throbber
i
`
`1;_.wejs-t.nghause_
`'
`'Eust‘Pi‘nssbu'rg'h, ‘Pehh-syliah'd .'
`
`GE 2016
`Vestas v. GE
`IPR2018-01015
`
`i
`
`

`

`Copyright 1964
`by Westinghouse Electric Corporation, East Pittsburgh, Pennsylvania
`Fourth Edition: Fourth Printing
`
`Printed in the United States of America
`
`ii
`
`

`

`348
`
`7‘ Application
`
`Chapter 11
`
`C
`
`i
`
`Relay and'cacmt—Breake
`the faulted phase only is in phase with the zero—sequenCe
`current.
`Individual overcurrent elements in the three
`be used for this selection as all three
`phases could not
`would pick up for a single line—to-ground fault on many
`solidly—grounded systems.
`
`.
`1‘
`0
`3
`
`1
`
`
`33
`
`_,
`
`,
`'
`
`
`3. A-C Generators
`
`Most a—c generators above 1000 kva and many smaller
`.
`machines are equipped with differential protection an
`ranged to trip if the currents at the two ends of each phase
`_
`
`,
`winding differ. This scheme is shown in Fig. 3.
`Smaller machines are sometimes operated without dif-
`ferential protection, but if paralleled with larger machines _
`
`EI cos (0+20 degrees) is used to re—
`12 operating against
`strict the tripping area to assist other relays in differenti—
`ating heavy load swings from faults. A reactance element,
`(x), is obtained similarly with the phase—shift devices ar—
`ranged so that the maximum—torque line is along the as
`(reactance) axis.
`Inductor—Loop Element~The inductor loop, (h), pro-
`vides a very high speed and very reliable directional ele-
`ment which has been used for many years now in high-
`speed distance measuring relays.
`basic balance—beam im-
`Balance-Beam
`pedance element is shown in (i), a balance occurring for
`E/I =Z0. For higher impedances than Z0 (current rela-
`tively lower) the contacts remain open; whereas for lower
`impedances (relatively higher currents) they close quickly.
`Since the balance is mechanical, the phase angle between
`of minor consequence, and the trip—
`voltage and current islotted on an R and X diagram is
`ping characteristic, p
`substantially a circle.
`stiC——The circu-
`Modified—Impedance Characteri
`be shifted by some circuits auxiliary
`lar characteristic may
`der to provide better
`to the element as shown in (Ir), in or
`d swing
`discrimination between fault currents and load an
`The
`currents on long, heavily—loaded transmission lines.
`al characteristic to the relay in
`shifting imparts a direction
`gion to more nearly
`addition to narrowing its tripping re
`just that required for faults.
`Circuits—~It may be
`Networks and Auxiliary
`relay elements cer—
`noted that in discussing fundamental
`ernal to the mechanical relay
`tain auxiliary circuits ext
`phase shifter; in (j), the
`have been introduced: in (g), the
`ork to produce in the
`Rectox; and in (k), a full fledged netw
`s a trend
`relay element proper, the desired currents. This i
`e as time goes on, as
`of which we shall certainly see mor
`mple current out-
`static circuits are devised to produce a si
`arious line
`put proportional to
`currents and voltages.
`11+K10’The
`Sequence—Segregating Networks,
`nts has been the key
`method of symmetrical compone
`ber of the aforemen-
`that has unlocked the door to a num
`illustrated in (r),
`tioned possibilities, some of which are
`and zero-sequence netw0rk in‘
`(8), and (t). The positive-
`d in pilot-wire relaying, where it iswhich
`(r)
`is commonly use
`the wires only one quantity,
`desired to compare over
`current irrespective of what
`is a good measure of the fault
`is A—B, A-Grd, ABC. The
`kind of fault it may be, that
`endent and widely different
`relay can be given almost indep
`using the single
`settings for phase faults and ground faults,
`be set for one ampere
`relay element. For example, it may
`itivity, but for
`ctions for one phase using the percen
`of ground fault to provide the requisite sens
`Fig. 3——Conne
`elay for generator protection.
`tion on loads.
`current to avoid Opera
`ential r
`(8).
`ten amperes of 3—phase
`'s shown in
`A negative-sequence directional element 1
`or with a system, they may be arranged to tri
`ement for ground faults on
`It is an adequate directional el
`two
`reversed flow of pOWer into the machine.
`reasonably Well—grounded systems, and requires only
`ther than three as with usual
`For differential protection the Type CA norm
`potential transformers ra
`d in the
`
`,_
`Another novel application,
`(If), is the phase—selector re— induction,
`ratio—type relays are use
`residual- directional relays.
`layto determinewhichphaseisfaulted. This information
`jority of cases, their speed (about 0.1 secondrelay“If:
`is necessary in single-pole tripping and reclosing schemes.
`severefaults) beingadequatetopreventseriousburmfi
`
`symmetrical— the iron in nearly all cases. However, a high-Spee‘i.
`e HA”, is available pm.
`
`It is predicated on the knowledge, from
`that the negative-sequence current in
`
`components theory,
`
`
`
`
`II. PROTECTIVE SCHEMES
`Protective schemes may be conveniently clasSified as
`follows :
`1. Apparatus Protection
`2. Bus Protection
`3. Line Protection
`Thus, in Fig. 1, generator and transformer protection
`come under the “Apparatus” classification; generator
`buses, high—voltage buses, and substation buses, under the
`second classification; and high—voltage transmission lines
`and feeders under “Line Protection.”
`The relay application chart, Table 2, has been included
`for ready reference in determining the operating principles
`and application of various specific relay types referred to
`throughout this chapter.
`
`CURRENT TRANSFORMER
`
`
`
`
`
`THREE PHASE A-C
`GENERATOR
`
`TYPICAL PHASE ONLY SHOWN
`
`crater-differential relay, Typ
`
`tagedifi
`
`

