`
`
`
`IN THE UNITED STATES PATENT & TRADEMARK OFFICE
`______________________
`BEFORE THE PATENT TRIAL AND APPEAL BOARD
`______________________
`VESTAS-AMERICAN WIND TECHNOLOGY, INC.
`and VESTAS WIND SYSTEMS A/S,
`Petitioner,
`v.
`GENERAL ELECTRIC CO.,
`Patent Owner.
`______________________
`Case IPR2018-01015
`U.S. Patent No. 7,629,705
`______________________
`PETITIONER’S REPLY BRIEF IN SUPPORT OF ITS
`PETITION FOR INTER PARTES REVIEW OF
`U.S. PATENT NO 7,629,705
`______________________
`
`
`
`10659019
`
`
`
`
`
`
`
`
`
`TABLE OF CONTENTS
`
`Page
`
`I.
`
`II.
`
`THE DEPENDENT CLAIMS STAND OR FALL WITH THE
`INDEPENDENT CLAIMS. ................................................................... 1
`GROUND 1 TEACHES AND RENDERS OBVIOUS
`CLAIMS 1 AND 7. ................................................................................ 2
`A.
`The Art Teaches the “configuring . . .” Element of Both
`Claims. .......................................................................................... 2
`1.
`Prior Testimony of the Same Expert Patentee
`Hired for This Proceeding Establishes That ZVRT
`Does Not Require Accommodating Changes in
`Grid Phase or Frequency ................................................... 4
`Patentee’s New Position About Grid-Fault
`Characteristics Is Not Supported By Relevant
`Evidence. ............................................................................ 6
`The Deng Systems Teach Zero-Voltage Faults And
`Can Handle “Unpredictable” Post-Fault Grid
`Waveforms. ........................................................................ 9
`(a)
`Zero-Voltage Faults ................................................. 9
`(b)
`“Unpredictable” Post-Fault Waveforms ................ 12
`POSAs Would Have Combined the Static Power
`Converter of Deng ‘988 With the Wind Turbine of
`Janssen, Which Itself Uses a Static Power Converter. .............. 13
`III. GROUND 2 ANTICIPATES CLAIMS 1 AND 7. .............................. 16
`A.
`Teodorescu Does Not Disconnect During Stand-Alone
`Control Mode. ............................................................................ 17
`Teodorescu Does Not Disconnect During Idle Mode. ............... 18
`Teodorescu Concerns Zero-Voltage Grid Faults. ...................... 20
`Teodorescu Does Not Require Division by Zero During
`Zero-Voltage Faults. .................................................................. 21
`- i -
`
`2.
`
`3.
`
`B.
`
`B.
`C.
`D.
`
`10659019
`
`
`
`
`
`
`
`Page
`
`V.
`
`IV. GROUND 3A TEACHES AND RENDERS OBVIOUS
`CLAIMS 1 AND 7. .............................................................................. 21
`EON AND FERC MOTIVATE THE COMBINATIONS OF
`GROUNDS 1 AND 3A-5. .................................................................... 23
`A.
`Janssen and Erdman Disclose Wind Turbines Subject to
`EON and FERC. ......................................................................... 24
`Patentee Cites No Evidence about EON’s or FERC’s
`Applicability to Deng. ................................................................ 25
`Patentee’s Reliance on Distribution Systems Is
`Inapposite. .................................................................................. 26
`VI. CONCLUSION .................................................................................... 28
`
`
`B.
`
`C.
`
`10659019
`
`
`
`- ii -
`
`
`
`
`
`TABLE OF AUTHORITIES
`
`
`
` Page(s)
`
`Cases
`In re Am. Acad. of Sci. Tech Ctr.,
`367 F.3d 1359 (Fed. Cir. 2004) ...................................................................... 9
`Johns Manville Corp. v. Knauf Insulation, Inc.,
`IPR2015-01402, Paper 45 (PTAB Oct. 9, 2016) ............................................ 8
`Masabi Ltd. v. Bytemark, Inc.,
`IPR2017-01449 (PTAB), Paper 38 (Dec. 3, 2017) ........................................ 6
`
`10659019
`
`
`
`- iii -
`
`
`
`
`
`
`
`Upon instituting trial, the Board found a reasonable likelihood that each
`
`of the Challenged Claims—claims 1-8 of the Challenged Patent—are
`
`unpatentable.
