throbber
UNITED STATES PATENT AND TRADEMARK OFFICE
`_______________
`
`BEFORE THE PATENT TRIAL AND APPEAL BOARD
`_____________
`
`GOOGLE LLC
`
`Petitioner
`
`v.
`
`ECOFACTOR, INC.
`
`(record) Patent Owner
`
`IPR2022-00538
`
`Patent No. 9,194,597
`
`REPLY DECLARATION OF RAJENDRA SHAH
`
`1
`
`GOOGLE 1021
`
`

`

`TABLE OF CONTENTS
`I. ENGAGEMENT AND INTRODUCTION ........................................................ 3
`II. ADDITIONAL OPINIONS REGARDING THE UNPATENTABILITY OF
`THE ’597 PATENT ................................................................................................... 3
`A. Ehlers’ 330’s “Thermal Gain Rates” Are Rates of Change In Inside
`Temperature Over Time .......................................................................................... 3
`B. Ehlers ’330’s Figures 3E and 3G Are Consistent With This Understanding . 11
`C. Ehlers ’330’s Thermal Gain Rates Predict a Speed that Inside Temperature
`Will Change in Response to Changes in Outside Temperature ........................... 17
`III. OATH ................................................................................................................ 27
`
`2
`
`

`

`I.
`
`ENGAGEMENT AND INTRODUCTION
`I am that same Rajendra Shah who previously submitted a declaration
`
`
`in the present Inter Partes Review in which I set forth certain opinions regarding the
`
`unpatentability of U.S. Pat. No. 9,194,597 (“the ’597 patent”) (“the First Shah
`
`Declaration”). My qualifications are set forth in the First Shah Declaration and my
`
`curriculum vitae is attached as Exhibit 1003 thereto.
`
`
`
`I understand that the Patent Trial and Appeal Board (“Board”) has
`
`issued an Order granting Google, LLC’s (“Google”) Petition for Inter Partes Review.
`
`I further understand that Dr. John A. Palmer has submitted a declaration on behalf
`
`of Patent Owner EcoFactor Inc. in this proceeding (“the Palmer Declaration”) in
`
`which he has offered certain opinions in response to the opinions set forth in the First
`
`Shah Declaration. I have reviewed the Palmer Declaration and the Exhibits cited
`
`therein. I have been asked by Google to provide additional opinions regarding the
`
`unpatentability of the ’597 patent in response to the opinions offered by Dr. Palmer.
`
`These additional opinions are set forth herein.
`
`II. ADDITIONAL OPINIONS REGARDING THE UNPATENTABILITY
`OF THE ’597 PATENT
`A. Ehlers’ 330’s “Thermal Gain Rates” Are Rates of Change In Inside
`Temperature Over Time
`As I explained in detail in the First Shah Declaration, Ehlers ’330
`
`
`teaches calculating the rate at which temperature inside a structure changes over time
`
`
`
`3
`
`

`

`at any given outside temperature (i.e., the “thermal gain rate”). Ehlers ’330
`
`illustrates this in Figure 3D, reproduced below.
`
`(Ex. 1004, Fig. 3D). As I further explained in detail in the First Shah Declaration,
`
`a POSITA would understand that in Figure 3D of Ehlers ’330, the HVAC system is
`
`“OFF” and the inside temperature is permitted to change or ‘drift’ in response to
`
`the outside temperature.1
`
`
`
`
`1 It appears that Dr. Palmer agrees with me and recognizes that that “information
`presented in Fig. 3D of Ehlers ’330 only relates to changes in temperature when
`the HVAC system is OFF” and that “the ‘thermal gain rates’ qualitatively
`illustrated in Fig. 3D are only for a building with an HVAC system turned OFF.”
`(See Ex. 2008, ¶54)(See also id. ¶56)(“Ehlers ’330 determines the thermal gain of
`
`
`
`
`4
`
`