`

`Chapter 11
`
`Relay and Circuit-Breaker Application
`
`349
`
`
`4337019 protection and is being used with 100 per cent suc-
`
`Iess in a number of important applications.
`
`'The relay is usually arranged to trip the generator, field
`
`ircui’fl, and neutral circuit breakers (if any) simultaneously
`
`y-a manually—reset lockout relay in new installations.
`
`Frequently the relay also trips the throttle and admits
`
`00,1901“ fire prevention. For example it may be required to
`
`cordinate with other high speed relays or to reduce the
`
`hock to the systems.
`
`If a Single—winding generator (or equivalent) is con—
`
`ected to a double bus through two breakers, a current
`
`ransformer matching problem is introduced. The cur-
`
`ent transformers in the connections to the busses may
`
`Harry large currents from one bus to the other in addition
`
`'0 the generator current. Thus, matching is not assured
`
`y identical current transformers as in the simpler case of
`
`Fig. 3, and consequently,
`the Type HA relay is pre—
`
`erred for this case because of its superior discriminating
`
`qualities.
`
`The Type CO relay is also used for generator differential
`
`r'otection. It provides straight differential protection, as
`
`o'ntrasted with percentage differential, the diagram being
`
`he same as Fig. 3 without the restraining coils. Its setting
`
`must be considerably coarser than that of the CA relay be-
`
`ause there are no restraining coils to desensitize it when
`
`'_i_gh-through—fault currents are flowing.
`
`:_ Double-Winding and Multiple-Winding Gener-
`
`ators—The differential protection scheme of Fig. 3 does
`
`not detect turn—to—turn short circuits within the winding
`
`because the entering and leaving currents of a phase re-
`
`main equal. Double and multiple winding machines pro-
`
`Vi'de a means for obtaining such protection in the larger,
`
`more important generators. The currents in the parallel
`
`branches, become unequal when turns are short circuited
`
`. one branch. The differential relays, Type CA or HA,
`
`Tan 'be arranged to detect shorted turns, grounds* or
`
`phase-to-phase faults, by placing one current transformer
`
`11 the neutral end of one of the parallel windings, and one
`
`(if double ratio at the line end in the combined circuit. The
`
`{hoice of schemes depends somewhat on the facility with
`
`Which leads can be brought out and the necessity of over—
`
`ping the generator breaker. With hydrogen cooling
`
`additional leads can be brought out through the necessary
`asetight bushings only with considerable difficulty, and
`
`ally there is no space for transformers inside the hydro-
`
`
`
`
`
`
`Efiect of the Method of Grounding—The method
`grounding the generator neutral affects the protection
`Orded by differential relays. For example, if sufficient
`unding impedance is used so that a ground fault at the
`nerator terminals draws full load current, then for a
`It at the midpoint of the winding, where the normal
`tags to ground is half as great, the fault current will be
`proximately one—half the full load current. When a
`11nd fault occurs 10 percent from the neutral end of the
`
`lidlng, the fault current, being limited largely by the
`
`litral impedance, is about 10 percent of full load current.
`1's corresponds to the sensitivity of a 10 percent differ—
`tlal relay and, therefore, represents the limit of protec—
`I.1 for phase to ground faults with such a relay. For