`
`Trial afforded Patent Owner (“Patentee”) an opportunity to supplement
`
`the record with evidence of patentability. Passing on that opportunity, Patentee
`
`instead takes positions based entirely on unsubstantiated attorney argument,
`
`misapprehensions of the prior-art references at issue, and direct contradictions
`
`of representations that it and its expert previously made to the Board, to the
`
`Patent Office, and to a federal court.
`
`None of these positions, even if accepted, overcome Petitioner’s prior
`
`art. Through the trial, both parties’ experts have confirmed key factual
`
`underpinnings of Petitioner’s account of unpatentability, which facts stand
`
`unrebutted. The record now before the Board mandates—with even greater
`
`weight than the record at the time of institution—that the Board cancel each of
`
`the Challenged Claims. Petitioner therefore respectfully requests their
`
`cancellation.
`
`I.
`
`The Dependent Claims Stand or Fall with the Independent Claims.
`
`Patentee attempts no specific arguments about claims 2-6 and 8
`
`discussed in Grounds 4 and 5, leaving those claims to stand or fall with
`
`extraordinarily broad independent claims 1 and 7, the only claims substantively
`
`10659019
`
`
`
`- 1 -
`
`
`
`
`
`
`
`discussed in the Response. Paper 20 [hereinafter “POR”], 67. Patentee does
`
`not differentiate claims 1 and 7 in its argument.
`
`Patentee previously disclaimed Claims 10-12 and 15-17 upon receiving
`
`the Petition. Ex. 2001; Paper 6, 50-51. Claims 9, 13, and 14 were cancelled in
`
`earlier proceedings. Paper 2 [hereinafter “Pet.”], 1 n.1.
`
`II. Ground 1 Teaches and Renders Obvious Claims 1 and 7.
`
`Patentee argues that Ground 1 does not teach the “configuring” element
`
`of claim 1 or its claim-7 analog, see POR, 28-36, and that persons of ordinary
`
`skill in the art (“POSAs”) would not have combined the references of Ground
`
`1. Id., 23-28. Both arguments fail for multiple reasons as discussed below.
`
`A. The Art Teaches the “configuring . . .” Element of Both
`
`Claims.
`
`Petitioner has shown with evidence that Deng ‘988 and Deng ‘650 teach
`
`every element of claims 1 and 7—including the “configuring” element of claim
`
`1 and its analog in claim 7, which relate to a wind turbine that remains
`
`“electrically connected to the electric power system during and subsequent to”
`
`a voltage amplitude of the electric power system decreasing to “approximately
`
`zero volts” for a period of time.. E.g., Pet., 17-20, 23-26, 37-40, 44-47.
`
`Patentee disputes whether the art teaches the “configuring” element.
`
`POR, 35-36; see generally id., 28-36. According to Patentee, the art “describes
`
`only a solution for scenarios when its system loses sight of the normally
`- 2 -
`
`10659019
`
`
`
`
`
`
`
`
`
`operating grid voltage” because of a “condition of zero current between two
`
`points in an open circuit.” Id., 28, 30 (emphases omitted). Patentee
`
`misdescribes the art. Moreover, Patentee does not explain any import of this
`
`attempted distinction, which even if true, would be of no consequence.
`
`Instead, “Deng ‘988 teaches a specific synchronization solution that works
`
`even when the grid’s voltage amplitude drops to approximately zero volts.”
`
`Pet., 18.1
`
`Nevertheless, in other parts of the Response not directed to any claim
`
`element, Patentee argues that three-phase zero-voltage faults allegedly result in
`
`“an unpredictable waveform ‘subsequent to’ a zero-voltage event,” and that the
`
`art “simply follows the same stable, consistent voltage phase and frequency
`
`waveform during an open circuit that it synchronizes with during a ‘normal,’
`
`closed circuit condition.” POR, 22-23. To the extent Patentee contends that
`
`Petitioner’s art does not account for this alleged characteristic of zero-voltage
`
`events, extensive prior testimony of the same expert that Patentee hired for this
`
`proceeding directly belies the contention. Apart from the conclusory—and
`
`contradictory—declaration of that expert, Patentee provides no relevant
`
`evidence that could support its allegations about “unpredictable” waveforms.
`
`
`1 All emphasis in quotations is added unless otherwise noted.
`
`10659019
`
`
`
`- 3 -
`
`
`
`
`
`
`
`Moreover, Petitioner’s art clearly teaches how to handle such grid
`
`conditions should they, in fact, occur.
`
`1.