`

`
`
`Ehlers ’330 specifically describes Figure 3D as depicting what Ehlers
`
`’330 refers to as the “thermal gain rate” of the home. Ehlers ’330 states: “the
`
`system 3.08 tracks the thermal gain rate of the home 2.18 for each set point
`
`selected over time by the customer.” (Ex. 1004, ¶0253). Ehlers ’330 goes on to
`
`state that “lines 3.12A, 3.12B, and 3.12C plot the thermal rate of gain in the site
`
`1.04 for different outside temperatures.” (Ex. 1004, ¶0253)(see also id.)(“The
`
`three trends shown as lines 3.14A, 3.14B, and 3.14C illustrate the thermal rate of
`
`gain in the home 2.18.”)(emphases added). Ehlers ’330 further states that “these
`
`graphs are drawn to illustrate the rate of thermal gain.” (Ex. 1004, ¶0253).
`
`
`
`Ehlers ’330 also explains:
`
` “[w]hile these graphs are drawn to illustrate the rate of thermal gain,
`
`they do not depict the rapid initial gain when the differential is large
`
`and the slower rate of thermal gain, which occurs as the indoor
`
`temperature reaches the outside temperature. This rate [of] thermal gain
`
`change is illustrated in FIG. 3D as plot line 3.16 which shows the
`
`
`the building under only certain conditions. Ex. 1004, ¶253, Fig. 3D. This involves,
`as Mr. Shah admits, turning the HVAC off and then measuring how much the
`inside temperature increases over time when at a certain outside temperature.”)(id.
`¶59)(“At best, the data in Fig 3D discloses the changes in inside temperature from
`a specific starting temperature and for a single, specific outside temperature when
`the HVAC system is OFF.”)(id., ¶38)(recognizing that “the slope of the line” in
`Figure 3D is the “rate of change of temperature”).
`5
`
`
`
`

`

`thermal gain for a set point of 74 degree F. and an outside temperature
`
`of 90 degrees F.”
`
`(Ex. 1004, ¶0253).
`
`
`
`I observe that Ehlers ’330 specifically states that the rate of thermal
`
`gain decreases “as the indoor temperature reaches the outside temperature.” (Ex.
`
`1004, ¶0253). A POSITA would understand that under the circumstances depicted
`
`in Figure 3D, the HVAC system is “OFF” and not cycling such that the indoor
`
`temperature is permitted to change to eventually “reach[] the outside temperature.”
`
`I observe that in no instance depicted in Figure 3D does the inside temperature
`
`exceed the outside temperature applicable to each line depicted, which is consistent
`
`with Ehlers ’330’s teachings. Nor does the inside temperature ever rise above about
`
`80 degrees F.
`
`
`
`The x axis of Figure 3D represents time in minutes and the y axis of
`
`Figure 3D represents temperature in degrees Fahrenheit. Each of the lines depicted
`
`in Figure 3D thus represents “rates” at which the temperature (y axis) in the structure
`
`changes over time (x axis). The x-axis of Figure 3D specifically suggests that
`
`temperature data be acquired every 4 minutes. In my opinion, Ehlers ’330 clearly
`
`and unequivocally uses the term “thermal gain rate” (or “rate of thermal gain” or
`
`variations thereof) to refer to the rate of change of inside temperature over time in
`
`
`
`6
`
`

`

`the structure in the context of Figure 3D. (See also, e.g., Ex. 1004, ¶0255)(“the rate
`
`of thermal gain per hour would be set at 3 degrees F. per hour”).
`
`
`
`I observe that Dr. Palmer appears to agree that the slopes of the lines
`
`depicted in Figure 3D represent rates of change of temperature. (Ex. 2008,
`
`¶38)(“The lines appear to reflect temperatures rather than rates of energy increase.”)
`
`(id., ¶38)(recognizing that “the slope of the line” in Figure 3D is the “rate of change
`
`of temperature”). As explained above, Ehlers ’330 specifically states that these lines
`
`“plot the thermal rate of gain” and “illustrate the rate of thermal gain.” (See also Ex.
`
`1004, ¶0253).
`
`
`
`Figure 3D of Ehlers ’330 illustrates the concept of thermal gain rate as
`
`a function of both inside and outside temperatures. Figure 3D visually demonstrates
`
`that for the same inside temperature, the higher the outside temperature, the greater
`
`is the rate of change of inside temperature in response to that outside temperature.
`
`Furthermore, Figure 3D also illustrates that the greater the differential between the
`
`inside and the outside temperature, the greater the thermal gain rate (the rate of
`
`change of inside temperature) will be in response. (See, e.g., Ex. 1004, ¶0253)(“This
`
`illustration is used to show the impact the set point versus outside temperature
`
`differential has over the thermal gain rate in the home 2.18.”).
`
`
`
`In my opinion, a POSITA would recognize that it would be desirable to
`
`obtain data such as that depicted in Figure 3D for a number of different inside and
`
`
`
`7
`
`