`With the same limitations as for a singlewinding generator.
`
`
`
`
`lower impedance grounding the differential relay protects
`closer to the neutral. With higher impedance grounding,
`the limit of protection for ground faults is farther from
`the neutral end, and for an ungrounded machine,
`the
`differential protection is ineffective against ground faults.
`The protection afforded for phase-to—phase, double-phase-
`to-ground, or three—phase faults is relatively unaffected by
`the method of grounding. A complete discussion of the
`methods of grounding is given in Chap. 19.
`Solidly Grounded and Low Resistance or React-
`ance Grounded Machineulf the generator is solidly
`grounded, or grounded through a reactor or resistor, draw-
`ing at least full—load current for a ground fault at a line
`terminal, the usual 10 percent differential relay operates
`for practically any short circuit within the machine and
`for grounds to within 10 percent of the neutral, or closer
`if the ground current is higher.
`Ungrounded, and Potential-Transformer-
`Grounded Generators—arethosegroundedonlythrough
`the natural capacitance from the metallically connected
`windings, buswork, and cables to ground. The potential
`transformer from neutral to ground, if properly appliedT,
`serves as a measuring device only. To insure that this is
`so, it must be liberally designed so that under no condition
`will its exciting current become appreciable compared with
`the charging current to ground. Otherwise,
`ferro-reso—
`nance may occur. Usually a full line-to—line rated trans—
`former will suffice. The potential transformer and a volt—
`age relay such as the SV (instantaneous) or CV (inverse
`time) may be used to initiate an alarm or optionally to
`trip. Or, on lower voltages, a static voltage unbalance
`indicator may be used connected directly to the primary
`circuit. Such an instrument is the Type G. These devices
`supplement the generator differential protection to provide
`indication or tripping for ground faults. Light resistance
`grounding as covered in the next section is generally pre—
`ferred to ungrounded operation.
`Light-Resistance-Grounded Generators — This
`scheme and an associated protective arrangement is i1-
`lustrated in Fig. 29 of Chap. 19.
`Indication from avolt-
`age relay, connected in parallel with the resistor as shown,
`or from a current relay, such as the Type BG, connected
`in series with the resistor, may be used to sound an alarm
`or to trip, depending on the application. Combinations
`of sensitive alarm and coarser trip, or of alarm and time—
`delay trip, have also been used. The latter gives time
`to transfer the load to another machine at the hazard of
`operating with a fault on one phase.
`This scheme was designed primarily for the unit station
`arrangement in which a generator and step—up transformer
`are operated as a unit without an intervening bus. How“
`ever, it can also be used where an intervening bus carries
`the station service transformer and one or two short feeder
`cables. A limited amount of selectivity is possible by the
`use of a polarized relay, such as the CWP—l, which obtains
`most of its energy from a potential coil in parallel with the
`grounding resistor. Such a relay used in the station—service
`feed, for example, can detect a ground on that circuit.
`Field Protection—While a large number of machines
`still operate without any protective relays to function on
`TSee also Light-Resistance—Grounded Generators.
`
`