`
`Prior Testimony of the Same Expert Patentee Hired for
`
`This Proceeding Establishes That ZVRT Does Not
`
`Require Accommodating Changes in Grid Phase or
`
`Frequency.
`
`Although it is unclear whether Patentee’s allegations about zero-voltage
`
`events relate to its position about claim construction or the alleged factual
`
`content of Petitioner’s art, neither could be sustained. These allegations are
`
`directly contrary to positions Patentee and its expert here took in prior
`
`proceedings to successfully defend the Challenged Patent.
`
`That expert, Dr. Grady, previously testified that the ZVRT capabilities
`
`covered by the Challenged Claims do not require wind turbines to handle
`
`changes to grid frequency or phase at all. To the contrary, he testified that a
`
`ZVRT-capable wind turbine consistent with the Challenged Claims must not
`
`stray from the pre-fault frequency and phase of the grid if the wind turbine is to
`
`remain connected subsequent to the fault.
`
`For example, Dr. Grady testified under oath that:
`
`• In the “ZVRT” state of the Challenged Patent’s preferred embodiment,
`
`“your rotor is turning, so you tell it to pretend like [the grid]’s there,
`
`10659019
`
`
`
`- 4 -
`
`
`
`
`
`
`
`okay, start where you left off and just keep it lined up. And when it
`
`comes back on, you hope it’s synchronized in.” Ex. 1043, 57:7-58:2.
`
`• “During a zero voltage event (i.e., when the grid voltage cannot be
`
`observed), the PLL state machine facilitates driving the PLL phase angle
`
`to a value that would be in effect if there was no grid disturbance and
`
`further facilitates operating the PLL in a fixed-frequency mode. This
`
`control strategy prevents the PLL from ‘wandering’ during a zero
`
`voltage event, and, therefore, facilitates the wind turbine remaining
`
`connected during and subsequent to the zero voltage event.” Ex. 1041,
`
`¶ 41 (citation omitted).2
`
`• The fixed-frequency mode referenced above—which Dr. Grady
`
`explained “you have to switch over to . . . while the grid is not visible so
`
`that you improve your chances of being synchronized when the grid does
`
`recover,” Ex. 1043, 108:13-109:3—can be implemented without any
`
`special accommodation of the anticipated return of the grid waveform at
`
`all: “[Y]ou could just have a switch that just switched it over and say,
`
`don’t try to estimate [when] the grid frequency is gone, let’s make it
`
`play through as though nothing happened, and when the grid comes
`
`
`2 Patentee echoed this position in a legal brief. See Ex. 1042, 11-12.
`
`10659019
`
`
`
`- 5 -
`
`
`
`
`
`
`
`back you hope it’s still connected; it does not require a state machine.”
`
`Id., 58:20-59:10.
`
`These prior statements directly contradict Dr. Grady’s claims in this
`
`proceeding that the grid phase or frequency can change after a fault and that
`
`ZVRT requires special accommodation of such changes. E.g., Ex. 2012,
`
`¶¶ 14, 33, 44, 45, 46, 47, 48, 89; see Ex. 1040, ¶¶ 10-14. And even absent
`
`these contradictions, Dr. Grady’s declaration in its entirety would have
`
`warranted at most minimal weight, because it almost exclusively parrots the
`
`attorney argument in the Patent Owner Response. See, e.g., Masabi Ltd. v.
`
`Bytemark, Inc., IPR2017-01449 (PTAB), Paper 38 at 50 (Dec. 3, 2017)
`
`(“Merely repeating an argument from the P.O. Response in the declaration
`
`of an expert does not give that argument enhanced probative value.”).
`
`2.
`
`Patentee’s New Position About Grid-Fault
`
`Characteristics Is Not Supported By Relevant Evidence.
`
`Even if Patentee’s new position about alleged “unpredictable” post-fault
`
`grid waveforms could be reconciled with the contradictory testimonies of its
`
`expert, Patentee fails to provide any relevant evidence in support thereof. The
`
`scant materials Patentee cites for that proposition generally discuss only the
`
`tendency of a near-fault generator’s rotor to change its rotational frequency
`
`and phase, not the electrical waveform of the grid itself—and these mechanical
`
`10659019
`
`
`
`- 6 -
`
`
`
`
`
`
`
`generator-side issues had already been solved by prior-art LVRT wind-turbine
`
`systems that Patentee emphatically distinguishes from ZVRT.
