throbber
Electric Power Systems
`
`Third Edition
`
`B. M. WEEDY
`
`Department cj'Electrical Engineering,
`The Universig/ (j Southampton
`
`
`
`JOHN WILEY 8; SONS
`
`GE2014
`CHICHESTER NEW YORK BRISBANE TORONTO Vestasv.GE
`|PR2018-01015
`
`GE 2014
`Vestas v. GE
`IPR2018-01015
`
`i
`
`

`

`Copyright © 1967, 1972, 1979 by John Wiley & Sons Ltd.
`
`All rights reserved.
`
`No part of this book may be reproduced by any means, nor
`transmitted, nor translated into a machine language without the
`written permission of the publisher.
`
`Library of Congress Cataloging in Publication Data:
`
`Weedy, Birron Mathew
`Electric power systems—w3rd ed.
`1. Electric power transmission
`I. Title
`
`621.319’1
`
`TK3001
`
`79-40081
`
`ISBN 0 471 27584 0
`
`Printed in Great Britain by J. W. Arrowsmith Ltd.,
`Winterstoke Road, Bristol B83 ZNT
`
`ii
`
`

`

`246
`
`7
`
`Fault Analysis
`
`7.1
`
`Introduction
`
`An essential part of the design of a power supply network is the calculation of
`the currents which flow in the components when faults of various types occur.
`In a fault survey, faults are applied at various points in the network and the
`resulting currents obtained by hand calculation, or, more likely now on large
`networks, by analogue or digital processes. The magnitude of the fault currents
`give the engineer the current settings for the protection to be used and the
`ratings of the circuit breakers.
`if” The types of fault commonly occurring in practice are illustrated1n Figure
`57.1 and the most common of theseis the short circuit of a single conductor to
`earth. Often the path to earth contains resistance in the form of an are as shown
`;
`in Figure 7.1(f). Although the single line to earth fault is the most common,
`:1
`calculations are frequently performed with the three-line, balanced short
`l
`circuit (Figure 7.1(d) and (e)). This is the most severe fault and also the most
`2“agamenable to calculation. The causes of faults are summarized in Table 7.1
`
`(a; j: (b)
`
`T
`
`E
`
`I
`
`1:;9"
`
`Figure 7.1 Common types of fault.
`
`246
`
`

`

`247
`
`Table 7.1 Causes of overhead~line faults, British system
`66 kV and above
`
`Faults/160 km
`of line
`
`
`Lightning
`Dew, Fog, Frost
`Snow, ice
`Gales
`
`Salt spray
`
`Total
`
`1.59
`0.15
`0.01
`0.24
`
`0.01
`
`2 faults per 160 km giving a
`total of 232 faults on system
`
`which gives the distribution of faults due to various causes on the British
`Central Electricity Generating Board system in a typical year. Table 7.2 shows
`the components affected. In tropical countries the incidence of lightning is
`much greater than in Britain, resulting in larger numbers of faults.
`
`Table 7.2 Distribution of faults, British system
`
`Type
`
`Number of faults
`
`Overhead lines
`Cables
`
`Switchgear
`Transformers
`
`Total
`
`289
`67
`
`56
`59
`
`471
`
`As well as fault current, fault MVA is frequently considered; this is obtained
`from the expression \/(3) VLIF X 10~6 fault, where VL is the nominal line voltage
`of the faulted part. The fault MVA is often referred to as the fault level; The
`calculation of fault currents can be divided into the following two main types.
`
`three phases when the network remains
`(a) Faults short-circuiting all
`these calculations normal
`single-phase
`balanced electrically. For
`equivalent circuits may be used as in ordinary load-flow calculations.
`(b) Faults other than three~phase short circuits when the network is elec—
`trically unbalanced. To facilitate these calculations a Special method for
`dealing with unbalanced networks is used known as the method of
`symmetrical components.
`
`The main objects of fault analysis may be enumerated as follows:
`
`1. To determine maximum and minimum three-phase short—circuit cur-
`rents.
`
`2. To determine the unsymmetrical fault current for single and double
`Iine-to-earth, Iine—to—line faults, and open—circuit faults.
`3. Investigation of the operation of protective relays.
`
`