`

`358
`
`Relay and Circuit-Breaker Application
`
`Chapter 11
`
`notations as to relay types and settings, these symbols
`compress the otherwise complicated picture of complete
`system protection into a form that can be readily visual—
`ized. The standard symbols are given in Table 3. Their
`use has been illustrated in Fig. 12.
`
`TABLE 3—RELAY SYMBOLS
`
`(a) SYMBOLS FROM THE ASA STANDARDS.
`OVERCURRENT
`4—- DIRECTIONAL OVERGURRENT ——->
`OVERVOLTAGE
`
`
`
`UNDERVOLTAGE
`
`DISTANCE
`
`BALANCED OR
`
`OVER FREQUENCY
`
`UNDER FREQUENCY
`
`OVER TEMPERATURE
`
`BALANCED PHASE
`
`PILOT WIRE (CURRENT
`DIFFERENTIAL)
`
`PILOT WIRE (DIRECTIONAL
`COMPARISON)
`
`CARRIER PILOT
`
`-a
`
`s.WWhummuswrw-Wlwwxm”calculusnun.
`
`Relative Number of different kinds of faults\
`The relative numbers of different types of faults vary Wide
`1y with such factors as relative insulation to ground and
`between phases, circuit configuration, the use of ground
`wires, voltage class, method of grounding, speed of fault
`clearing, isokeraunic level*, atmospheric conditions, qua}-
`ity of construction and local conditions. Thus the figures
`given below serve merely to indicate the order of preva.
`lence and emphasize that there are usually a great many'
`more line—to—ground faults than faults of other types.
`Three—Phase Faults
`5 percent
`Two—Line—to—Ground Faults
`10 percent
`Line-to—Line Faults
`15 percent
`Line—to—Ground Faults
`70 percent
`
`Total
`
`100 percent
`
`10. Overcurrent Protection
`
`The general plan of coordination with overcurrent relays
`on a radial system is shown in Fig. 13. The time shown in
`each case is the fastest operating time for a fault at the 10-
`cation of the next device in sequence. At lighter generat-
`ing capacity the fault currents are reduced and all Operat-
`
`.
`
`(IO-0.5 Sec.
`CO~0;__5.SBC. c...-
`7] *
`CO-1.Q§ec.
`O-
`
`
`
`H
`
`CO~0‘.7—5’Sec_.
`
`g
`
`CO-0.§—§CC.
`
`' }Feeders
`
`S C Inst.
`
`GROUND DIRECTIONAL WITH INSTANTANEOUS ATTACHMENT
`DIRECTIONALLY CONTROLLED
`
`Fig. 13—Coordination of overcurrent protection on a radial
`power system.
`
`Where the operation of a relay Is conditional upon the flow of ground
`current (residual or zero sequence) this shall be indicated by prefixing
`the ground symbol
`thus:-
`
`Residual Overcurrenf -i||¢-——— Directional Residuai 0vercurrent~rtl—————>
`
`Other prefixes such as ® and GD to indicate operation on positive
`or negative phase sequence quantities, and suffixes to indicate the
`relay types,
`inclusion of
`instantaneous trip attachments, etc. may be
`added at
`the discretion of
`the user.
`
`(b) FREQUENTLY USED VARIATIONS OF THE STANDARD SYMBOLS.
`OVERCURRENT GROUND WITH INSTANTANEOUS ATTACHMENT
`
`BUS GROUND DIFFERENTIAL
`
`POWER DIRECTIONAL WITH INSTANTANEOUS ATTACHMENT
`DIRECTIONALLY CONTROLLED
`
`BUS CURRENT DIFFERENTIAL
`
`9. Fault Frequency and Distribution
`
`About 300 disturbances (or one per ten miles) occurred
`per year in a typical system operating 3000 miles of llO-kv
`circuit. This system used mostly overcurrent and direc-
`tional relays, and in a 4-year period experienced 2800 relay
`operations of which
`
`92.2 percent were correct and desired
`5.3 percent were correct but undesired
`2.1 percent were wrong tripping operations
`0.4 percent were failure to trip
`
`The faults were as follows:
`
`56 percent
`Lightning
`Sleet, Wind, Jumping Conductors 11 percent
`Apparatus Failure
`11 percent
`Close-in on Fault
`11 percent
`Miscellaneous
`11 percent
`
`
`
`
`
`
`ing times increase, but because of the inverse time charac-
`teristics of the relay the margins between successive relays _
`also increase.
`'
`
`Relays used with feeder circuit breakers must be coor-..
`dinated with fuses of distribution transformers and with
`the main and branch line sectionalizing fuses.83 Several
`
`characteristic curve shapes are available in different 66-
`
`signs of the induction-type overcurrent relays as illustrated:
`
`in Fig. 14. These provide latitude in selecting the relayg.
`
`'
`that coordinates best with the fuse curves at the current
`
`involved.
`
`The definite minimum time characteristic provides a.
`ready means for coordinating several relays in series w1th
`
`.
`only an approximate knowledge of the maximum current,
`and results in relatively small increase in the relay time as
`the fault current is lowered. It is used in the maJ'oritY_9_f
`overcurrent relay applications. The inverse and very 1n-'
`verse characteristics are sometimes more favorable Where
`close coordination with fuses is required. They also .make
`it possible to take advantage of the reduction of maXIImlm
`
`fault current as distance from the power source increases
`
`Several relays in series can be set for the same time for
`
`*Number of storm-days per year
`
`
`
`
`
`
`
`
`

