throbber
1398
`
`IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 53, NO. 5, OCTOBER 2006
`
`Overview of Control and Grid Synchronization for
`Distributed Power Generation Systems
`
`Frede Blaabjerg, Fellow, IEEE, Remus Teodorescu, Senior Member, IEEE, Marco Liserre, Member, IEEE,
`and Adrian V. Timbus, Student Member, IEEE
`
`Abstract—Renewable energy sources like wind, sun, and hydro
`are seen as a reliable alternative to the traditional energy sources
`such as oil, natural gas, or coal. Distributed power generation
`systems (DPGSs) based on renewable energy sources experience
`a large development worldwide, with Germany, Denmark, Japan,
`and USA as leaders in the development in this field. Due to the
`increasing number of DPGSs connected to the utility network,
`new and stricter standards in respect to power quality, safe run-
`ning, and islanding protection are issued. As a consequence, the
`control of distributed generation systems should be improved to
`meet the requirements for grid interconnection. This paper gives
`an overview of the structures for the DPGS based on fuel cell,
`photovoltaic, and wind turbines. In addition, control structures of
`the grid-side converter are presented, and the possibility of com-
`pensation for low-order harmonics is also discussed. Moreover,
`control strategies when running on grid faults are treated. This
`paper ends up with an overview of synchronization methods and a
`discussion about their importance in the control.
`
`Index Terms—Control strategies, distributed power generation,
`grid converter control, grid disturbances, grid synchronization.
`
`I. INTRODUCTION
`
`N OWADAYS, fossil fuel is the main energy supplier of the
`
`worldwide economy, but the recognition of it as being a
`major cause of environmental problems makes the mankind to
`look for alternative resources in power generation. Moreover,
`the day-by-day increasing demand for energy can create prob-
`lems for the power distributors, like grid instability and even
`outages. The necessity of producing more energy combined
`with the interest in clean technologies yields in an increased
`development of power distribution systems using renewable
`energy [1].
`Among the renewable energy sources, hydropower and wind
`energy have the largest utilization nowadays. In countries with
`hydropower potential, small hydro turbines are used at the
`distribution level to sustain the utility network in dispersed or
`remote locations. The wind power potential in many countries
`
`Manuscript received January 31, 2006. Abstract published on the Internet
`July 14, 2006. This work was supported in part by Risø National Laboratory,
`in part by Eltra, and in part by the Danish Research Councils under Contract
`2058-03-0003.
`F. Blaabjerg, R. Teodorescu, and A. V. Timbus are with the Institute of
`Energy Technology, Aalborg University, 9220 Aalborg, Denmark (e-mail:
`fbl@iet.aau.dk; ret@iet.aau.dk; avt@iet.aau.dk).
`M. Liserre is with the Department of Electrotechnical and Electronic Engi-
`neering, Polytechnic of Bari, 70125 Bari, Italy (e-mail: liserre@poliba.it).
`Digital Object Identifier 10.1109/TIE.2006.881997
`
`Installed capacity at the end of 2004. (a) Wind energy in Europe [2].
`Fig. 1.
`(b) PV power in the world [3].
`
`around the world has led to a large interest and fast development
`of wind turbine (WT) technology in the last decade [2]. A total
`amount of nearly 35-GW wind power has been installed in
`Europe by the end of 2004, as shown in Fig. 1(a).
`Another renewable energy technology that gains acceptance
`as a way of maintaining and improving living standards without
`harming the environment is the photovoltaic (PV) technology.
`As shown in Fig. 1(b), the number of PV installations has an
`exponential growth, mainly due to the governments and utility
`companies that support programs that focus on grid-connected
`PV systems [3], [4].
`Besides their low efficiency, the controllability of the distrib-
`uted power generation systems (DPGSs) based on both wind
`and sun are their main drawback [5]. As a consequence, their
`connection to the utility network can lead to grid instability
`or even failure, if these systems are not properly controlled.
`Moreover, the standards for interconnecting these systems to
`the utility network are stressing more and more the capability of
`the DPGS to run over short grid disturbances. In this case, both
`synchronization algorithm and current controller play a major
`role. Therefore, the control strategies applied to distributed
`systems become of high interest.
`This paper gives an overview of the main DPGS structures,
`PV and fuel cell (FC) systems being first discussed. A clas-
`sification of WT systems with regard to the use of power
`electronics follows. This is continued by a discussion of control
`structures for grid-side converter and the possibilities of imple-
`mentation in different reference frames. Further on, the main
`characteristics of control strategies under grid fault conditions
`are discussed. The overview of grid synchronization methods
`and their influence in control conclude this paper.
`
`0278-0046/$20.00 © 2006 IEEE
`
`GE 2011
`Vestas v. GE
`IPR2018-01015
`
`