`
`For example, Patentee cites to EON’s statement that “[o]nce a fault in
`
`the ENE network is cleared or after a three-phase automatic reclosure, the
`
`operator of a generating unit must expect that the voltages in the networks of
`
`ENE and at the network connection of the connectee could be asynchronous.”
`
`Ex. 1007, 17 (quoted in POR, 8). This describes the behavior of a generator
`
`near a zero-voltage fault, as Patentee’s own expert explains:
`
`If a generator is close to the faulted point, its voltage
`
`drops during the fault, power flow out of the
`
`generator drops, and the rotor speeds up due to power
`
`imbalance. The worst case is when the voltage
`
`output is zero, because all mechanical output power
`
`goes towards increasing [rotor] inertia via speed.
`
`This condition is referred to as asynchronous voltage
`
`and EON expressly warns that this condition can
`
`exist once the fault is cleared.
`
`Ex. 2012, ¶ 14 (citing Ex. 1007, 17). Patentee’s similar assertion elsewhere
`
`that an “aspect of the post-fault scenario is that both generator speeds and
`
`voltage phase angles will differ—often dramatically—from their pre-fault
`
`10659019
`
`
`
`- 7 -
`
`
`
`
`
`
`
`values” similarly relates on its face only to generator, not grid, behavior. POR,
`
`7-8; Ex. 2012, ¶ 14. See Ex. 1040, ¶¶ 15-18.
`
`Undermining the import of these general assertions about generators,
`
`Patentee’s expert conceded in cross-examination that during the 0.15-second
`
`ride-through period required by EON, “there’s not going to be much
`
`speedup . . . . So I don’t think speedup is going to be a very big problem in
`
`the time frame we’re talking about.” Ex. 1046, 94:22-95:10; Ex. 1040, ¶ 20.
`
`And, as discussed in the Petition and supporting materials, potential
`
`asynchronicity due to generator-side rotor speed-up of this sort had already
`
`been solved in wind turbines by LVRT-capable prior art such as Janssen and
`
`Erdman, using wind-turbine-specific techniques such as blade pitch control that
`
`counteract speed-up and others. See, e.g., Pet., 6; Ex. 1003, ¶¶ 66-67, 79, 83;
`
`Ex. 1040, ¶¶ 19, 21.
`
`Patentee cites to its expert’s ambiguous, conclusory, and unexplained
`
`discussion of “[r]eal synchrophasor measurements” (which does not cite or
`
`provide even a single such measurement). Ex. 2012 ¶ 47. Such
`
`unsubstantiated testimony should not be credited. Ex. 1040, ¶ 22; see Johns
`
`Manville Corp. v. Knauf Insulation, Inc., IPR2015-01402, Paper 45 at 16
`
`(PTAB Oct. 9, 2016) (“Dr. Smith essentially states what Patent Owner argues
`
`in the Response . . . . We give such conclusory, unsupported assertions by
`
`10659019
`
`
`
`- 8 -
`
`
`
`
`
`
`
`Patent Owner’s expert little weight.”) (citing In re Am. Acad. of Sci. Tech Ctr.,
`
`367 F.3d 1359, 1368 (Fed. Cir. 2004)).
`
`3.
`
`The Deng Systems Teach Zero-Voltage Faults And Can
`
`Handle “Unpredictable” Post-Fault Grid Waveforms.
`
`Premised on its unproven allegations about the behavior of the grid
`
`during and after three-phase zero-voltage faults, Patentee suggests that the art
`
`cannot handle such alleged behavior because it does not teach grid faults and
`
`because “Deng’s system simply follows the same stable, consistent voltage
`
`phase and frequency waveform during an open circuit condition.” POR, 22-23.
`
`Patentee’s assertion about both Deng references is incorrect. Those
`
`references specifically discuss zero-voltage faults, and “ride through” those
`
`faults with digital controllers that sample the grid thousands of times per
`
`second. Once these systems detect clearance of fault conditions, their output
`
`waveforms conform with those of the restored grid within one cycle of the grid
`
`waveform—even if that waveform has changed—as explained below.
`
`(a) Zero-Voltage Faults
`
`Patentee incorrectly argues that Deng ‘988 addresses only “open circuit”
`
`conditions and “only a solution for scenarios when its system loses sight of the
`
`normally operating grid voltage” rather than scenarios with the grid voltage
`
`itself decreasing to approximately zero volts. POR, 28, 30 (emphasis omitted).
`
`This argument disregards Deng ‘988’s express teaching about “grid voltage
`- 9 -
`
`10659019
`
`
`
`
`
`
`
`
`
`fault[s]” and “abnormal operating conditions” wherein “grid voltage is lost.”