`

`Chapter 11
`
`Relay and Circuit-Breaker Application
`
`359
`
`
`
`WIIIII:
`IflflIIIII
`. IIIIIIIII
`II
`
`IHNIIII
`II
`IHWIIIIII
`IflHIIII
`II
`II
`IHIIIII
`IMIRIIII
`I
`IHEHIIIIIIIIIIIIIIII
`IIHIEIQIIIIIIIIIIIII
`III-==III-====!!!lll
`
`
`
`
`
`
`
`TimeinSeconds
`
`
`
`
`
`
`12
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`Immediately beyond the relay and still provide the
`(3025 second or more margin for fault beyond the
`:ay'beeause 0f the lower current value for fault in-
`ation. For example the timing on curve (b), Fig.
`
`bles when the current is reduced from 700 percent
`'ercent of pick—up value. Several settings of 0 3 sec-
`0 percent could be used1n series While still having
`
`d margin between successive relays if the fault
`opped1n the ratio 7 to 4 between successive loca-
`
`
`
`
`
`
`
`
` .500-
`
`1000
`
`1500
`
`
`2000
`
`Fig. l4—Characteristics of various induction type overcurrent relays.
`
`Percent of Pick Up Current
`
`--a)' Type OOH.
`) Very inverse-low energy relay, Type CO.
`
`nice of relaysis also influencedin certain cases by
`' urden of the “low energy” and “very inverse”
`
`aleSpeed Impedance Relay*
`'—d.iStance tripping characteristic of the Type
`peed directional distance relay1s illustrated1n
`ch shows a number of line sections in series.
`ually well be a loop, the two ends of the section
`at the same supply point. The tripping time
`increasesin direct proportion to the distance
`Y to the fault, except that the minimum time
`mind for a fault at the relay. Each relay1s
`OWard the high-speed impedance relay describedIn
`mter'mediate voltage transmission lines.
`
`
`(c) Inverse—10W energy relay, Type CO.
`(d) Standard, definite minimum time, Type CO relay.
`
`Trip Time for Bkr. fit 1
`
`
`
` Distan ce—p—
`
`Fig. 15—Time-distance curves of the Type CZ relay. The slope
`of the curve is changed by varying the resistance in series with
`the potential coil. The minimum operating time with zero
`voltage on the relay is about Mr sec.
`
`adjusted to trip in approximately % second for a fault at
`the next bus, except as Will be noted.
`It is essential that for a fault near bus 4, breaker No. 3
`be tripped in preference to breaker No. 1. Thus the oper—
`ating time of relay No. 1 must exceed that of relay N o. 3
`for fault at location No. 4 by one circuit breaker operating
`time plus margin. For 8—cycle breakers a reasonable break—
`er time plus margin is 0.4 second.
`
`