`

`BLAABJERG et al.: OVERVIEW OF CONTROL AND GRID SYNCHRONIZATION FOR DPGSs
`
`1399
`
`Fig. 3. Hardware structure for a PV system using a dc–dc stage to boost the
`input voltage.
`
`III. HARDWARE TOPOLOGIES FOR DPGS
`
`A detailed description of the hardware structure for many
`types of DPGSs is given in [5]. Noticeable is that the PV and
`FC systems have a similar hardware structure, whereas different
`hardware topologies can be found for WT systems, depending
`on the type of the generator used. A brief introduction into the
`structure of these systems is given below.
`
`A. PV and FC Systems
`
`As aforementioned, the hardware structures of PV and FC
`systems are quite similar. Although both FC and PV systems
`have a low-voltage input provided by the FC and PV panels,
`more such units can be connected together to obtain the re-
`quired voltage and power. Usually, power conditioning systems,
`including inverters and dc–dc converters, are often required to
`supply normal customer load demand or send electricity into
`the grid, as shown in Fig. 3. The voltage boosting can be done
`in the dc or ac stage of the system [5]–[11]. For smoothing the
`output current, an LCL filter is normally used between these
`systems and the utility network. In addition, isolation between
`the input and output powers is required in many countries where
`such systems are installed. Again, there are two ways to achieve
`isolation, namely: 1) using the dc–dc converter and 2) using an
`isolation transformer after the dc–ac stage.
`
`B. WT Systems
`
`In this section, a classification of WT systems in those using
`and those not using power electronics as interface to the utility
`network is given. Hardware structures in each case will be
`illustrated to distinguish the systems.
`1) WT Systems Without Power Electronics: Most of these
`topologies are based on squirrel-cage induction generator
`(SCIG), which is directly connected to the grid. A soft starter
`is usually used to reduce the inrush currents during start up
`[5], [12], [13]. Moreover, a capacitor bank is necessary to
`compensate for the reactive power necessary to the machine,
`as shown in Fig. 4(a).
`2) WT Systems With Power Electronics: By adding power
`electronics units into the WT systems, the complexity of the
`system is increased. In addition, the solution becomes more
`expensive. In any case, better control of the input power and
`grid interaction is obtained. For example, maximum power for
`a large interval of wind speeds can be extracted while control
`of both active and reactive powers into the grid is achieved by
`means of power electronics.
`
`Fig. 2. General structure for distributed power system having different input
`power sources.
`
`II. DPGS STRUCTURE
`
`A general structure for distributed systems is illustrated in
`Fig. 2. The input power is transformed into electricity by means
`of a power conversion unit whose configuration is closely
`related to the input power nature. The electricity produced
`can be delivered to the local loads or to the utility network,
`depending where the generation system is connected.
`One important part of the distributed system is its control.
`The control tasks can be divided into two major parts.
`
`1) Input-side controller, with the main property to extract
`the maximum power from the input source. Naturally,
`protection of the input-side converter is also considered
`in this controller.
`2) Grid-side controller, which can have the following tasks:
`• control of active power generated to the grid;
`• control of reactive power transfer between the DPGS
`and the grid;
`• control of dc-link voltage;
`• ensure high quality of the injected power;
`• grid synchronization.
`
`The items listed above for the grid-side converter are the ba-
`sic features this converter should have. Additionally, ancillary
`services like local voltage and frequency regulation, voltage
`harmonic compensation, or active filtering might be requested
`by the grid operator.
`As previously pointed out, the power conversion unit has
`different hardware structures, which are closely related to the
`input power nature. The following section presents the revision
`of the technologies mostly used today in FC and PV systems as
`well as WT systems.
`
`