`
`E.g., Ex. 1009, 6:20, 1:31-35; see also Ex. 1046, 135:3-14 (Patentee’s expert
`
`referring to a grid fault as “abnormal conditions”). Ex. 1040, ¶¶ 23-24.
`
`Indeed, Deng ‘988 expressly distinguishes actual grid voltage (“grid
`
`voltages Va_g, Vb_g, and Vc_g”)—which is what goes to zero in Deng ‘988—
`
`from its own measured samples of that voltage (“Va_g_k, Vb_g_k, and
`
`Vc_g_k are the sampled three-phase grid voltages of Va_g, Vb_g, Vc_g at the
`
`time step ‘k’“). Ex. 1009, 3:58-59, 4:7-9; see also id., 3:9-18. For example,
`
`Figure 5 shows a scenario with grid voltage Va_g—not the system’s
`
`measurement Va_g_k thereof—decreasing to 0, i.e., actual zero-voltage-fault
`
`conditions on the grid:
`
`Ex. 1040, ¶¶ 26-29. Thus, where Patentee incorrectly argues that “the grid
`
`voltages described in Deng ‘988 are measured from the perspective of Deng’s
`
`
`
`10659019
`
`
`
`- 10 -
`
`
`
`
`
`
`
`system,” POR 31, Patentee overlooks Deng ‘988’s express distinction between
`
`voltage measurements and actual grid behavior.
`
`Further, as can be seen in Figure 5’s depiction of grid voltage Va_g, the
`
`voltage amplitude continuously decreases before the fault voltage period and
`
`continuously increases thereafter. This waveform depicts a zero-volt grid fault
`
`condition; it is inconsistent with the abrupt “open circuit” that Patentee ascribes
`
`to Deng ‘988. Ex. 1040, ¶¶ 30-32.
`
`Finally, Patentee dwells on Deng ‘988’s example of “switch ‘bounce,’“
`
`POR, 30, but that single example does not limit the reference’s broader
`
`discussion of zero-voltage grid faults. And Deng ‘988 does not define “switch
`
`bounce” in relation to circuit breaker 16, a relationship Patentee appears to
`
`assume (but never proves). Ex. 1040, ¶¶ 23-25.
`
`In fact, Patentee interprets “switch bounce” using an inapposite
`
`definition taken from a chapter about sensors in a book on embedded
`
`microprocessors (Ex. 2019). POSAs would not understand that book to
`
`correctly define “switch bounce” in this context; for example, the “switch”
`
`referenced in Ball (Ex. 2019) is not a high-power switch used to control
`
`electrical current, but a mechanical switch used to drive a low-power input to a
`
`microprocessor. See id., 88-89; Ex. 1040, ¶ 25. Patentee’s reproduction of
`
`Ball’s Figure 3.30 on page 30 of the Response removes most of the figure,
`
`concealing this context:
`
`10659019
`
`
`
`- 11 -
`
`
`
`
`
`
`
`
`Ball does not discuss electric conversion systems or grids, which have different
`
`electrical behavior than microprocessor inputs. This context confirms Ball’s
`
`irrelevance here.
`
`(b)
`
`“Unpredictable” Post-Fault Waveforms
`
`Because both Deng references generate output waveforms digitally, they
`
`accommodate any changes to the grid waveform within one cycle thereof:
`
`“synchronization is guaranteed between an AC power source 100, such as a
`
`SPC, and a power grid 190 . . . . This is because the initial angle θ0 is equal to
`
`the actual grid voltage phase angle γ at the initiation of every cycle.” Ex. 1012,
`
`6:33-36; see also Ex. 1009, 6:4-9; Ex. 1040, ¶¶ 33-37. In other words, once the
`
`Deng systems detect recovery from a fault, their output waveform promptly
`
`10659019
`
`
`
`- 12 -
`
`
`
`
`
`
`
`conforms to the detected frequency and phase of the grid, even if these
`
`characteristics have changed. Ex. 1040, ¶¶ 38-41; see also Ex. 1003, ¶ 95.
`
`Patentee claims that Figure 5 of Deng ‘988 shows no change in the
`
`frequency or phase of the grid and therefore would not be understood to show a
`
`zero-voltage fault. But Figure 5 is an idealized example; it shows “a fault
`
`condition,” not every possible fault condition. Ex. 1009, 2:52-55. Patentee’s
`
`expert testified that an analogous figure in Janssen (Figure 1) describing
`
`exemplary fault voltage levels is “an idealized example, because they have to
`
`give – every fault is like clouds, they’re all different.” Ex. 1046, 62:6-62:14.