`

`outside temperatures in order to develop accurate predictions for how inside
`
`temperature changes in response to changes in outside temperature for a particular
`
`structure. In my opinion, it would have been straightforward both to acquire and to
`
`interpolate thermal gain rate data for other indoor and outdoor temperatures. Some
`
`of this data collection could be done, for example, when a system is first installed
`
`and before the building at issue is occupied. Ehlers ’330 also states that collecting
`
`and tracking of data would be done in a continuous manner. (See, e.g., Ex. 1004,
`
`¶0256). A POSITA would understand that it would be desirable to do so such that
`
`the data best represents the current characteristics of the structure.
`
` This data can be used, as taught by Ehlers ’330 to compute, for example
`
`an “average normalized thermal gain or loss for the site 1.04.” (Ex. 1004, ¶0295).
`
`It can also be used to compute, for example, the information depicted in Figure 3E
`
`(discussed in further detail below). (Ex. 1004, Fig. 3E).
`
`
`
`8
`
`

`

`
`
`Specifically, the dashed line in Figure 3E illustrates how the thermal gain rate for a
`
`structure changes over time in response to changes in outside temperature
`
`throughout the day. Based on the teachings in Ehlers ’330, in my opinion, a POSITA
`
`would understand how to collect and/or generate the kind of data depicted in Figure
`
`3D and use that data to generate thermal gain rate plots such as that depicted in
`
`Figure 3E.
`
` Dr. Palmer states that “the phrase ‘thermal gain rate’ is well understood
`
`by a POSITA to be the rate at which energy is absorbed.” (Ex. 2008, ¶37). I note
`
`that Dr. Palmer cites nothing in support of that statement. Regardless of how the
`
`term may or may not be used in other contexts, it is clear to me that within the context
`
`
`
`9
`
`

`

`of Ehlers ’330’s disclosure, Ehlers ’330 uses the term to refer to the rate of change
`
`of inside temperature over time.
`
`
`
`I also note that Ehlers ’330 measures and quantifies the “thermal gain
`
`rate” at various points. (See, e.g., Ex. 1004, ¶¶0253-256, Figs. 3D-3G). While doing
`
`so, Ehlers ’330 does not describe “thermal gain rates” as an amount or rate at which
`
`“energy is absorbed” by a structure, nor does Dr. Palmer identify any such teachings
`
`separate and apart from instruction to measure the temperature in a structure and
`
`determine the rate at which that inside temperature changes over time, and I am
`
`aware of none. Instead, Ehlers ’330 clearly uses the term “thermal gain rate” to refer
`
`to the rate of change of inside temperature in a structure over time.
`
`
`
`In describing Figure 3D, Dr. Palmer states that “[i]f read literally,
`
`Ehlers ’330’s description would indicate that the thermal gain rate would be a
`
`continuously increasing value between 72 and 80 (units unspecified).” (Ex. 2008,
`
`¶38). I disagree. A POSITA reading Figure 3D would clearly understand that the
`
`“thermal gain rate[s]” in Figure 3D are the slopes of the various lines depicted. In
`
`the straight lines depicted in Figure 3D, the thermal gain rate is, of course, a constant.
`
`Curved line 3.16, as Ehlers ’330 explains, and as I explain above, illustrates the
`
`“rapid initial gain when the differential is large and the slower rate of thermal gain,
`
`which occurs as the indoor temperature reaches the outside temperature.” (Ex. 1004,
`
`¶0253).
`
`
`
`10
`
`

`

` Ehlers ’330 teaches and a POSITA would understand that the rate of
`
`change of inside temperature, due to outside conditions, does not remain constant
`
`throughout a day. (Ex. 1004, ¶0253, Fig. 3D). As the inside temperature increases,
`
`the difference between the outside and inside temperature decreases, which causes
`
`the rate of change of inside temperature to decrease as well, as specifically illustrated
`
`in Fig 3D, Line 3.16. Also, as would be apparent to a POSITA, the outside
`
`temperature does not remain at a high level as the day progresses into the evening
`
`and night. As the outside temperature falls, so does the rate of change of inside
`
`temperature.
`
`B. Ehlers ’330’s Figures 3E and 3G Are Consistent With This
`Understanding
`In an HVAC “cycle,” the percent run time (HVAC Run %) is the
`
`
`percent of time in the cycle the HVAC system is ON and actively working to change
`
`the temperature in a structure. As is apparent to a POSITA, during normal
`
`unrestricted operation, as the HVAC system cycles “ON” and “OFF,” its % run time
`
`increases or decreases to balance the thermal gain rate of the structure—e.g., to keep
`
`the net rate of change in indoor temperature over time at or close to zero. For
`
`example, in the “cooling” context, when the HVAC system is ON and cooling, the
`
`system can reduce the temperature inside the structure despite the warming effect
`
`due to the outside conditions. A POSITA can consider this to be a “negative”
`
`
`
`11
`
`