`

`1400
`
`IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 53, NO. 5, OCTOBER 2006
`
`only delivered into the rotor from the grid. A speed variation of
`60% around synchronous speed may be obtained by the use of
`a power converter of 30% of nominal power [5].
`By implementing a full-scale power converter between the
`generator and the utility grid, additional technical performances
`of the WT system can be achieved, with the payback in losses
`in the power conversion stage. Normally, as shown in Fig. 4(c),
`SCIG is used in this configuration, but an advantage to elim-
`inate the gearbox can be obtained by using multipole wound-
`rotor synchronous generator or permanent-magnet synchronous
`generator, as depicted in Fig. 4(d).
`It could be noticed that for interacting with the power system,
`all the structures presented above use two-level pulsewidth-
`modulation (PWM) voltage-source inverters (VSI) because this
`is the state-of-the-art technology used today by all manufactur-
`ers of wind systems. The possibility of high switching frequen-
`cies combined with a proper control makes these converters
`suitable for grid interface in the case of distributed generation,
`which has a large contribution to the improvement of generated
`power quality.
`Yet, three-level neutral-point-clamped VSI is an option for
`high-power WT systems (5 MW) to avoid high-voltage power
`devices. Attempts of using multilevel [14] or matrix converters
`[15], [16] have been made, but the use of these technologies is
`not validated yet in the field of distributed generation.
`Therefore, the next section presents discussion on the con-
`trol structures and strategies applied to two-level VSI PWM-
`driven converters, focusing on the grid-side converter control.
`Control structures implemented in different reference frames
`are presented, and the possibility of compensating for low-order
`harmonics is discussed. Moreover, control strategies when grid
`faults occur are considered.
`
`IV. CONTROL STRUCTURES FOR GRID-CONNECTED DPGS
`
`The control strategy applied to the grid-side converter con-
`sists mainly of two cascaded loops. Usually, there is a fast
`internal current loop, which regulates the grid current, and
`an external voltage loop, which controls the dc-link voltage
`[17]–[22]. The current loop is responsible for power quality
`issues and current protection; thus, harmonic compensation and
`dynamics are the important properties of the current controller.
`The dc-link voltage controller is designed for balancing the
`power flow in the system. Usually, the design of this controller
`aims for system stability having slow dynamics.
`In some works, the control of grid-side controller is based
`on a dc-link voltage loop cascaded with an inner power loop
`instead of a current loop. In this way, the current injected into
`the utility network is indirectly controlled [23].
`Moreover, control strategies employing an outer power loop
`and an inner current loop are also reported [24].
`In the following, a division of the control strategies in respect
`to the reference frame they are implemented in is given, and the
`main properties of each structure are highlighted.
`
`A. Synchronous Reference Frame Control
`
`Synchronous reference frame control, also called dq control,
`uses a reference frame transformation module, e.g., abc → dq,
`
`Fig. 4. WT systems using power electronics. (a) Minimum electronics unit.
`(b) Partial power converter. (c) Full-scale power converter structure with
`gearbox. (d) Full-scale power converter structure without gearbox and using
`multipole synchronous generator.
`
`The usage of power electronics into WT systems can be
`further divided into two categories, namely: 1) systems using
`partial-scale power electronics units and 2) systems using full-
`scale power electronics units. A particular structure is to use an
`induction generator with a wounded rotor. An extra resistance
`controlled by power electronics is added in the rotor, which
`gives a variable speed range of 2% to 4%. The power converter
`for the rotor resistance control is for low voltage but high
`currents. In any case, this solution also needs a soft starter and
`a reactive power compensator [5].
`Additionally, another solution is to use a medium-scale
`power converter with a wounded rotor induction generator, as
`shown in Fig. 4(b). In this case, a power converter connected
`to the rotor through slip rings controls the rotor currents.
`If the generator is running supersynchronously, the electrical
`power is delivered through both the rotor and stator. If the
`generator is running subsynchronously, the electrical power is
`
`

