up to 5 minutes for us to download a document if the court servers are running slowly.

Thank you for your continued patience.

This document could not be displayed.

We could not find this document within its docket. Please go back to the docket page and check the link. If that does not work, go back to the docket and refresh it to pull the newest information.

Your account does not support viewing this document.

You need a Paid Account to view this document. Click here to change your account type.

Your account does not support viewing this document.

Set your membership status to view this document.

With a Docket Alarm membership, you'll get a whole lot more, including:

  • Up-to-date information for this case.
  • Email alerts whenever there is an update.
  • Full text search for other cases.
  • Get email alerts whenever a new case matches your search.

Become a Member

One Moment Please

The filing “” is large (MB) and is being downloaded.

Please refresh this page in a few minutes to see if the filing has been downloaded. The filing will also be emailed to you when the download completes.

Your document is on its way!

If you do not receive the document in five minutes, contact support at support@docketalarm.com.

Sealed Document

We are unable to display this document, it may be under a court ordered seal.

If you have proper credentials to access the file, you may proceed directly to the court's system using your government issued username and password.


Access Government Site

We are redirecting you
to a mobile optimized page.





Document Unreadable or Corrupt

Refresh this Document
Go to the Docket

We are unable to display this document.

Refresh this Document
Go to the Docket