`

`thermal gain rate that not only balances but overcomes the “positive” thermal gain
`
`rate of the structure which occurs when the system is OFF.
`
` The net effect of the operation of the system is to keep the inside
`
`temperature essentially unchanged at or near the setpoint. A POSITA knows that
`
`the purpose of an HVAC system under thermostatic control is to balance the rate of
`
`change of inside temperature due to outside conditions and to maintain the inside
`
`temperature at or near the user’s desired setpoint. In other words, the HVAC system
`
`cycles ON and OFF to effectively balance out the overall full cycle average rate of
`
`change of inside temperature at or near zero.
`
` Figure 3E of Ehlers ’330 illustrates how the daily outdoor temperature
`
`variation results in a variation in the thermal gain rate variation and a
`
`corresponding variation in HVAC run time %. A POSITA would understand that
`
`this example is in summer when the HVAC system is in the cooling mode. In
`
`Figure 3E, the horizontal axis is time in hours covering a 24-hour day. The left
`
`vertical axis is the HVAC system run time in % (i.e., the percentage of time in a
`
`cycle in which the HVAC system is ON and, in this context, cooling). The right
`
`vertical axis is the thermal gain rate in degrees Fahrenheit per hour. Ehlers ’330
`
`explains that this thermal gain rate is expected to change over the day, as graphed
`
`in the dashed line, in response to changes in outside temperatures during the day.
`
`(Ex. 1004, ¶0254). Figure 3E (and Figure 3G, discussed below) specifically depict
`
`
`
`12
`
`

`

`how the thermal gain rate changes throughout the day in response to changes in
`
`outside temperature throughout the day. (See, e.g., Ex. 1004, ¶0256)(“As the
`
`outside temperature rises, the thermal gain on the home 2.18 is monitored . . . on a
`
`continuous basis.”). Ehlers ’330’s thermal gain rates are calculated and monitored
`
`with changes in outside temperature.
`
` As shown in Figure 3E, the HVAC run time % correlates with the
`
`thermal gain rate. As Ehlers ’330 explains, the setpoint is fixed at the same level
`
`through the entire day and the HVAC system cycles “ON” and “OFF” throughout
`
`the day as necessary to maintain the inside temperature at or near the setpoint. As
`
`the time progresses from late night to morning and then afternoon, the outside
`
`temperature increases and so does the inside temperature during the periods of time
`
`in which the HVAC system is OFF. During these periods of time, the thermal gain
`
`rate of the structure is positive and increases as the temperature differential between
`
`inside and outside temperature increases. This would substantially increase the
`
`actual inside temperature itself over time, if it were not for the HVAC system
`
`delivering sufficient cooling during the periods of time in which it is ON, effectively
`
`balancing and overcoming the thermal gain rate as I describe above, to maintain the
`
`average inside temperature at or near the setpoint.
`
`
`
`In each typical HVAC cycle, during normal operation, when the system
`
`is OFF, the inside temperature increases at the thermal gain rate associated with the
`
`
`
`13
`
`

`

`applicable inside and outside temperatures (as shown in Fig. 3D). As the inside
`
`temperature increases sufficiently above the setpoint, the HVAC system turns ON
`
`and runs in cooling mode until the inside temperature cools down to the setpoint. At
`
`that point, the HVAC system turns OFF again, and the cycle repeats. This is shown
`
`in the exemplary diagram below, which I have created based on the information
`
`presented in Figure 3E. Specifically, I have chosen approximately 11 am where
`
`Figure 3E illustrates a thermal gain rate of approximately 2.5 degrees F/hour and a
`
`corresponding HVAC run % of approximately 60%.
`
`Exemplary Thermosta�c Cycle Control of HVAC System, Ehlers ‘330
`Cooling Mode, based on Fig. 3E @ ~11 am
`
`Cooling Cycle 120 min.
`
`OFF 48 min.
`
`Upper Temp. Control Limit
`
`RUN 72 min.
`60% Run Time
`
`76F
`
`74F
`
`Dead-band
`
`Inside Temperature
`
`
`
`Setpoint
`
`72F
`
`Lower Temp. Control Limit
`30
`
`0
`
`60
`
`90
`Time in Minutes
`
`120
`
`150
`
`180
`
`Example Diagram A
`
`
`
`
`
`14
`
`