`

`BLAABJERG et al.: OVERVIEW OF CONTROL AND GRID SYNCHRONIZATION FOR DPGSs
`
`1401
`
`Fig. 5. General structure for synchronous rotating frame control structure.
`
`Fig. 6. General structure for stationary reference frame control strategy.
`
`to transform the grid current and voltage waveforms into a ref-
`erence frame that rotates synchronously with the grid voltage.
`By means of this, the control variables become dc values; thus,
`filtering and controlling can be easier achieved [25].
`A schematic of the dq control is represented in Fig. 5. In
`this structure, the dc-link voltage is controlled in accordance to
`the necessary output power. Its output is the reference for the
`active current controller, whereas the reference for the reactive
`current is usually set to zero, if the reactive power control is not
`allowed. In the case that the reactive power has to be controlled,
`a reactive power reference must be imposed to the system.
`The dq control structure is normally associated with
`proportional–integral (PI) controllers since they have a satisfac-
`tory behavior when regulating dc variables. The matrix transfer
`function of the controller in dq coordinates can be written as
`
`(cid:2)
`
`(dq)
`PI (s) =
`
`G
`
`Kp + Ki
`0
`
`s
`
`0
`Kp + Ki
`
`s
`
`(cid:3)
`
`(1)
`
`where Kp is the proportional gain and Ki is the integral gain of
`the controller.
`Since the controlled current has to be in phase with the grid
`voltage, the phase angle used by the abc → dq transformation
`module has to be extracted from the grid voltages. As a solution,
`filtering of the grid voltages and using arctangent function
`to extract the phase angle can be a possibility [26]–[28]. In
`addition, the phase-locked loop (PLL) technique [29]–[33]
`became a state of the art in extracting the phase angle of the
`grid voltages in the case of distributed generation systems.
`
`For improving the performance of PI controller in such a
`structure as depicted in Fig. 5, cross-coupling terms and voltage
`feedforward are usually used [17], [19], [25], [34], [35]. In any
`case, with all these improvements, the compensation capability
`of the low-order harmonics in the case of PI controllers is
`very poor, standing as a major drawback when using it in grid-
`connected systems.
`
`B. Stationary Reference Frame Control
`
`Another possible way to structure the control loops is to
`use the implementation in stationary reference frame, as shown
`in Fig. 6. In this case, the grid currents are transformed into
`stationary reference frame using the abc → αβ module. Since
`the control variables are sinusoidal in this situation and due
`to the known drawback of PI controller in failing to remove
`the steady-state error when controlling sinusoidal waveforms,
`employment of other controller types is necessary. Proportional
`resonant (PR) controller [36]–[39] gained a large popularity in
`the last decade in current regulation of grid-tied systems.
`In the PR case, the controller matrix in the stationary refer-
`ence frame is given by
`
`(cid:2)
`
`(αβ)
`PR (s) =
`G
`
`Kp + Kis
`s2+ω2
`0
`
`0
`Kp + Kis
`s2+ω2
`
`(cid:3)
`
`(2)
`
`where ω is the resonance frequency of the controller, Kp is the
`proportional gain, and Ki is the integral gain of the controller.
`
`