`

`248
`
`4. Determination of rated rupturing capacity of breakers.
`5. To determine fault-current distribution and busbar—voltage levels during
`faults.
`
`7.2 Calculation of Three-phase Balanced Fault Currents
`
`The action of synchronous generators on three—phase short circuits has, been
`described in Chapter 3. There it was seen that dependent on the time elapsing
`from the incidence of the fault, either the transient or the subtransient
`
`reactance should be used to represent the generator. For specifying switchgear
`the value of the current flowing at the instant at which the circuit breakers open
`is required, It has been seen, however, that the initially high fault current
`associated with the subtransient reactance decays with the passage of time.
`Modern air-blast circuit breakers usually operate in 2.5 cycles of 60 Hz
`alternating current and are associated with extremely fast protection. Older
`circuit breakers and those on lower voltage networks usually associated with
`relatively cruder protection can take in the order of 8 cycles or more to operate.
`In calculations it is usual to use the subtransient reactance of generators and to
`ignore the effects of induction motors. The calculation of fault currents ignores
`the direct-current component, the magnitude Of which depends on the instant -
`in the cycle that the short circuit occurs. If the circuit breaker opens a
`reasonable time after the incidence of the fault the direct-current component
`will have decayed considerably. With fast—acting circuit breakers the actual
`current to be interrupted is increased by the direct-current component and it
`must be taken into account. To allow for the direct-current component of the ' 2'7;
`fault current the symmetrical r.m.s. value is modified by the use of multiplying 533-5".
`factors such as the following:
`Mi
`8 cycle circuit breaker opening time, multiply by 1
`3 cycle circuit breaker opening time, multiply by 1.2
`2 cycle circuit breaker opening time, multiply by 1.4
`
`
`
`
`
`
`
`
`
`g
`5M...
`
`ff:
`"-3-:-
`
`_
`
`'_
`
`
`
`Consider an initially unloaded generator with a short circuit across the three.
`terminals as in Figure 7.2. The generated voltage per phase is E and therefore
`the short-circuit current is [E/Z(Q)]A, where Z is either the transient "or;
`
`Figure 7.2 VoItage source with short circuit and equivalent circuit.
`
`

This document is available on Docket Alarm but you must sign up to view it.


Or .

Accessing this document will incur an additional charge of $.

After purchase, you can access this document again without charge.

Accept $ Charge
throbber

Still Working On It

This document is taking longer than usual to download. This can happen if we need to contact the court directly to obtain the document and their servers are running slowly.

Give it another minute or two to complete, and then try the refresh button.

throbber

A few More Minutes ... Still Working

It can take up to 5 minutes for us to download a document if the court servers are running slowly.

Thank you for your continued patience.

This document could not be displayed.

We could not find this document within its docket. Please go back to the docket page and check the link. If that does not work, go back to the docket and refresh it to pull the newest information.

Your account does not support viewing this document.

You need a Paid Account to view this document. Click here to change your account type.

Your account does not support viewing this document.

Set your membership status to view this document.

With a Docket Alarm membership, you'll get a whole lot more, including:

  • Up-to-date information for this case.
  • Email alerts whenever there is an update.
  • Full text search for other cases.
  • Get email alerts whenever a new case matches your search.

Become a Member

One Moment Please

The filing “” is large (MB) and is being downloaded.

Please refresh this page in a few minutes to see if the filing has been downloaded. The filing will also be emailed to you when the download completes.

Your document is on its way!

If you do not receive the document in five minutes, contact support at support@docketalarm.com.

Sealed Document

We are unable to display this document, it may be under a court ordered seal.

If you have proper credentials to access the file, you may proceed directly to the court's system using your government issued username and password.


Access Government Site

We are redirecting you
to a mobile optimized page.





Document Unreadable or Corrupt

Refresh this Document
Go to the Docket

We are unable to display this document.

Refresh this Document
Go to the Docket