`

`CHAPTER 14
`
`POWER SYSTEM VOLTAGES AND CURRENTS DURING
`ABNORMAL CONDITIONS
`
`Original Author:
`R. L. Witzke
`
`Revised by:
`
`R. L. Witzke
`
`FOR manyyears it was commonpractice tobase the
`
`requirements of system apparatus on normal load
`conditions and on three-phase short circuits. More
`or less empirical multiplying factors were sometimes used
`to predict the probable ground—fault currents from the
`three—phase fault currents. However,
`this procedure is
`unsatisfactory because the relations between three-phase
`and ground—fault currents vary greatly between systems.
`In some systems the current for a single line—to-ground
`fault is less than normal load current, whereas, in other
`systems, or at other locations in the same systems, the
`current for a single line-to—ground fault is larger than the
`three—phase fault current. The analysis of power systems
`by symmetrical components1 (see Chap. 2) has made pos-
`sible the accurate calculation of fault currents and voltages
`for unsymmetrical faults directly from system constants.
`Under many conditions the voltages present on a power
`system may be higher than those calculated for steady—
`state conditions. These higher voltages are usually of a
`transient nature and exist during the transition from one
`steady-state condition to another. Transient voltages can
`be produced by simple circuit changes such as the opening
`of a circuit breaker or the grounding of a conductor, or
`they can be produced by an intermittent arc in a circuit
`breaker or in a fault. Usually the higher voltages are
`associated with intermittent arcs rather than with simple
`circuit changes without arcing. Most transient voltages
`are not of large magnitude but may still be important
`because of
`their effect on the performance of circuit—
`interrupting equipment and protective devices. An appre-
`ciable number of these transient voltages are of sufficient
`magnitude to cause insulation breakdown_
`The various factors that determine the magnitudes of
`currents and voltages in power systems during abnormal
`conditions will be discussed in this chapter.
`I. STEADY-STATE VOLTAGES AND CURRENTS
`DURING FAULT CONDITIONS
`1. Assumptions
`Voltages and currents producedunder fault conditions
`are a function of the type of fault and the ratios of the
`sequence impedances. The effect of these factors on the
`voltages and currents produced can be shown by sets of
`curves as will be done here. The four types of faults il—
`lustrated in Fig. 1 will be considered. It is assumed that
`the network is symmetrical to the point of fault, F, and
`can be reduced to series impedances, Z1, Z2, and Z, for
`
`.
`3 PHASE FAULT
`“-‘L‘L 0R 31"“
`
`7
`SINGLE LINE-T07 GROUND
`FAULT (L's)
`
`
`
`.
`
`496
`
`
`.
`LINE_TO_UNE FAULT--
`DOUBLE L|NE_T0_GR'OUND
`(L—L)
`.
`FAULT (n-6,
`
`'
`'
`Fig. l—Types of faults on three-phase systems; I
`.
`
`.
`--
`-
`-
`the positive—, negative-, and zero-sequence netWOl'kSi If?"
`
`spectively. In the present analysis the fault-'reslstance- 15"
`represented by R and is not included in Z0. 'Zo 11101119135 3‘.
`3
`
`zero-sequence resistance 130 the point 0f fault but (1065;12:011-
`include the fault resistance. It is further assumed that“
`
`
`the generated emfs can be reduced to a single 903E ‘57
`sequence emf, E
`
`2- Formulas
`.
`_
`.
`
`In Tables 1 and 2 are given the formulasl‘ for'caflfi"
`the line currents and line—to—ground voltages for the
`
`illustrated in Fig. 1. These formulas are 99111131109“
`such an extent that it is difficult to Vis_uallZ§3'1_"_3
`
`currents and voltages that can be produced 113d?
`conditions for ranges of system constants. For '13.-
`
`the currents and voltages have been malculated.f‘;J
`*Formulas taken from pages 224 and 226 of referel_1_0_e -
`
`
`
`