`

`1402
`
`IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 53, NO. 5, OCTOBER 2006
`
`Fig. 7. General structure for natural reference frame control strategy.
`
`Characteristic to this controller is the fact that it achieves
`a very high gain around the resonance frequency, thus being
`capable to eliminate the steady-state error between the con-
`trolled signal and its reference [38]. The width of the frequency
`band around the resonance point depends on the integral time
`constant Ki. A low Ki leads to a very narrow band, whereas a
`high Ki leads to a wider band.
`Moreover, high dynamic characteristics of PR controller have
`been reported in different works [39], [40].
`
`C. Natural Frame Control
`
`The idea of abc control is to have an individual controller
`for each grid current; however, the different ways to connect
`the three-phase systems, i.e., delta, star with or without isolated
`neutral, etc., is an issue to be considered when designing
`the controller. In the situation of isolated neutral systems, the
`phases interact to one another; hence, only two controllers are
`necessary since the third current is given by the Kirchhoff
`current law. In any case, the possibility of having three inde-
`pendent controller is possible by having extra considerations in
`the controller design as usually is the case for hysteresis and
`dead-beat control.
`Normally, abc control is a structure where nonlinear con-
`trollers like hysteresis or dead beat are preferred due to their
`high dynamics. It is well known that the performance of these
`controllers is proportional to the sampling frequency; hence,
`the rapid development of digital systems such as digital signal
`
`processors or field-programmable gate array is an advantage for
`such an implementation.
`A possible implementation of abc control is depicted in
`Fig. 7, where the output of dc-link voltage controller sets the
`active current reference. Using the phase angle of the grid
`voltages provided by a PLL system, the three current references
`are created. Each of them is compared with the corresponding
`measured current, and the error goes into the controller. If
`hysteresis or dead-beat controllers are employed in the current
`loop, the modulator is not anymore necessary. The output of
`these controllers is the switching states for the switches in the
`power converter. In the case that three PI or PR controllers are
`used, the modulator is necessary to create the duty cycles for
`the PWM pattern.
`1) PI Controller: PI controller is widely used in conjunction
`with dq control, but its implementation in abc frame is also
`possible as described in [35]. The transfer function of the
`controller in this case becomes (3), shown at the bottom of the
`page, and the complexity of the controller matrix in this case,
`due to the significant off-diagonal terms representing the cross
`coupling between the phases, is noticeable.
`2) PR Controller: The implementation of PR controller in
`abc is straightforward since the controller is already in station-
`ary frame and implementation of three controllers is possible
`as illustrated in (4), shown at the bottom of the page. Again,
`in this case, the influence of the isolated neutral in the control
`has to be accounted; hence, the third controller is not neces-
`sary in (4). However, it is worth noticing that the complexity
`
`⎡⎢⎢⎢⎣
`

`
`2 3
`
`⎡⎢⎣
`
`(abc)
`G
`PI
`
`(s) =
`
`(abc)
`PR (s) =
`G
`
`(3)
`
`(4)
`
`⎤⎥⎥⎥⎦
`
`2 − Kis−√
`− Kp
`3Kiω0
`2·(s2+ω2
`0)
`√
`
`− Kp2 − Kis+
`3Kiω0
`2·(s2+ω2
`0)
`Kp + Kis
`s2+ω2
`0
`
`√
`− Kp2 − Kis+
`
`3Kiω0
`2·(s2+ω2
`0)
`Kp + Kis
`s2+ω2
`2 − Kis−√
`0
`− Kp
`3Kiω0
`2·(s2+ω2
`0)
`0
`0
`Kp + Kis
`s2+ω2
`0
`
`⎤⎥⎦
`
`Kp + Kis
`s2+ω2
`2 − Kis−√
`0
`− Kp
`3Kiω0
`2·(s2+ω2
`0)
`√
`2 − Kis+
`− Kp
`3Kiω0
`2·(s2+ω2
`0)
`Kp + Kis
`0
`s2+ω2
`0
`0
`Kp + Kis
`s2+ω2
`0
`0
`0
`
`