`

` Thus, a POSITA would understand that the “thermal gain rates”
`
`specifically graphed in Figure 3E (as well as Figure 3G, discussed below) represent
`
`rates of change of inside temperature during the portion(s) of the cycle when the
`
`HVAC system is OFF. The HVAC run time % graphed is the percentage of the
`
`cycle that the system needs to run in order to balance or counteract that thermal gain
`
`rate. I further note that the fact that the “thermal gain rate[s]” illustrated in both
`
`Figures 3E and 3G are similar supports my interpretation. In Figures 3E and 3G, the
`
`HVAC system is operating at different amounts and thus, the effect of the HVAC
`
`system on the inside temperature should be different. However, in Figures 3E and
`
`3G, the rate of change of inside temperature when the system is “OFF” and not
`
`cooling under similar conditions would be expected to be similar.
`
`
`
`I note that Dr. Palmer suggests that Ehlers ’330 does not measure the
`
`“thermal gain rates” for a building when the HVAC system is “ON” and functioning.
`
`I observe that the challenged claims do not specifically require the system to
`
`determine the rate of change of inside temperature for a building when the HVAC
`
`system is ON and functioning.
`
` Nonetheless, in my opinion, Ehlers ’330 teaches this as well. For
`
`example, Ehlers ’330 states that “[a]s the outside temperature rises, the thermal gain
`
`on the home 2.18 is monitored along with the HVAC cycle rate on a continuous
`
`basis. The rise in the outside temperature causes the HVAC cycle time to increase
`
`
`
`15
`
`

`

`as illustrated in FIG. 3E.” (Ex. 1004, ¶0256)(Emphasis added). In my opinion, a
`
`POSITA would recognize that the “thermal gain” as well as the “HVAC cycle rate”
`
`are both being measured “on a continuous basis” and thus, the system is also
`
`measuring the thermal gain rate during periods when the status of the HVAC system
`
`is “ON”.
`
` Ehlers ’330 also states that it computes and stores a “[c]omputed
`
`thermal recovery time for heating and cooling adjusted to compensate for the
`
`external temperature.” (Ex. 1004, ¶0295)(Emphasis added). Ehlers ’330 explains
`
`that “this computed factor is used to more accurately compute the recovery time
`
`for thermal gain or loss when combined with the average normalized thermal gain
`
`or loss for the site 1.04.” (Id.)(Emphasis added). Ehlers ’330 further explains that
`
`it stores “[t]he average thermal recovery time per degree when heating and
`
`cooling systems are operational for a rolling 30, 60, and 90 day period by hour of
`
`the day.” (Ex. 1004, ¶0285)(Emphasis added). In my opinion, a POSITA would
`
`also understand from these disclosures that Ehlers ’330 computes rates of change of
`
`temperature in the structure when the system is “ON.” For example, “[t]he average
`
`thermal recovery time per degree when heating and cooling systems are operational”
`
`is a rate of time per degree of temperature (Δt/ΔT). This value can also be expressed
`
`as (ΔT/ Δt), which is the rate of temperature change over time. In my opinion, a
`
`POSITA would further understand that this rate is calculated when the HVAC
`
`
`
`16
`
`

`

`system is “ON” because the HVAC system will be on and running during at least
`
`some portion of the time during which the HVAC system is operational. A POSITA
`
`would also understand that these rates change are in response to changes in outside
`
`temperature by virtue of being adjusted to take into account the outside temperature.
`
`(Ex. 1004, ¶0295).
`
` Furthermore, as illustrated in my exemplary diagram A (above), it is
`
`also a straightforward matter to calculate the corresponding “balancing” rate of
`
`thermal gain when the system is “ON” by simply determining the rate of change that
`
`would be needed to return the inside temperature to the setpoint during the “ON”
`
`portion of a cycle. I have specifically done this for illustrative purposes with a 2-
`
`degree “normal deadband” and a cycle of 120 minutes. (See, e.g., Ex. 1004, ¶0255).
`
`C. Ehlers ’330’s Thermal Gain Rates Predict a Speed that Inside
`Temperature Will Change
`in Response to Changes
`in Outside
`Temperature
` The reason that Ehlers ’330 “tracks and learns about the thermal gain
`
`characteristics of the home” (Ex. 1004, ¶0253) is to be able to use that data to make
`
`predictions about the future behavior of the inside temperature in the home. This
`
`information is then used in controlling the system to “manage costs and comfort.”
`
`(Ex. 1004, ¶¶0252-0253).
`
` Ehlers ’330 uses the thermal gain rates as predicted rates of change in
`
`order to predict changes in inside temperature various ways.
`
`
`
`17
`
`

