throbber

`
`
`
`UNITED STATES PATENT AND TRADEMARK OFFICE
`
`____________________________________________
`
`BEFORE THE PATENT TRIAL AND APPEAL BOARD
`
`____________________________________________
`
`VESTAS-AMERICAN WIND TECHNOLOGY, INC. AND
`VESTAS WIND SYSTEMS A/S,
`Petitioner,
`
`v.
`
`GENERAL ELECTRIC CO.,
`Patent Owner.
`____________________________________________
`
`Case IPR2018-01015
`U.S. Patent 7,629,705
`____________________________________________
`
`DECLARATION OF DR. WILLIAM MACK GRADY
`
`
`GE 2012
`Vestas v. GE
`IPR2018-01015
`
`

`

`IPR2018-01015
`Declaration of Dr. William Mack Grady
`I, William Mack Grady, declare as follows:
`Introduction
`1. My name is William Mack Grady. I have been retained by counsel
`
`I.
`
`for General Electric Co. (“GE” or “Patent Owner”) to serve as a technical expert in
`
`this inter partes review proceeding of U.S. Patent No. 7,629,705 (“the ’705
`
`patent”). I have been asked to provide this declaration to explain the teachings of
`
`the ’705 patent and the references that make up the instituted grounds in this
`
`proceeding, as well as to respond to characterizations made in both the petition and
`
`the Declaration of Professor Blaabjerg (Ex. 1003). I have previously prepared
`
`declarations for submission in the previous inter partes reexamination of the ’705
`
`patent, Control No. 95/000,633, as well as in the concluded ex parte reexamination
`
`of the ’705 patent, Control No. 90/012,587. I have also provided expert consulting
`
`services, including submitting expert reports and offering expert testimony in
`
`depositions and at trial, on behalf of GE in a litigation involving the ’705 patent:
`
`General Elec. Co. v. Mitsubishi Heavy Indus., Ltd., No. 3:10-cv-00276-F (N.D.
`
`Tex).
`
`2.
`
`I have reviewed and am familiar with the ’705 patent, filed on
`
`October 20, 2006, and its prosecution history. I understand that claims 1-9 of the
`
`’705 patent are subject to this proceeding before the PTAB and have reviewed the
`
`original petition and the Board’s Decision on Institution (“DI”). I have also
`
`
`
`1
`
`

`

`IPR2018-01015
`Declaration of Dr. William Mack Grady
`reviewed the various exhibits, including the Declaration of Professor Blaabjerg,
`
`that were filed in support of the petition. In this declaration, I will describe: the
`
`teachings of each reference asserted in the petition; how those references would be
`
`understood by a person having ordinary skill in the relevant art; and what each
`
`reference does and does not disclose with respect to the challenged claims of the
`
`’705 patent. I understand that my technical analysis and opinions will be used to
`
`support legal conclusions presented in GE’s Patent Owner’s Response.
`
`II. Qualifications
`I graduated with a B.S. in Electrical Engineering from the University
`3.
`
`of Texas, Arlington in 1971, and then went on to receive an M.S. in Electrical
`
`Engineering from Purdue University in 1973. From 1974 to 1980, I worked as a
`
`System Planning Engineer for Texas Power & Light Company (now Oncor) in
`
`Dallas. My responsibilities included transmission system planning in one of the
`
`four geographical divisions of Texas Power & Light. During that time I also served
`
`as chairman of the Dallas Chapter of the IEEE Power Engineering Society and as a
`
`member of the Edison Electric Institute Computer Committee.
`
`4.
`
`I returned to Purdue and graduated with a Ph.D. in Electrical
`
`Engineering in 1983. I joined the faculty at the Department of Electrical and
`
`Computer Engineering, University of Texas, Austin in 1983, where I attained the
`
`title (now Emeritus) of Professor and Jack S. Josey Centennial Professor in Energy
`
`
`
`2
`
`