`

`BLAABJERG et al.: OVERVIEW OF CONTROL AND GRID SYNCHRONIZATION FOR DPGSs
`
`1403
`
`TABLE I
`DISTORTION LIMITS FOR DISTRIBUTED GENERATION SYSTEMS
`SET BY IEC STANDARD [50]
`
`In addition, in the case of abc control, two modalities of
`implementing the PLL are possible. The first possibility is to
`use three single-phase PLL systems [33]; thus, the three phase
`angles are independently extracted from the grid voltages. In
`this case, the transformation module dq → abc is not anymore
`necessary, with the active current reference being multiplied
`with the sine of the phase angles. The second possibility is to
`use one three-phase PLL [31], [32], [48], [49]. In this case, the
`current references are created, as shown in Fig. 7. A discussion
`about the influence of the PLL in the control loop is given in
`Section VII.
`
`D. Evaluation of Control Structures
`
`The necessity of voltage feedforward and cross-coupling
`terms is the major drawbacks of the control structure imple-
`mented in synchronous reference frame. Moreover, the phase
`angle of the grid voltage is a must in this implementation. In the
`case of control structure implemented in stationary reference
`frame, if PR controllers are used for current regulation, the
`complexity of the control becomes lower compared to the
`structure implemented in dq frame. Additionally, the phase
`angle information is not a necessity, and filtered grid voltages
`can be used as template for the reference current waveform.
`In the case of control structure implemented in natural frame,
`the complexity of the control can be high if an adaptive band
`hysteresis controller is used for current regulation. A simpler
`control scheme can be achieved by implementing a dead-beat
`controller instead. Again, as in the case of stationary frame
`control, the phase angle information is not a must. Noticeable
`for this control structure is the fact that independent control
`of each phase can be achieved if grid voltages or three single-
`phase PLLs are used to generate the current reference.
`
`V. POWER QUALITY CONSIDERATIONS
`
`One of the demands present in all standards with regard
`to grid-tied systems is the quality of the distributed power.
`According to the standards in this field [13], [50]–[53], the
`injected current in the grid should not have a total harmonic
`distortion larger than 5%. A detailed image of the harmonic
`distortion with regard to each harmonic is given in Table I.
`As it was mentioned previously, one of the responsibilities of
`the current controller is the power quality issue. Therefore, dif-
`ferent methods to compensate for the grid harmonics to obtain
`an improved power quality are addressed in the following.
`
`Fig. 8. Structure of the dead-beat controller using an observer to compensate
`for the delay introduced by the controller.
`
`of the controller in this case is considerably reduced com-
`pared to (3).
`3) Hysteresis Controller: It is worth noticing that in the
`case of hysteresis control implementation, an adaptive band
`of the controller has to be designed to obtain fixed switching
`frequency. In [41]–[44], different methods and algorithms to
`obtain fixed switching frequency are presented.
`Since the output of the hysteresis controller is the state of
`the switches, considerations about the isolated neutral are again
`(cid:4)
`term is introduced in the formula of
`necessary. In [43], an a
`the hysteresis band (HB) to account for the load (transformer)
`connection type, i.e.,
`(cid:4)
`0.25a
`Udc
`fswLT
`
`(cid:11)
`
`(cid:10)
`1 − L2
`(cid:2)2Udca
`
`
`T
`
`∗
`+ di
`dt
`
`Ug
`LT
`
`(cid:13)
`
`(cid:12)2
`
`.
`
`(5)
`
`HB =
`
`In [45], a similar approach is used, but the current error is split
`into its noninteracting part ζ and the interacting part γ to resolve
`the equation for the variable HB.
`4) Dead-Beat Controller: The dead-beat controller attempts
`to null the error with one sample delay. The controller in its
`digital implementation is as follows:
`
`(6)
`
`(7)
`
`(cid:12)
`
`.
`
`· 1 − az
`−1
`1 − z−1
`where a and b are denoted as follows:
`− RT
`a = e
`LT
`b = − 1
`RT
`
`T s
`
`(cid:11)
`
`− RT
`e
`LT
`
`T s − 1
`
`1 b
`
`(abc)
`DB =
`G
`
`Since dead-beat controller regulates the current such that it
`reaches its reference at the end of the next switching period,
`the controller introduces one sample time delay. To compensate
`for this delay, an observer can be introduced in the structure of
`the controller, with the aim to modify the current reference to
`compensate for the delay [46], as shown in Fig. 8.
`The discrete transfer function of the observer is given by
`1
`1 − z−1
`thus, the new current reference becomes
`∗ − i).
`∗(cid:2) = F
`(abc)
`DB (i
`i
`
`(8)
`
`(9)
`
`(abc)
`DB =
`
`F
`
`As a consequence, a very fast controller containing no delay
`is finally obtained. Moreover, the algorithms of the dead-beat
`controller and observer are not complicated, which is suitable
`for microprocessor-based implementation [47].
`
`A. Harmonics Compensation Using PI Controllers
`
`Since PI controllers typically are associated with dq control
`structure, the possibilities for harmonic compensation are based
`
`