`
`POSAs would understand that the “abnormal operating conditions” of the Deng
`
`references could yield a number of actual waveforms and that, as the Deng
`
`references expressly state, their digital controllers can handle the concomitant
`
`grid conditions. Ex. 1040, ¶ 31.
`
`B.
`
`POSAs Would Have Combined the Static Power Converter of
`
`Deng ‘988 With the Wind Turbine of Janssen, Which Itself
`
`Uses a Static Power Converter.
`
`Patentee argues that POSAs would not have applied Deng ‘988 to wind
`
`turbines such as Janssen because “static power converters are mechanically and
`
`operationally very different than large scale electrical machines like wind
`
`turbines or power plants like wind farms.” POR, 24. But Patentee fails to
`
`respond to (let alone rebut) Petitioner’s evidence of the many reasons why
`- 13 -
`
`10659019
`
`
`
`
`
`
`
`
`
`POSAs would in fact have applied Deng ‘988’s teachings about static power
`
`converters to Janssen’s static power converter. E.g., Ex. 1003, ¶¶ 81-103. And
`
`aside from its expert’s conclusory testimony, Patentee does not provide any
`
`evidence to support its own assertion about the alleged differences.
`
`As an initial matter, wind turbines use both a generator (which generates
`
`electricity) and a static power converter (which converts that electricity to
`
`make it suitable for the grid), as Professor Blaabjerg’s annotated Figure 2 of
`
`Janssen shows below. See Ex. 1046, 100:15-18. The term “static” identifies
`
`power converters that do not use rotating elements. See Ex. 1046, 112:13-
`
`113:7, 113:9-114:12; Ex. 2020, 132:12-15; Ex. 1045, 1:36-38. POSAs “would
`
`understand that in order to work with a wind turbine, a static power converter
`
`is necessary.” Ex. 2020, 131:20-132:3, 129:3-13; Ex. 1040, ¶¶ 90-92. Indeed,
`
`Patentee’s own expert admits that Janssen uses a static power converter, Ex.
`
`1046, 111:7-113, and concedes in his declaration more broadly that “wind
`
`turbine generators do include static power conversion components.” Ex. 2012,
`
`¶ 39. These facts belie any claim that static converters or the techniques of
`
`Deng are incompatible with Janssen, let alone all wind turbines subject to
`
`ZVRT requirements as Patentee appears to claim. Ex. 1040, ¶¶ 43-48.
`
`10659019
`
`
`
`- 14 -
`
`
`
`
`
`
`
`
`Patentee’s alleged support for confusing and contrasting these distinct
`
`elements is a single statement in Deng ‘650 (which is not even part of Ground
`
`1 and thus does not support Patentee’s argument here) about generators. POR
`
`24 (citing Ex. 1012, 1:38-42). But Deng ‘650 expressly teaches that it is
`
`tackling a power conversion in power converters used with generators large
`
`and small: “As with the connection of a large power plant to an existing
`
`power grid, when connecting an additional AC power source, such as a static
`
`power converter, to a three-phase power grid, synchronization of the
`
`amplitudes, frequencies, and phase angles . . . is required.” Id., 1:48-54; see
`
`also id., Abstract; Ex. 1040, ¶¶ 49-51. This is precisely the same problem that
`
`the Challenged Patent purports to solve. See Pet., 6-7.
`
`10659019
`
`
`
`- 15 -
`
`
`
`
`
`
`
`Patentee disregards this voluminous evidence showing that POSAs
`
`would have combined Deng ‘988 with Janssen (and Deng ‘650 with Erdman),
`
`and neither Patentee nor its expert identifies even a single feature of either
`
`Deng reference that would make them unsuitable for a wind turbine subject to
`
`grid-code ZVRT requirements. See also Section V. Indeed, the Deng
`
`solutions are applicable to all AC power sources. Pet., 37; Ex. 1003, ¶¶ 148-
`
`150.
`
`III. Ground 2 Anticipates Claims 1 and 7.
`
`Petitioner has shown with evidence that Teodorescu teaches every
`
`element of the Challenged Claims. See, e.g., Pet., 27-36.