`

`IPR2018-01015
`Declaration of Dr. William Mack Grady
`Resources. On September 1, 2012, I joined the faculty at the Electrical and
`
`Computer Engineering Department at Baylor University. My current title is
`
`Professor of Electrical and Computer Engineering.
`
`5. My areas of specialization are electric power systems, power quality
`
`and harmonics, renewable energy integration, power electronics, and
`
`synchrophasor applications in power grids. My present research funding comes
`
`from the Electric Reliability Council of Texas (“ERCOT”), Schweitzer
`
`Engineering Labs, and the U.S. Department of Defense’s Defense Threat
`
`Reduction Agency (“DTRA”). I have held a security clearance through DTRA
`
`since 2008 to study the impact of nuclear weapons, specifically MHD-E3 (slow)
`
`and MHD-E1 (fast) events, on power systems.
`
`6.
`
`I am also a Department of Energy contractor for Idaho National
`
`Laboratory. In 2012 and 2013, I participated in a series of grid tests on the topic of
`
`HEMP at the Idaho National Laboratory. Now, through my project work at
`
`Baylor, I use the data collected in Idaho to determine how best to protect the grid
`
`from MHD-E3 and MHD-E1 attacks. I am also a regular technical advisor to the
`
`FBI on critical power system infrastructure issues.
`
`7.
`
`Presently, I am working on an ERCOT project using ERCOT’s
`
`synchrophasor data to determine stability limits associated with the large wind
`
`turbine generation percentage in Texas. On some days, ERCOT’s power
`
`
`
`3
`
`

`

`IPR2018-01015
`Declaration of Dr. William Mack Grady
`generation reaches 40% or more for hours. Occasionally, it exceeds 50%, but is
`
`curtailed beyond that due to stability concerns. Details of my DTRA and ERCOT
`
`work are attached in Appendix B to this declaration.
`
`8.
`
`I currently teach courses in power systems, power electronics, and
`
`renewable energy at Baylor University. In 2000, I was elected an IEEE fellow for
`
`“contributions in the analyses and control of power system harmonics and power
`
`quality.” I have twice won the annual Texas Execs Award for Outstanding
`
`Teacher in the College of Engineering. Other honors and awards that I have
`
`received are listed in Appendix A to this declaration. I have been a Registered
`
`Professional Engineer in Texas (#48629) since 1981.
`
`9. While my entire career has dealt with electric power systems, wind
`
`and solar integration in power grids, as well as defending against nuclear MHD-E3
`
`and MHD-E1 attack, has been the main focus of my research for the past ten years.
`
`In particular, the emphasis has been on the use of synchrophasors as “health
`
`monitors” of grid stability so that more of the existing wind generator fleet in the
`
`Electric Reliability Council of Texas (ERCOT) can be utilized. My paper with
`
`David Costello of Schweitzer Engineering, “Implementation and Application of an
`
`Independent Texas Synchrophasor Network”, describes the Texas Synchrophasor
`
`Network at U.T. Austin that I developed with EPRI and Schweitzer for the purpose
`
`of wind integration in ERCOT. A 200+ page summary report of our findings—
`
`
`
`4
`
`

`

`IPR2018-01015
`Declaration of Dr. William Mack Grady
`consisting of weekly, monthly, and event reports—is on my Baylor web page, and
`
`I made presentations on this subject in the last ten years at conferences sponsored
`
`or regularly attended by NERC, FERC, NASPI, UWIG, numerous IEEE
`
`conferences, invited presentations and training sessions at Sandia National
`
`Laboratories and other institutions, and smaller audiences. One of the key
`
`contributions thus far is to illustrate with actual data that wind generation does not
`
`reduce ERCOT’s grid inertia as commonly believed. For the past ten years, I have
`
`continued to produce synchrophasor reports which now also include the Eastern
`
`and Western grids. I routinely collaborate with engineers at ERCOT and American
`
`Electric Power, where I visit wind farms to understand wind turbine operation,
`
`real-world issues, modeling, and simulation. My contributions include
`
`determining and identifying when wind curtailment is necessary based on my
`
`experience in power grids and wind generation, as well as my synchrophasor
`
`measurements and data interpretations procedures.
`
`10.
`
`In 2010, I testified in court on behalf of the Texas Attorney General’s
`
`Office in a case involving El Paso Electric. My testimony provided the judge with
`
`a description of how grids operate and to explain the role of power distribution
`
`
`
`5
`
`