`

`Chapter 14
`
`Power System Voltages and Currents During Abnormal Conditions
`
`497
`
`
`
`
`
`ratios of system constants and the results are presented as
`a series of curves.
`
`3. Range of Sequence Impedances Considered
`
`4. Fault Current and Voltage Curves
`Curves prepared in accordance with the preceding dis—
`cussion are plotted in Figs. 2 to 6 inclusive. In these figures
`the fault current is plotted as a ratio of the three—phase
`short—circuit, and the line—to—ground and line-to—line volt—
`ages are plotted as a ratio to their respective normal values.
`In Figs. 2, 3, and 4 all resistances are equal to zero.
`Figs. 2 and 3 show the ranges of line currents and line—to-
`
`The principal impedances that usually apply to tran-
`
`sient conditions are the positive—sequence impedance Z1,
`
`the negative-sequence impedance Z2, and the zero—sequence
`impedance Z0, each consisting of a resistance and a react-
`
`ance component.
`In general, the positive—sequence resist—
`ance R1 and the negative—sequence resistance R2 are small
`
`in comparison to the positive— and negative—sequence re-
`actances. Consequently, the effect of these two resistances
`
`on the magnitude of the voltages and currents during fault
`conditions is small. For this reason and because of compli—
`
`cations introduced by considering positive— and negative—
`sequence resistances, these factors will be neglected. Zero—
`
`sequence resistance R0 and zero—sequence reactance X0 can
`vary through wide ranges depending on the type of system
`grounding used, hence the curves are arranged to cover a
`Wide range of zero-sequence resistance and zero—sequence
`
`reactance.
`
`
`
`The positive—sequence reactance that applies to tran—
`
`sient conditions may be either the sub—transient or the
`
`transient reactance depending on whether or not the initial
`
`high decrement component of the current is to be consid—
`
`ered or neglected. The ratio of X2 to X1 for commercial
`
`machines usually lies between 0.5 and 15, although with
`' special machines it is possible to exceed this range. The
`
`higher ratios of X2 to X1 are in machines without dampers
`
`_whereas the lower ratios are in machines with dampers
`
`or their equivalent.
`In general calculations it is usually
`
`_ permissible to assume a ratio of X2/X1 of unity especially
`If an appreciable percentage of the negative-sequence re—
`
`actance to the point of fault is in static apparatus or trans-
`
`mission lines. The general curves are limited to ratios
`of X2 to X1 within the range of 0.5 to 1.5; the formulas
`In Tables 1 and 2 can be used for ratios outside of this
`
`2.0
`
`1.8
`
`u.
`M
`1.2
`
`g
`3
`t 10
`0018
`
`0‘6
`04
`'
`0.2
`
`
`
`‘
`_
`
`
`
`
`
`
`
`
`
`
`r
`I
`i
`,
`
`
`
`
`I
`I
`T
`'
`l‘
`’ZL‘G short-c:rcui+~§—i: 0.5
`
`I
`I
`X l
`'ZL-G shori- circuit
`-x—2-=l40
`
`I
`
`‘I
`
`..
`
`I
`
`-
`
`_
`
`ZL-G shod-circuit %—=l5
`I
`I
`I
`,
`.
`I
`|
`L-G short-circui't X1(X =0.5"I.0" 1.5 '
`\
`I
`
`4'
`
`+
`
`00
`
`l
`
`2
`
`3
`Rad-i0 Xq/Xg
`
`4
`
`5
`
`6 CD
`
`Fig. 2—Curves of fault currents vs. system reactances for
`single and double line-to—ground faults. Each curve is labeled
`to indicate the type of fault and the ratio of Xg/Xl. All cur-
`rents are expressed as a ratio to the three-phase short-circuit
`current. For these curves, all resistances are assumed equal
`to zerol.
`
`ground voltages respectively for single and double line-to—I
`ground faults for ratios of Xo/X1 from zero to six. The
`ranges of fault current and fault voltages for ratios of
`X2/X1 between 0.5 and 1.5 are shown in Fig. 4.
`.
`R
`The ranges of fault current for ratlos of X2 between zero
`1
`and six are given in Fig. 5. In this figure the ratio X2/X1
`
`
`
`
`
`
`
`
`TABLE 1~FAULT CURRENTS
`
`Au=X1X2+Xo(X1~I—X2)
`
`
`Type of fault
`Vector expression, effect of fault resistance included
`Milfiggriiggfisfi Euérsrgs 1V(1)1en
`_
`_
`_ _ g _
`
`Three— h
`................
`= Er;
`= = =E$
`p ase
`Ia Z1+
`Is.
`It
`Io X1
`
`_
`_ —j\/§Eg
`*
`e-to—hne ................
`Ib‘zl+zg+R
`1b=102fl
`—
`X1+X2
`Ic -— -—Ib
`
`€19 line—to—ground ........
`Ia =4E’g—
`= ——'3-Eg—
`Zo+zl+zz+3R
`1“ xo+xl+x2
`
`_
`.
`'
`— 3E
`—
`-.———
`1. = Tip{van—42L) +1(220+zz+3RL—-6R.>]
`1b =1. = “if vXa+XoX2+X§
`
`
`— $14]
`—
`.
`3E
`lZI:\/3(Z2 RL)
`Ic— 21/311
`J<2Z° I Z2+3RL“6Rg):I
`Ig=A_MgX2
`Ig=1b+Ic=3lo
`
`—3E
`= A1) g(Z2 +RL)
`Av‘(Z1 I RL)(Z2 I RI.) I (Z1 I Z2 I 2RL)(Z0 I RL I 3Rg)
`
`-
`
`,
`uble line-to—ground .......
`
`
`
`figsitive-sequence impedance to the point of fault
`gatlve—sequence impedance to the point of fault
`
`zero'SGQUence impedance to the point of fault and does not include any fault resistance
`99 Fig. 1 for definitions of R, RL and R.
`
`
`
`
`
`
`
`
`
`