`

`1404
`
`IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 53, NO. 5, OCTOBER 2006
`
`Fig. 9. Method for compensating the positive sequence of the fifth harmonic in dq control structure.
`
`on low-pass and high-pass filters [54]. If the current controller
`has to be immune to the grid voltage harmonic distortion
`(mainly fifth and seventh in three-phase systems), harmonic
`compensator for each harmonic order should be designed.
`Fig. 9 shows the dq control structure having a harmonic com-
`pensator for the positive sequence of the fifth harmonic. In
`addition, under unbalanced conditions, harmonic compensators
`for both positive and negative sequences of each harmonic order
`are necessary. As a consequence, four compensators like the
`ones depicted in Fig. 9 are necessary to compensate for the
`fifth and seventh harmonics. The complexity of the control
`algorithm is noticeable in this case.
`
`B. Harmonics Compensation Using PR Controllers
`
`In the case of PR control implementation, things are dif-
`ferent. Harmonic compensation can be achieved by cascading
`several generalized integrators tuned to resonate at the desired
`frequency. In this way, selective harmonic compensation at dif-
`ferent frequencies is obtained. In [38], the transfer function of
`a typical harmonic compensator (HC) designed to compensate
`the third, fifth, and seventh harmonics is given as follows:
`
`Kih
`
`s
`s2 + (ω · h)2 .
`
`(10)
`
`(cid:14)
`
`h=3,5,7
`
`Gh(s) =
`
`In this case, it is easy to extend the capabilities of the
`scheme by adding harmonic compensation features simply with
`more resonant controllers in parallel to the main controller, as
`illustrated in Fig. 10. The main advantage in this situation is
`given by the fact that the harmonic compensator works on both
`positive and negative sequences of the selected harmonic; thus,
`only one HC is necessary for a harmonic order.
`An interesting feature of the HC is that it does not affect the
`dynamics of the PR controller, as it only reacts to the frequen-
`cies very close to the resonance frequency. This characteristic
`
`Fig. 10. Structure of the harmonic compensator attached to the resonant
`controller of the fundamental current.
`
`makes the PR controller a successful solution in applications
`where high dynamics and harmonics compensation, especially
`low-order harmonics, are required, as in the case of a DPGS.
`
`C. Harmonics Compensation Using Nonlinear Controllers
`
`Since both hysteresis and dead-beat controller have very fast
`dynamics, there is no concern about the low-order harmonics
`when the implemented control structure uses such controllers.
`In any case, it should be noticed that the current waveform will
`contain harmonics at switching and sampling frequencies order.
`Another issue is the necessity of fast sampling capabilities of
`the hardware used.
`
`D. Evaluation of Harmonic Compensators
`
`The necessity of using two filters, two transformation mod-
`ules, and one controller to compensate for the positive sequence
`of only one harmonic makes the harmonic compensator imple-
`mented in dq frame to be not a practical solution. On the other
`
`