`

`IPR2018-01015
`Declaration of Dr. William Mack Grady
`equipment (e.g., distribution feeders, service drops, protection) and how it differs
`
`from transmission-level equipment.
`
`11. A copy of my curriculum vitae is also attached as part of Appendix A,
`
`providing a more complete list of my experience.
`
`III. The Practical Effects of Zero-Voltage Events on Both The Grid and
`Real Wind Turbine Equipment
`12. Zero-voltage faults on the grid are caused by a three-phase short-
`
`circuit. Ex. 2013, 145 (“… switches, circuit breakers, and fuses [] protect key
`
`components and [] allow different segments of the system to be isolated for …
`
`during emergency faults (short circuits) that may occur in the system.”) As has
`
`been the understanding of a POSITA for decades, a short-circuit across all three
`
`phases (or lines) of the grid, while the least common type of fault, “is the most
`
`severe fault.” Ex. 2014, 246; Ex. 2015, 14 (Acknowledging that “[t]he smallest
`
`number of faults, roughly 5%, involve all three phases and are called three-phase
`
`faults.”); Ex. 2016, 496-497 (further characterizing three-phase faults). The
`
`
`
`6
`
`

`

`IPR2018-01015
`Declaration of Dr. William Mack Grady
`severity of three-phase short-circuit faults is precisely why EON and FERC set out
`
`requirements based on them: they are the worst-case scenario.
`
`
`
`Ex. 2014 showing three-line (i.e., phase) short-circuits in Figures 7.l(d) and (e).
`
`13. Operators of electric power grids have long recognized the importance
`
`of generating units riding through short-circuit faults to minimize blackouts. As
`
`explained by Professor Luther (see e.g., Ex. 1031), operators routinely evaluate
`
`grid security for a variety of such faults, with a three-phase short circuit fault
`
`
`
`7
`
`

`

`IPR2018-01015
`Declaration of Dr. William Mack Grady
`reducing the grid voltage to a magnitude of zero volts being the worst case. This is
`
`the condition contemplated by EON.
`
`
`
`EON, Figure 5a illustrating line-to-line voltage magnitude during and subsequent
`
`to a “Near-to-generator three-phase short-circuit” (Ex. 1007, 18)
`
`14. Power system engineers have also long recognized that during the
`
`period immediately following when the fault clears, the grid will be in a disturbed
`
`state. One aspect of this post-fault condition is an abnormal grid voltage, either
`
`lower than normal (as shown in EON’s Figure 5a) or higher than normal due to
`
`electrical transients that linger on long AC transmission lines. But another aspect
`
`of the post-fault scenario is that both generator speeds and voltage phase angles
`
`will swing from their pre-fault values—often dramatically. Ex. 2017, 331
`8
`
`
`
`

`

`IPR2018-01015
`Declaration of Dr. William Mack Grady
`(“During a fault … the synchronous machines of the system undergo changes in
`
`the relative positions of their rotors. With constant internal generated voltages, the
`
`phase angles between these voltages will vary until a new condition of equilibrium
`
`is established; or, if the disturbance is sufficiently severe, loss of synchronism will
`
`result.”) If a generator is close to the faulted point, its voltage drops during the
`
`fault, power flow out of the generator drops, and the rotor speeds up due to power
`
`imbalance. The worst case is when the voltage output is zero, because all
`
`mechanical output power goes towards increasing inertia via speed. This condition
`
`is referred to as asynchronous voltage and EON expressly warns that this condition
`
`can exist once the fault is cleared.
`
`Ex. 1007, 17.
`
`
`
`15. The conventional response of older turbines to such voltage
`
`fluctuations on the grid was to trip offline (i.e., disconnecting the machine from the
`
`grid) until the asynchronous fault cleared, allowing the turbine to reconnect to a
`
`measurable and stable grid voltage. Ex. 2018, 245 (“Somewhere in the circuit
`
`between the generator and the electrical grid are circuit breakers or fuses. These
`
`are intended to open the circuit if the current gets too high, presumably as a result
`
`
`
`9
`
`