`

` First, one way in which Ehlers ’330 does so is when they are used to
`
`determine a new offset temperature in connection with a demand reduction request
`
`and/or reducing demand in response to a change in energy pricing. As I explain,
`
`Ehlers ’330 uses the “computed thermal gain rate” to “compute[] the required
`
`effective set point offset needed to keep the HVAC cycle run time at [a] specified
`
`trigger level.” (Ex. 1004, ¶0256). To do so, Ehlers ’330 predicts that the thermal
`
`gain rate it computed in the past represents a speed a temperature inside the first
`
`location will change in response to changes in outside temperature at the current time
`
`or at a time in the future. A POSITA would understand that the thermal gain rate is
`
`used as a predicted rate of change in the context of the example described in
`
`paragraph 256 of Ehlers ’330.
`
`
`
`In paragraph 256 of Ehlers ’330, Ehlers ’330 describes a specific
`
`example of how it “uses the thermal gain rate of the home 2.18” “to manage the
`
`demand and consumption rate at either a flat level or at some reduced level by
`
`varying the indoor air temperature within the allowable range.” (Ex. 1004, ¶0256).
`
`Ehlers ’330 describes an example in which “the set point of the thermostat is 72
`
`degrees F and the allowed variation selected by the customer is 4 degrees F. making
`
`the acceptable range for indoor temperature from 72 degrees F. to 76 degrees F.”
`
`(Ex. 1004, ¶0256). What Ehlers ’330 is describing in this example is an instance in
`
`which the customer has enabled a setting which permits the system to vary the
`
`
`
`18
`
`

`

`setpoint by up to 4 degrees (i.e., 76 degrees F) in order to save energy. (See, e.g.,
`
`Ex. 1004, ¶0255) (“In the maximum savings setting, the set point offset would be 4
`
`degrees F. which would permit the system in this example to vary the temperature
`
`in the home [from] the normal set point of 72 F by the 4 degree offset making the
`
`acceptable temperature range 72 F to 76 F within which the system 3.08 would
`
`manage the environment.”). In the example described in paragraph 256, while the
`
`customer has permitted the system to vary the setpoint by up to 4 degrees, the system
`
`need not do so if a smaller setpoint offset would accomplish the system’s energy
`
`savings goals, as explained below. (See also, e.g., Ex, 1004, ¶0141)(“ The setpoints
`
`are offset and the temperature is monitored. . . . By adjusting the setpoint of the
`
`thermostat 1.30D, the actual consumption of the HVAC system should reduce as a
`
`result of a higher setpoint for heating or cooling being established.”). This can be
`
`seen from Ehlers ’330’s statement that the system “computes the required effective
`
`set point offset needed to keep the HVAC cycle run time at the specified trigger level
`
`of 33%. (Ex. 1004, ¶0256)(emphasis added).
`
`
`
`In this example, to reduce energy consumption, the customer has
`
`specified that the HVAC system is only permitted to be “ON” for a maximum of
`
`33% of an HVAC cycle (i.e., a 33% HVAC run time). (Ex. 1004, ¶0256)(“For this
`
`example it is assumed that the customer has set the base line trigger to be set when
`
`the HVAC unit’s run time reaches 33%.”). However, at some point, in this example,
`
`
`
`19
`
`