`

`BLAABJERG et al.: OVERVIEW OF CONTROL AND GRID SYNCHRONIZATION FOR DPGSs
`
`1405
`
`capabilities for a DPGS, the influence of the unbalance should
`be minimized when running under faulty conditions.
`With regard to the control strategy under faults, four major
`possibilities are available.
`
`A. Unity Power Factor Control Strategy
`
`Fig. 11. Distributed generation system connected through a Δ/Y transformer
`to the utility network.
`
`hand, easier implementation is observed in the situation when
`the control structure is implemented in stationary reference
`frame since the structure of the compensator is reduced and it
`acts on both positive and negative sequences.
`
`VI. CONTROL STRATEGY UNDER GRID FAULTS
`
`Due to the large amount of distributed power generation con-
`nected to the utility networks in some countries, instability of
`the power system may arise. As a consequence, more stringent
`demands for interconnecting the DPGS to the grid are issued.
`Among all the requests, more and more stress is put on the
`ability of a DPGS to ride through short grid disturbances such
`as voltage and frequency variations.
`The grid faults can be classified in two main categories [55].
`1) Symmetrical fault is when all three grid voltages register
`the same amplitude drop but the system remains balanced
`(no phase shifting is registered). This type of fault is very
`seldom in the power systems.
`2) Unsymmetrical fault is when the phases register an un-
`equal amplitude drop together with phase shifting be-
`tween them. This type of fault occurs due to one or two
`phases shorted to ground or to each other.
`By considering the DPGS connected to the utility network
`as shown in Fig. 11, where a distribution transformer is used
`by the generation system to interface the power system, the
`propagation of a voltage fault occurring at bus 1 appears
`different at bus 2. For example, if a severe grid fault like
`single phase shorted to ground takes place at bus 1, two of the
`voltages at the DPGS terminals (after the Δ/Y transformer)
`experience a voltage drop that is dependent on the impedance
`of the line between the fault and DPGS transformer value. As a
`consequence, the voltages at bus 2 will register both amplitude
`and phase unbalance [55].
`the negative
`Since this case is an unsymmetrical fault,
`sequence appears in the grid voltages. This creates second-
`harmonic oscillations that propagate in the system, which ap-
`pear in the dc-link voltage as a ripple [56]. Moreover, the
`control variables are also affected by this phenomenon. In
`[57]–[59], it has been shown that the PLL system can be
`designed to filter out the negative sequence, which produces
`a clean synchronization signal. If the three-phase PLL system
`is not designed to be robust to unbalanced, second-harmonic
`oscillations will appear in the phase angle signal, thus in the
`current reference.
`In addition, the second-harmonic ripple present in the dc-link
`voltage will also have a negative influence in generation of the
`current reference. As a consequence, to provide ride-through
`
`(11)
`
`i = gv,
`
`One of the control strategies that a DPGS can adopt on grid
`faults is to maintain unity power factor during the fault. The
`most efficient set of currents delivering the instantaneous active
`power P to the grid can be calculated as follows:
`g = P|v|2
`where g is the instantaneous conductance seen from the inverter
`output, and |v| denotes the module of the three-phase voltage
`vector v. Its value is constant in balanced sinusoidal condi-
`tions, but under grid faults, the negative sequence component
`gives rise to oscillations at twice the fundamental frequency
`in |v|. Consequently, the injected currents will not keep their
`sinusoidal waveform, and high-order components will appear
`in their waveform. Current vector of (11) is instantaneously
`proportional to the voltage vector and, therefore, does not have
`any orthogonal component in relation to the grid voltage, hence
`giving rise to the injection of no reactive power to the gr

This document is available on Docket Alarm but you must sign up to view it.


Or .

Accessing this document will incur an additional charge of $.

After purchase, you can access this document again without charge.

Accept $ Charge
throbber

Still Working On It

This document is taking longer than usual to download. This can happen if we need to contact the court directly to obtain the document and their servers are running slowly.

Give it another minute or two to complete, and then try the refresh button.

throbber

A few More Minutes ... Still Working

It can take up to 5 minutes for us to download a document if the court servers are running slowly.

Thank you for your continued patience.

This document could not be displayed.

We could not find this document within its docket. Please go back to the docket page and check the link. If that does not work, go back to the docket and refresh it to pull the newest information.

Your account does not support viewing this document.

You need a Paid Account to view this document. Click here to change your account type.

Your account does not support viewing this document.

Set your membership status to view this document.

With a Docket Alarm membership, you'll get a whole lot more, including:

  • Up-to-date information for this case.
  • Email alerts whenever there is an update.
  • Full text search for other cases.
  • Get email alerts whenever a new case matches your search.

Become a Member

One Moment Please

The filing “” is large (MB) and is being downloaded.

Please refresh this page in a few minutes to see if the filing has been downloaded. The filing will also be emailed to you when the download completes.

Your document is on its way!

If you do not receive the document in five minutes, contact support at support@docketalarm.com.

Sealed Document

We are unable to display this document, it may be under a court ordered seal.

If you have proper credentials to access the file, you may proceed directly to the court's system using your government issued username and password.


Access Government Site

We are redirecting you
to a mobile optimized page.





Document Unreadable or Corrupt

Refresh this Document
Go to the Docket

We are unable to display this document.

Refresh this Document
Go to the Docket