`

`IPR2018-01015
`Declaration of Dr. William Mack Grady
`of a fault or short circuit. Circuit breakers can be reset after the fault is
`
`corrected.”); Ex. 2015, 13-14 (“The opening of circuit breakers to isolate the
`
`faulted portion of the line from the rest of the system interrupts the flow of current
`
`in the ionized path and allows deionization to take place.”); Ex. 2013, 145.
`
`16. This was an acceptable response when wind turbines were not a large
`
`contributor to power generation. However, as the percentage of wind turbines
`
`increased, becoming a substantial contributor to total power generation in grid
`
`networks, the prospect of entire wind farms tripping offline due to voltage drops
`
`became a grid issue, as opposed to simply a wind farm operator issue. For
`
`example, if an entire wind farm trips offline, the surrounding region is likely to
`
`experience a large voltage drop, which may cause a blackout in extreme
`
`conditions. Because it became increasingly important for the wind turbine
`
`generators to remain connected immediately following a zero-voltage fault in a
`
`controlled manner to help maintain overall grid voltage close to the normal
`
`operating range, challenging standards like EON and FERC requiring such
`
`capability for grid-connected wind turbines were developed. See e.g., Ex. 1031.
`
`17. Wind turbine generators are designed with a predefined tolerance of
`
`currents or voltages that fluctuate above the normal operating range. Should a
`
`combination of a grid voltage transient and wind turbine control action cause either
`
`current or voltage to exceed this tolerance—during, for example, the unpredictable
`
`
`
`10
`
`

`

`IPR2018-01015
`Declaration of Dr. William Mack Grady
`recovery period after a zero-voltage fault—then protective action will trip (i.e.,
`
`disconnect) the machine from the grid, thereby failing ride-through. See e.g., Ex.
`
`1001, 5:26-5:29, 6:47-6:55. Therefore, it is important for the wind turbine control
`
`to manage both current and voltage within equipment rating. Proper phase
`
`synchronization of the wind turbine control is also essential to ensure that the
`
`actual currents follow the commands generated by the control functions that
`
`regulate current and voltage. E.g., Ex. 1001, 8:37-8:46.
`
`18. When experiencing a zero-voltage event, however, the wind turbine’s
`
`control system is no longer able to sense the frequency and phase of the grid
`
`voltage signal that are ordinarily relied on to maintain synchronization because the
`
`voltage of the grid itself has decreased to approximately zero volts. In other
`
`words, not only is the wind turbine blind during a zero-voltage event, but there is
`
`also no grid voltage present to see. As such, ZVRT presents, at the wind turbine, a
`
`much more complex problem to solve than either low voltage ride through,
`
`including single and two-phase faults, (where there is at least a low voltage present
`
`on the grid to sense) or an open circuit condition in the network (where the wind
`
`turbine cannot measure the grid voltage temporarily, but can still remain
`
`synchronized because the grid voltage is not changing in frequency or phase).
`
`
`
`
`
`
`
`11
`
`

`

`IPR2018-01015
`Declaration of Dr. William Mack Grady
`IV. Person of Ordinary Skill in the Art
`19.
`
`I have read that Petitioner and Professor Blaabjerg submit that a
`
`POSITA would have “completed at least a Master’s-level academic program in
`
`electrical engineering and obtained two or more years of industry experience in
`
`that field, or completed a Bachelor’s-level program in electrical engineering
`
`supplemented by at least four years of industry experience.” Petition, 16 citing Ex.
`
`1003, ¶¶16-18. Although I generally agree with this level of ordinary skill, based
`
`on my own experience and opinion, “industry experience” is simply too broad for
`
`the technology at issue. The challenges created by zero-voltage events in the field
`
`in 2006, as well as the specific solution described and claimed by the ’705 patent,
`
`are specific to power electronics used in large-scale, grid-connected, wind turbine
`
`generators. Accordingly, the level of ordinary skill in the art should include
`
`specific “industry experience” in power electronics tailored to wind turbine
`
`generators.
`
`20.
`
`I believe that a person having this level of skill—including the
`
`appropriate industry experience in the relevant fields of power electronics tailored
`
`to wind turbine generators— would appreciate that in the context of the specific
`
`technical problem of zero-voltage ride for wind turbine generators, the asserted
`
`prior art is not applicable. However, even under Petitioner’s definition of a
`
`POSITA, I would come to the same conclusions that I discuss below.
`
`
`
`12
`
`