`
`Patentee responds that Teodorescu disconnects from the grid during a
`
`fault and that it does not discuss zero-voltage faults, but Patentee does not
`
`provide any evidence to support these allegations absent its expert’s conclusory
`
`testimony. Professor Blaabjerg, the senior author of Teodorescu, confirmed
`
`under cross-examination that the wind turbine of Teodorescu does not
`
`disconnect from the grid in any of its three disclosed modes: “In grid-
`
`connected mode, we are grid connected. In standalone mode, we are grid
`
`connected. In idle mode, we are grid connected, . . . .” Ex. 2020, 217:15-17;
`
`see also id., 218:8-9; 203:13-14; 207:4-5. Patentee’s expert, on the other hand,
`
`directly contradicts his own prior testimony about the crux of Patentee’s
`
`argument.
`
`10659019
`
`
`
`- 16 -
`
`
`
`
`
`
`
`A. Teodorescu Does Not Disconnect During Stand-Alone Control
`
`Mode.
`
`The Board has already rejected Patentee’s lead argument against Ground
`
`2—that the Board should simply discard the Teodorescu reference actually
`
`asserted and analyze instead a different reference, Tirumala. Institution
`
`Decision, Paper 9 [hereinafter “ID”], 59-60. Although Patentee copies nearly
`
`verbatim its previously rejected Tirumala discussion, it offers no new relevant
`
`evidence in support of that analysis. Compare Paper 6, 35-37, with POR, 38-
`
`40. It relies on a single snippet of Professor Blaabjerg’s testimony, which
`
`speaks specifically to Tirumala and offers no insight into Teodorescu. Ex.
`
`2020, 221:17-222:1; Ex. 1040, ¶¶ 53-54.
`
`The mere fact that Teodorescu cites to another paper about a system that
`
`might disconnect does not mean that Teodorescu similarly disconnects.
`
`Patentee never acknowledges the most obvious explanation for the “advantage”
`
`over Tirumala referenced in Teodorescu: Teodorescu does not need the extra
`
`switching hardware because it does not disconnect from the grid when
`
`switching modes. Ex. 1040, ¶ 55.
`
`Patentee also argues that Figure 17(b) shows that Teodorescu’s power
`
`converter “is not yet connected to the grid” during the Stand-Alone Control
`
`Mode (“SACM”) time period -0.02s to 0.00s. POR, 44 (emphasis omitted).
`
`But this assertion is belied by the figure, which shows non-zero currents ia, ib,
`- 17 -
`
`10659019
`
`
`
`
`
`
`
`
`
`and ic during that time period between the converter and the grid, as observed
`
`at nodes iA, iB, and iC in the schematic representation of Teodorescu’s system in
`
`Figure 3. Ex. 2020, 200:4-201:9. Current could not flow, of course, if the
`
`converter was disconnected from the grid, and Patentee never addresses this
`
`fundamental inconsistency between its argument and Figure 17(b). Ex. 1040,
`
`¶¶ 56-57.
`
`B.
`
`Teodorescu Does Not Disconnect During Idle Mode.
`
`Figure 17(b) shows that current continues to flow through Figure 3’s
`
`nodes iA, iB, and iC during the Idle-Mode period of 0.00s to 0.03s, disproving
`
`Patentee’s contention that “when Teodorescu’s system transitions into idle
`
`mode . . . it also controls the grid converter in such a way that current cannot
`
`flow, thus electrically disconnecting the control system from the grid.” POR,
`
`50. Professor Blaabjerg confirmed that the current is non-zero during the Idle-
`
`Mode period as a result of the system’s connection to the grid. Ex. 2020,
`
`204:2-21; Ex. 1040, ¶¶ 58-61. Patentee dismisses this evidence in a footnote of
`
`attorney argument, but offers no evidence of its own beyond an
`
`unsubstantiated, parroting expert assertion. See POR, 50 n.5; Ex. 2012, ¶ 79.
`
`The crux of Patentee’s and its expert’s argument about Idle Mode—that
`
`Teodorescu’s suspension of transistor firing in its converter somehow results in
`
`a disconnection from the grid, see POR, 49-50, Ex. 2012, ¶¶ 78-79—
`
`contradicts previous sworn testimony of that very same expert, who explained
`- 18 -
`
`10659019
`
`
`
`
`
`
`
`
`
`that such suspension is not only within the scope of the Challenged Claims but
`
`a fundamental aspect of the invention and its preferred embodiments.
`
`For example:
`
`Q. . . . Does suspending the firing of the converter
`
`mean that the converter is disconnected from the
`
`grid?