`

`due to the increase in outside temperature in the middle of the day, the HVAC system
`
`will need to operate more than 33% of the time to cool the home to the setpoint of
`
`72 degrees. In order to maintain the maximum HVAC run time % at 33%, the system
`
`uses the thermal gain rate to compute a new setpoint somewhere between 72 and 76
`
`degrees, which will require no more than 33% cycling time to maintain. Ehlers ’330
`
`explains this process as follows:
`
`“In the early morning when it is cool, the system 3.08 in this example
`
`will be operating at a cycle rate of 10%. As the outside temperature
`
`rises, the thermal gain on the home 2.18 is monitored along with the
`
`HVAC cycle rate on a continuous basis. The rise in the outside
`
`temperature causes the HVAC cycle time to increase as illustrated in
`
`FIG. 3E. As the system 3.08 reaches the trigger level of 33% cycle run
`
`time, the base line is established and the system 3.08 using its
`
`computed thermal gain rate and the corresponding HVAC cycle
`
`run time projections, computes the required effective set point
`
`offset needed to keep the HVAC cycle run time at the specified
`
`trigger level of 33%. By adjusting the effective set point upward,
`
`the system 3.08 is able to maintain the HVAC run time at the
`
`predetermined trigger level up to the point that the thermal gain rise rate
`
`exhausts the allowed temperature variant allowed for the site 1.04.”
`
`
`
`20
`
`

`

`(Ex. 1004, ¶0256)(emphasis added)(See also, e.g., Ex, 1004, ¶0141)(“The setpoints
`
`are offset and the temperature is monitored. . . . By adjusting the setpoint of the
`
`thermostat 1.30D, the actual consumption of the HVAC system should reduce as a
`
`result of a higher setpoint for heating or cooling being established.”)(emphasis
`
`added)(Fig. 3F)(illustrating an increase in the “indoor setpoint”).
`
` Ehlers ’330 explains that Figure 3G, reproduced below, “illustrates this
`
`scenario, assuming that the thermal gain of the site 1.04 does not exhaust the allowed
`
`temperature variant for the site 1.04.” (Ex. 1004, ¶0256).
`
` At some point, despite setting the thermostat to 76 degrees Fahrenheit
`
`(the maximum setpoint allowed in this example), the inside temperature in the home
`21
`
`
`
`
`
`

`

`may be increasing too rapidly for the system to maintain a 33% HVAC run time. As
`
`can be seen in the quotation reproduced above, Ehlers ’330 describes this situation
`
`as one in which “the thermal gain rise rate exhausts the allowed temperature variant
`
`allowed for the site 1.04.” (Ex. 1004, ¶0256). As Ehlers ’330 explains, under such
`
`circumstances, the system can either allow the cycle rate to increase above 33% or
`
`allow the home to “exceed the allowed temperature.” (Ex. 1004, ¶0256).
`
` Ehlers ’330 predicts that the thermal gain rate it computed in the past
`
`represents a speed a temperature inside the first location will change in response to
`
`changes in outside temperature at the current time or at a time in the future, for
`
`example, as per a weather forecast. Thus, when Ehlers ’330 computes its thermal
`
`gain rate, it is stored as a predicted thermal gain rate for a given setpoint and a given
`
`outside temperature, which may re-occur in the future.
`
` For example, with reference to Figure 3D, given an initial setpoint
`
`starting temperature of 72 degrees F, it can be predicted that when the HVAC
`
`system is OFF and not actively working to cool the structure, the inside temperature
`
`of the structure will change at about 1 degree F per hour when the outside
`
`temperature is 77 degrees F. However, if the outside temperature changes, to for
`
`
`
`22
`
`

`

`example, 99 degrees F, it can be predicted that the inside temperature will change
`
`at a speed of about 3.9 degrees F per hour. 2
`
`
`
`In this example, Ehlers ’330 uses such predictions to determine what
`
`future setpoint would result in a thermal gain rate that would not increase HVAC
`
`run time over a future period of time. The way in which Ehlers ’330 does this is
`
`further explained below with reference to the following exemplary diagram I have
`
`created:
`
`
`
`
`2 I note that as Ehlers ’330 explains, the rates of change illustrated by the straight
`lines in Figure 3D are “drawn to illustrate the rate of thermal gain” and “do not
`depict the rapid initial gain when the differential is large and the slower rate of
`thermal gain, which occurs as the indoor temperature reaches the outside
`temperature.” (Ex. 1004, ¶0253). Accordingly, the rates of change are illustrations
`only and in reality, when measured, would vary dynamically as the inside
`temperature changes. I use the above-recited values for illustrative purposes as
`Ehlers ’330 does.
`
`
`
`23
`
`