`

`IPR2018-01015
`Declaration of Dr. William Mack Grady
`V. The Challenged Claims of the ’705 Patent Recite An Implementation for
`Facilitating Zero-Voltage Ride Through
`21. Connecting a wind turbine to the electric grid when the turbine
`
`voltage phases are not synchronized with the grid voltage phases can result in
`
`significant damage to the wind turbine equipment. This risk of damage is
`
`heightened when a wind turbine is already coupled to the electric grid and the grid
`
`experiences a severe fault. When a severe grid fault occurs, the amplitude of the
`
`grid voltage can decrease to zero volts on all three phases (“zero voltage event”).
`
`As a result, the wind turbine can no longer synchronize its voltage phases with the
`
`grid because the grid fault caused the grid voltage amplitudes to decrease such that
`
`the grid voltage is no longer present for the wind turbine to sense.
`
`
`
`22. As wind turbines proliferated and became a greater percentage of the
`
`electric grid, grid operators promulgated requirements that wind farms remain
`
`connected to the grid during voltage decreases of a certain duration and magnitude.
`
`Necessarily, the capability of a wind turbine generator to remain electrically
`
`connected to the electrical grid when the voltage of the electrical grid drops to zero
`
`volts was required. Ex. 1001, 8:29–46. This capability is called “zero voltage ride
`
`through” or “ZVRT,” and it is my opinion that the claims of the ’705 patent
`
`capture the specific features necessary to facilitate ZVRT.
`
`23. For example, stepping through the “configuring the electrical machine
`
`and the control system...” limitation of independent claim 1 highlights each of the
`
`
`
`13
`
`

`

`IPR2018-01015
`Declaration of Dr. William Mack Grady
`claimed requirements for facilitating ZVRT. I note that corresponding language is
`
`also recited in independent claim 7.
`
`24. First, the electrical machine (e.g., the wind turbine) and its control
`
`system must be configured such that “the electrical machine remains electrically
`
`connected to the electric power system,” as highlighted in the annotated portion of
`
`challenged claim 1 below.
`
`Ex. 1001, claim 1
`
`
`
`25. Consistent with the requirement of ZVRT originally contemplated by
`
`the grid operators and set out in the grid codes, the plain language of the claims
`
`confirms that the wind turbine does not disconnect from the grid during (or
`
`subsequent to) a zero-voltage event on the grid. Electrical disconnection can be
`
`achieved, generally, using mechanical devices like switches and circuit breakers, or
`
`electrical circuit components such as rectifiers that prevent current flow. In either
`
`
`
`14
`
`

`

`IPR2018-01015
`Declaration of Dr. William Mack Grady
`case, where electrical disconnection occurs, the electrical machine has not
`
`remained electrically connected to the grid.
`
`26. Moreover, to remain electrically connected means that the electrical
`
`machine has already connected to the grid in the moments before the fault. In
`
`other words, ZVRT is facilitated in an electrical machine that is already connected
`
`to the grid (and must, therefore, ride through the fault) and not upon its initial
`
`connection to the grid.
`
`27.
`
`Second, the claim language confirms that the condition during which
`
`ZVRT is facilitated is a grid fault—that is, when “the voltage amplitude of the
`
`electric power system” decreases to “approximately zero volts,” as highlighted in
`
`the annotated portion of challenged claim 1 below.
`
`Ex. 1001, claim 1
`
`
`
`28.
`
`It is clear from both the plain language of the claim highlighted above
`
`and the meaning of “approximately zero volts” that I understand the Board has
`
`adopted, that the condition necessitating ZVRT is a grid voltage fault in which the
`
`
`
`15
`
`

`

`IPR2018-01015
`Declaration of Dr. William Mack Grady
`grid voltage has decreased. Put differently, instances in which the grid voltage has
`
`not decreased—such as when grid voltage is still present, but an electrical machine
`
`simply cannot sense or read the grid voltage due to a lost connection or defective
`
`sensor—are not a condition requiring ZVRT, as confirmed by the challenged
`
`claims.
`
`29. Third, the challenged claims require that, when the electrical machine
`
`remains electrically connected to the grid when the grid voltage amplitude
`
`deceases to approximately zero volts, it remains connected both during and
`
`subsequent to the zero-voltage event. This is also highlighted in the annotated
`
`portion of claim 1 below.
`
`Ex. 1001, claim 1
`
`
`
`30. When grid voltage recovers from a zero-voltage event (i.e., the grid
`
`voltage amplitude increases to an operating magnitude that enables the connected
`
`electrical machine to sense and synchronize with the grid voltage phase), the phase
`
`of the grid voltage can be at any angle relative to that of the connected machine.
`
`This is especially true of unusually long fault periods, such as 0.15 seconds.
`
`
`
`16
`
`