This document is available on Docket Alarm but you must sign up to view it.


Or .

Accessing this document will incur an additional charge of $.

After purchase, you can access this document again without charge.

Accept $ Charge
throbber

Still Working On It

This document is taking longer than usual to download. This can happen if we need to contact the court directly to obtain the document and their servers are running slowly.

Give it another minute or two to complete, and then try the refresh button.

throbber

A few More Minutes ... Still Working

It can take up to 5 minutes for us to download a document if the court servers are running slowly.

Thank you for your continued patience.

This document could not be displayed.

We could not find this document within its docket. Please go back to the docket page and check the link. If that does not work, go back to the docket and refresh it to pull the newest information.

Your account does not support viewing this document.

You need a Paid Account to view this document. Click here to change your account type.

Your account does not support viewing this document.

Set your membership status to view this document.

With a Docket Alarm membership, you'll get a whole lot more, including:

  • Up-to-date information for this case.
  • Email alerts whenever there is an update.
  • Full text search for other cases.
  • Get email alerts whenever a new case matches your search.

Become a Member

One Moment Please

The filing “” is large (MB) and is being downloaded.

Please refresh this page in a few minutes to see if the filing has been downloaded. The filing will also be emailed to you when the download completes.

Your document is on its way!

If you do not receive the document in five minutes, contact support at support@docketalarm.com.

Sealed Document

We are unable to display this document, it may be under a court ordered seal.

If you have proper credentials to access the file, you may proceed directly to the court's system using your government issued username and password.


Access Government Site

We are redirecting you
to a mobile optimized page.





Document Unreadable or Corrupt

Refresh this Document
Go to the Docket

We are unable to display this document.

Refresh this Document
Go to the Docket