`
`A. No, it’s not disconnected at all. Like I told you,
`
`the way power electronic circuits works is, you open
`
`and close these switches, power electronic switches.
`
`They are not physically opened and closed
`
`electrically, and you are and doing it at a very high
`
`rate. Instead of doing this all the time, you simply
`
`halt for the moment, you know, and you see this big
`
`zero voltage event, it’s only going to last a fraction,
`
`you know, this long, and then when it comes back,
`
`you restart. And that is not disconnecting, it is
`
`simply suspending it.
`
`Ex. 1043, 59:11-25. Dr. Grady also confirmed that the preferred embodiments
`
`of the Challenged Patent “suspend the firing of the converter in just the right
`
`way at the right time to get you through the zero voltage ride through problem”
`
`10659019
`
`
`
`- 19 -
`
`
`
`
`
`
`
`as described in 6:14-19 of the Challenged Patent. Id., 108:13-109:1, 112:3-24;
`
`Ex. 1040, ¶¶ 62-64.
`
`Current can and does flow through the diodes in a static power converter
`
`such as that of Teodorescu. Indeed, such diodes cannot be switched off the
`
`way transistors can. Ex. 2020, 178:25-181:8; Ex. 1040, ¶¶ 65-66. Patentee
`
`attempts to discount this conductivity by arguing the diodes will not conduct
`
`current in a particular scenario, but provides no evidence to support its claim
`
`(e.g., that “the DC voltage labelled VDC in Figure [of Teodorescu] will always
`
`be controlled to be higher than the line-to-line voltage of grid connection points
`
`‘A,’ ‘B’,’ and ‘C,’“ POR, 49)—other than unsubstantiated expert testimony,
`
`which has no probative weight.
`
`C. Teodorescu Concerns Zero-Voltage Grid Faults.
`
`Patentee incorrectly argues that Teodorescu does not contemplate zero-
`
`voltage grid faults. See, e.g., POR, 37. This argument ignores Teodorescu’s
`
`identification of grid failure as its motivation. See, e.g., Ex. 1010, 1323 (“A
`
`novel automatic mode switch method . . . is developed in order to detect grid
`
`failure or recovery and switch the operation mode accordingly.”); id. (“[A]
`
`novel PLL-based method for grid failure detection and automatic mode
`
`switching is proposed where the phase difference between the grid and the
`
`inverter is used to determine grid failure and restoring.”); Ex. 1040, ¶¶ 67-70.
`
`10659019
`
`
`
`- 20 -
`
`
`
`
`
`
`
`Patentee misquotes Professor Blaabjerg’s statement that “the grid is
`
`always there.” POR, 36. Professor Blaabjerg was simply responding to
`
`insinuations that Teodorescu’s wind turbine disconnects physically from the
`
`grid when it experiences a zero-voltage fault. Ex. 1040, ¶ 71.
`
`D. Teodorescu Does Not Require Division by Zero During Zero-
`
`Voltage Faults.
`
`Finally, Patentee argues that “if the grid voltage decreased to zero due to
`
`a zero-voltage event on the grid, then grid voltage components Vx and Vy [of
`
`Equation 5] would each go down to zero,” allegedly resulting in division by
`
`zero. POR, 51. But Equation 5 of Teodorescu is inapposite during fault
`
`conditions or during SACM; it is presented only in connection with Grid-
`
`Connected Control Mode (“GCCM”), when the PLL is used to track the
`
`unfaulted grid—as made clear by the italicized heading on page 1325. When
`
`Teodorescu’s system detects impending fault conditions, it switches away from
`
`GCCM and “the PLL is disabled,” Ex. 1010, 1329. Equation 5 then no longer
`
`models the system for the duration of the fault. There is thus never any risk of
`
`division by zero. Ex. 1040, ¶¶ 72-74.
`
`IV. Ground 3A Teaches and Renders Obvious Claims 1 and 7.
`
`Patentee’s arguments against Ground 3A are the same as those it makes
`
`in Ground 1. For example, Patentee argues that “Deng ‘650’s grid never
`
`decreases to ‘approximately zero volts,’“ POR, 58-64, but, as discussed in the
`- 21 -
`
`10659019
`
`
`
`
`
`
`
`
`
`Petition, the Deng systems do tackle such grid faults. Deng ‘650, for example,
`
`discusses “fault conditions, when the PLL loses synchronization with the grid”
`
`and when “grid voltage is lost.” Ex. 1012, 1:62-2:2. Deng explains