`

`IPR2018-01015
`Declaration of Dr. William Mack Grady
`Further, the frequency of the grid may differ from that of the connected machine
`
`and the relative phase will continue to move away in value from that of the
`
`connected machine. In other words, the phase of the grid will be asynchronous to
`
`the phase of the connected machine. Practically speaking, this means that to
`
`facilitate ZVRT as recited by the challenged claims, the electrical machine must
`
`remain connected to the grid both during the time period of the zero-voltage event
`
`(when it senses no voltage from the grid) and during the time period subsequent to
`
`the zero-voltage event (when it can sense an unsettled voltage having any number
`
`of completely unpredictable asynchronous voltage phases). Accordingly, an
`
`electrical machine that disconnects from the grid, even subsequent to the zero-
`
`voltage event has not facilitated ZVRT as claimed.
`
`VI. How the Grid Codes are Meant to be Applied
`I note that Petitioner and Professor Blaabjerg rely on the ZVRT
`31.
`
`requirements set out in grid codes, such as EON and FERC, to establish the
`
`purported motivation to make the combinations proposed in its grounds. E.g.,
`
`Petition, 17-18, 38. And, as both Petitioner and the Board have observed, “the
`
`E.ON requirements [(EON, Ex. 1007)] provided powerful incentives to produce a
`
`wind turbine that would ride through a zero voltage grid fault.” DI, 50 citing Ex.
`
`
`
`17
`
`

`

`IPR2018-01015
`Declaration of Dr. William Mack Grady
`1028, 44. I agree with this statement: EON (and FERC) promulgated standards
`
`that required wind turbine ride through of “a zero voltage grid fault” (i.e., ZVRT).
`
`32. That said, a POSITA would first recognize that EON and FERC apply
`
`to high power wind turbine generators rated on the order of 1.0-1.5MW, which is
`
`consistent with the high power and voltage of the grid rated at more than 100 kV.
`
`Ex. 2013, 145-146 (“The utility grid system starts with transmission lines that
`
`carry large blocks of power, at voltages ranging from 161 kV to 765 kV.”); Ex.
`
`2015, 13 (describing “faults on transmission lines of 115 kv and higher.”) In
`
`contrast, small-scale generators, like the 11kW turbine in Teodorescu (Ex. 1010, 1-
`
`2) or the static power converter of Deng (Ex. 1009; Ex. 1012, 1:38-39 (“An
`
`alternative to large power plants is the use of small low cost power generators …
`
`AC power sources, such as static power converters (SPCs) drawing power from
`
`batteries, fuel cells, and the like, have been used as low cost power generators”)
`
`would neither fall under the scope of EON and FERC, nor give rise to a POSITA
`
`even considering those grid codes. Instead, a POSITA would expect that small-
`
`scale systems are applied to the grid with the design intent that they must
`
`disconnect in the presence of a severe, zero-voltage fault. Ex. 2013, 523-524
`
`(“The power conditioning unit absolutely must be designed to quickly and
`
`
`
`18
`
`

`

`IPR2018-01015
`Declaration of Dr. William Mack Grady
`automatically drop the [small-sized, static] PV system from the grid in the event of
`
`a utility power outage.”)
`
`33. EON warns that: “Once a fault in the ENE network is cleared or after
`
`a three-phase automatic reclosure, the operator of a generating unit must expect
`
`that the voltages in the networks of ENE and at the network connection of the
`
`connectee could be asynchronous.” Ex. 1007, 17. An asynchronous grid voltage
`
`appearing on the grid subsequent to a zero-voltage event on the grid (during which
`
`the voltage amplitude of the grid decreased to zero volts) is a specific problem that
`
`necessitates ZVRT capability. In contrast, when a system (like that of either Deng
`
`reference) loses sight of the grid voltage due to an open circuit condition (e.g.,
`
`caused by switch “bounce”), the grid itself has not changed its phase.
`
`34. The scope of FERC is comparable: “Order No. 661 requires public
`
`utilities that own, control, or operate facilities for transmitting electric energy in
`
`interstate commerce to append to their standard large generator interconnection
`
`procedures and large generator interconnection agreements … and technical
`
`requirements for the interconnection of large wind generation.” Ex. 1005, 1.
`
`Footnote 6 of FERC defines that the “large wind generating plants” to which it
`
`applies “are those with an output rated at more than 20 MW at the point of
`
`interconnection. The interconnection requirements for small generators rated at 20
`
`MW or less are set forth in Standardization of Small Generator Interconnection
`
`
`
`19
`
`