`

`Exemplary Thermosta�c Cycle Control of HVAC System, Ehlers ‘330
`Cooling Mode, based on Fig. 3G @ ~1:30 PM
`
`Cooling Cycle 68 min.
`
`OFF 45 min.
`
`RUN 23 min.
`33% Run Time
`
`Upper Temp. Control Limit
`
`Lower Temp. Control Limit
`23
`
`0
`
`45
`
`68
`Time in Minutes
`
`90
`
`113
`
`135
`
`78F
`
`76F
`
`Dead-band
`
`Inside Temperature
`
`74F
`
`Setpoint +
`2F Offset
`(computed)
`
`Setpoint 72F
`
`Example Diagram B
`
`
`
`
`
`In the case depicted above, the HVAC system is operating in cooling
`
`mode with an exemplary cooling cycle duration of 68 minutes. During this cycle,
`
`while the system is OFF, the inside temperature increases due to the effects of the
`
`(warmer) outside temperature, and while the system is on and running, the
`
`temperature decreases due to the cooling effects of the HVAC system. In this
`
`example, the system uses the learned thermal gain rates to predict that a 33% run
`
`time will be maintained if the setpoint is allowed to change to 74 degrees F3 because
`
`if the inside temperature changes by 2.7 degrees F/hour while the system is OFF,
`
`
`3 I have chosen a 2-degree computed offset as an example. (See, e.g., Ex. 1004,
`¶0256). I have also assumed a 2-degree “normal deadband.” (See, e.g., Ex. 1004,
`¶0255).
`
`
`
`24
`
`

`

`then the system need only run for 33% of the time to recover the indoor temperature
`
`to the original setpoint. In my opinion, given Ehlers ’330’s teachings, a POSITA
`
`would understand how to use Ehlers ’330’s thermal gain rates as well as other system
`
`data to calculate an appropriate setpoint offset, thereby calculating a new setpoint
`
`for the HVAC system. Specifically, using past performance data such as that
`
`illustrated in Figures 3D and 3E, a POSITA would understand how to calculate the
`
`setpoint that would maintain a particular HVAC runtime percentage given certain
`
`predicted indoor and outdoor temperature conditions by treating the setpoint as a
`
`variable.
`
` Second, Ehlers ’330 teaches that the thermal gain rates can be used to
`
`predict recovery time. Specifically, the system uses the thermal gain rates to
`
`calculate a first time at which a certain setpoint should be implemented in order to
`
`program the system to control the inside temperature to (i.e., recover) to that setpoint
`
`by a second time. (Ex. 1004, ¶¶0246, 0268, 0285, 0295, 0119, 0319, 0324-0325).
`
`This first time can be, for example, the time at which recovery must begin (e.g., the
`
`first setpoint must be implemented) to achieve that “occupied” setpoint by a
`
`particular time. In my opinion, the use of rates of change of inside temperature to
`
`determine the optimum time at which to begin recovery was well known in the art
`
`as of the relevant time. In my opinion, in view of Ehlers ’330’s teachings, a POSITA
`
`would understand how to use the thermal gain rates as well as other system

This document is available on Docket Alarm but you must sign up to view it.


Or .

Accessing this document will incur an additional charge of $.

After purchase, you can access this document again without charge.

Accept $ Charge
throbber

Still Working On It

This document is taking longer than usual to download. This can happen if we need to contact the court directly to obtain the document and their servers are running slowly.

Give it another minute or two to complete, and then try the refresh button.

throbber

A few More Minutes ... Still Working

It can take up to 5 minutes for us to download a document if the court servers are running slowly.

Thank you for your continued patience.

This document could not be displayed.

We could not find this document within its docket. Please go back to the docket page and check the link. If that does not work, go back to the docket and refresh it to pull the newest information.

Your account does not support viewing this document.

You need a Paid Account to view this document. Click here to change your account type.

Your account does not support viewing this document.

Set your membership status to view this document.

With a Docket Alarm membership, you'll get a whole lot more, including:

  • Up-to-date information for this case.
  • Email alerts whenever there is an update.
  • Full text search for other cases.
  • Get email alerts whenever a new case matches your search.

Become a Member

One Moment Please

The filing “” is large (MB) and is being downloaded.

Please refresh this page in a few minutes to see if the filing has been downloaded. The filing will also be emailed to you when the download completes.

Your document is on its way!

If you do not receive the document in five minutes, contact support at support@docketalarm.com.

Sealed Document

We are unable to display this document, it may be under a court ordered seal.

If you have proper credentials to access the file, you may proceed directly to the court's system using your government issued username and password.


Access Government Site

We are redirecting you
to a mobile optimized page.





Document Unreadable or Corrupt

Refresh this Document
Go to the Docket

We are unable to display this document.

Refresh this Document
Go to the Docket