`

`IPR2018-01015
`Declaration of Dr. William Mack Grady
`Agreements and Procedures, Order No. 2006, 70 FR 34190 (June 13, 2005).” A
`
`POSITA would recognize that, because FERC applies to large plants or wind farms
`
`rated at more than 20 MW, each wind turbine generator in that plant would be
`
`rated for approximately 1.0-1.5 MW. It follows naturally that no POSITA,
`
`motivated by EON or FERC, would look to small-scale references like either Deng
`
`(or even Teodorescu’s 11-KW system) to find a solution for achieving ZVRT.
`
`VII. Each and Every Instituted Ground Fails to Describe or Teach an
`Implementation That Achieves ZVRT as Recited by the Challenged
`Claims
`It is my opinion that the references identified by Petitioner and
`35.
`
`Professor Blaabjerg do not describe an implementation to facilitate ZVRT, nor do
`
`they even consider the unique problem presented by ZVRT as I have discussed
`
`above. I will discuss my analysis of these references and the proposed
`
`combinations of references below, with reference to each ground instituted in this
`
`case, and will explain how they do not describe what Petitioner or Professor
`
`Blaabjerg suggest they describe.
`
`A. Ground 1: Deng ’988 in combination with Janssen fails to teach
`an implementation that achieves ZVRT
`36. The Janssen patent makes clear throughout its disclosure that it is
`
`directed to low voltage ride through (LVRT) scenarios only, not ZVRT. Ex. 1008,
`
`1:6-9 (“More particularly, the invention relates to supporting low voltage ride
`
`through for wind turbine generators coupled with a power distribution grid.”),
`
`
`
`20
`
`

`

`IPR2018-01015
`Declaration of Dr. William Mack Grady
`4:32-33 (“As described in greater detail below, in order to protect the wind turbine
`
`generator against low voltage events,..”), 4:65-5:3 (“During a low voltage event
`
`converter controller 430 selectively activates crowbar circuit 440 to maintain
`
`current levels in a safe range. Thus, crowbar circuit 440 and converter
`
`controller 430 are part of a system that allows a wind turbine generator to ride
`
`through low voltage events and remain synchronized to the power grid.”), 5:26-28
`
`(“To support low voltage ride through capability, turbine controller 500 detects a
`
`low voltage event and responds to the event.”).
`
`37. The ’705 patent, in contrast, distinguishes its ZVRT capability from
`
`LVRT capability: “ZVRT is contrasted to low voltage ride through (LVRT)
`
`features known in the art that facilitate mitigating wind turbine generator 100 trips
`
`during transients wherein the voltage amplitude rapidly decreases, yet does not
`
`decrease to zero volts.” Ex. 1001, 6:63-67. The ZVRT capability of the ’705
`
`patent, as recited in the ZVRT claims and described in the specification, is
`
`fundamentally different from Janssen’s LVRT. This fundamental difference
`
`between Janssen’s LVRT and the ’705 patent’s ZVRT only confirms that Janssen
`
`on its own cannot describe or teach the implementation of ZVRT recited by the
`
`challenged claims of the ’705 patent.
`
`38.
`
`I understand that Petitioner proposes a combination of Janssen with
`
`Deng ’988 that collectively shows how to achieve ZVRT, as recited by the
`
`
`
`21
`
`

`

`IPR2018-01015
`Declaration of Dr. William Mack Grady
`“configuring the electrical machine and the control system…” limitation of claim 1
`
`(and its corresponding features recited in claim 7). Petition, 24-27. However,
`
`Deng ’988 describes a solution to an entirely different problem than zero-voltage
`
`events, which cannot be implemented to facilitate ZVRT, and is directed to a
`
`technology that no POSITA would look to with any expectancy of successfully
`
`applying its teachings to the wind turbine of Janssen.
`
`1.
`
`A POSITA would not look to Deng ’988’s static power
`converter when seeking to modify the wind turbine system of
`Janssen
`39. Deng ’988 describes a system and method for synchronizing
`
`alternating current power sources (“APS”), “such as static power converters
`
`(‘SPC’),” with a power grid. See e.g., Ex. 1009, Abstract, 1:16-24. Generally,
`
`static power converters on their own are small-scale, supplemental power sources.
`
`While wind turbine generators do include static power conversion components,
`
`they are just one piece of a larger wind turbine generator system.
`
`40.
`
`I note that there is also a Deng ’650 patent introduced in this case,
`
`which is not materially different from Deng ’988 other than its introduction of a
`
`basic PLL. This is notable because Deng ’650 provides more insight into its static
`
`power converters than Deng ’988. In particular, Deng ’650 explains that “AC
`
`power sources, such as static power converters (SPCs) draw[] power from
`
`batteries, fuel cells, and the like, [and] have been used as low cost power
`
`
`
`22
`
`

`

`IPR2018-01015
`Declaration of Dr. William Mack Grady
`generators to provide added power capacity to power grids during peak periods.”
`
`Ex. 1012, 1:44-48. Professor Blaabjerg also identified several examples of static
`
`power converters during his deposition, including a fuel cell, a photovoltaic power
`
`converter, or a DC-DC converter. Ex. 2020, 128:14-129:1.
`
`41. Static power converters are mechanically and operationally very
`
`different than large scale electrical machines like wind turbines or power plants
`
`like wind farms. In fact, Deng ’650 expressly distinguishes its static power
`
`converters: “An alternative to large power plants is the use of small low cost power
`
`generators connected in parallel to power grids to provide added power capacity
`
`during peak power consumption periods in order to reduce the strain on power
`
`grids.” Id., 1:38-42. This distinction in Deng ’650 alone would discourage a
`
`POSITA from looking to either Deng reference in solving a problem in large scale
`
`power plant consisting of wind turbines.
`
`42.
`
`In setting out its alleged motivation to combine Janssen and Deng
`
`’988, I note that Petitioner relies on the grid codes (i.e., EON and FERC) as the
`
`ba

This document is available on Docket Alarm but you must sign up to view it.


Or .

Accessing this document will incur an additional charge of $.

After purchase, you can access this document again without charge.

Accept $ Charge
throbber

Still Working On It

This document is taking longer than usual to download. This can happen if we need to contact the court directly to obtain the document and their servers are running slowly.

Give it another minute or two to complete, and then try the refresh button.

throbber

A few More Minutes ... Still Working

It can take up to 5 minutes for us to download a document if the court servers are running slowly.

Thank you for your continued patience.

This document could not be displayed.

We could not find this document within its docket. Please go back to the docket page and check the link. If that does not work, go back to the docket and refresh it to pull the newest information.

Your account does not support viewing this document.

You need a Paid Account to view this document. Click here to change your account type.

Your account does not support viewing this document.

Set your membership status to view this document.

With a Docket Alarm membership, you'll get a whole lot more, including:

  • Up-to-date information for this case.
  • Email alerts whenever there is an update.
  • Full text search for other cases.
  • Get email alerts whenever a new case matches your search.

Become a Member

One Moment Please

The filing “” is large (MB) and is being downloaded.

Please refresh this page in a few minutes to see if the filing has been downloaded. The filing will also be emailed to you when the download completes.

Your document is on its way!

If you do not receive the document in five minutes, contact support at support@docketalarm.com.

Sealed Document

We are unable to display this document, it may be under a court ordered seal.

If you have proper credentials to access the file, you may proceed directly to the court's system using your government issued username and password.


Access Government Site

We are redirecting you
to a mobile optimized page.





Document Unreadable or Corrupt

Refresh this Document
Go to the Docket

We are unable to display this document.

Refresh this Document
Go to the Docket