throbber
TRANSMISSION LINE
`TRANSFORMERS
`
`by Jerry Sevick, WZFMI
`
`I Znd Edition I
`
`•
`
`Published by - - - - - - - (cid:173)
`the American Radio Relay League
`
`225 Main Street
`Newington, CT 06111
`
`Ex.1029 p.1
`
`

`
`..
`
`Copyright© 1990 by
`
`The American Radio Relay League, Inc
`
`Copyright secured under the Pan-American
`Convention
`
`This work is publication No. 75 of the Radio
`Amateur's Library, published by the League. All
`rights reserved. No part of this work may be
`reproduced in any form except by written
`permission of the publisher. All rights of
`translation are reserved.
`
`Printed in USA
`
`Quedan reservados todos los derechos
`
`ISBN: 0-87259-296-0
`
`$20.00 in USA
`
`Second Edition
`Second Printing, 1991
`
`Ex.1029 p.2
`
`

`
`Contents
`
`Preface
`About the Author
`
`Chapter 1 Analysis
`1.1
`Introduction
`1.2 The Basic Building Block
`1.3 The Guanella Analysis
`1.4 The Ruthroff Analysis
`
`Chapter 2 Low-Frequency Characterization
`2.1
`Introduction
`2.2 Low-Frequency Analyses of Ruthroff 's
`1 :4 Transformers
`2.3 Low-Frequency Analyses of Guanella's
`1 :4 Transformers
`2.4 The Rod v the Toroid
`2.5 Rod Parameters
`
`Chapter 3 High-Frequency Characterization
`3.1
`Introduction
`3.2 Experiment v Theory
`3.3 To Twist or Not to Twist
`3.4 The Autotransformer v the
`Transmission Line Transformer
`Ferrites and Frequency Response
`
`3.5
`
`Chapter 4 Transformer Parameters for Low-Impedance
`Applications
`4.1
`Introduction
`4.2
`Stripline Transformers
`4.3 Low-Impedance Coaxial Cable Transformers
`4.4 The Third Winding
`
`Ex.1029 p.3
`
`

`
`Chapter 5 Transformer Parameters for High-Impedance
`Applications
`5.1
`Introduction
`5.2 High-Impedance Limitations
`5.3 Long Transmission Lines
`5.4 Variable Characteristic Impedance Lines
`5.5
`Series Transformers
`
`Chapter 6 1:4 Unbalanced-to-Unbalanced Transformer Designs
`6.1
`Introduction
`6.2
`Schematics and Pictorials
`6.3
`12.5:50-0 Ununs
`6.4
`25:100-0, 50:200-Q and 75:300-0 Ununs
`
`Chapter 7 Unbalanced-to-Unbalanced Transformer Designs
`with Impedance Ratios Less Than 1:4
`7 .1
`Introduction
`1:1.5Ununs
`7.2
`7.2.1 Tapped-Bifilar Transformers
`7 .2.2 Quintufilar Transformers
`1:2 Ununs
`1:3 Ununs
`
`7.3
`7.4
`
`Chapter 8 Unbalanced-to-Unbalanced Transformer Designs
`with Impedance Ratios Greater Than 1:4
`8.1
`Introduction
`8.2 Guanella Transformers
`8.2.1 5.56:50-0 Ununs
`8.2.2 50:300-0 Ununs
`8.2.3 50:450-0 Ununs
`8.2.4 50:600-0 Ununs
`8.2.5 50:800-Q Ununs
`8.3 Ruthroff-Type Transformers
`8.3.1 5.56:50-0 Ununs
`8.3.2 50:450-0 Ununs
`8.3.3 3.125:50-0 Ununs
`8.4 Ruthroff-Guanella Transformers
`8.5 Coaxial Cable Transformers: Ruthroff-Type
`
`Ex.1029 p.4
`
`

`
`Chapter 9 Baluns
`9 .1
`Introduction
`9.2 The 1: 1 Balun
`9.2.1 Rod v Toroidal Baluns
`9.2.2 Bifilar v Trifilar Baluns
`9.2.3 Air-Core v Ferrite-Core Baluns
`9.3 The 1 :4 Balun
`9.3.1 50:200-Q Baluns
`9.3.2 75:300-Q Baluns
`9.3.3 25:1 00-Q Baluns
`9.3.4 12.5:50-Q Baluns
`9.4 The 1:9Balun
`9.5 Baluns for Yagi, Quad and Rhombic Antennas
`9.5.1 Yagi Beams
`9.5.2 Quad Antennas
`9.5.3 Rhombic Antennas
`
`Chapter 10 Multimatch Transformers
`10.1
`Introduction
`10.2 Dual-Output Transformers
`10.2.1 1:1.5 and 1:3 Ratios
`10.2.2 1 :2 and 1 :4 Ratios
`10.3 Parallel Transformers
`10.4 Dual-Output, Parallel Transformers
`10.5 8-Ratio Transformer
`
`Chapter 11 Materials and Power Ratings
`11 .1
`Introduction
`11. 2 History of Ferrites
`11.3 Experimental Results
`11.4 Power Ratings
`11.5 Suppliers of Materials
`
`Chapter 12 Simple Test Equipment
`12. 1 Introduction
`12.2 The Wheatstone Bridge
`12.3 A High-Frequency Resistive Bridge
`12.4 Signal Generators
`12.5 Efficiency Measurements- The Soak Test
`12.6 Characteristic Impedance Measurements
`
`Ex.1029 p.5
`
`

`
`Chapter 13 Hints and Kinks
`13 .1
`Introduction
`13.2 Selecting Ferrites- Substitutions
`13.3 Winding Rod Transformers
`13.4 Winding Toroidal Transformers
`13.5 Constructing Low-Impedance Coaxial Cable
`13.6 The Care and Handling of Ferrite Transformers
`Chapter 14 Summary Statements
`Chapter 15 References
`
`Ex.1029 p.6
`
`

`
`Chapter 1
`
`Analysis
`
`Sec 1.1 Introduction
`
`T here are two basic methods for constructing broadband, imped(cid:173)
`
`ance-matching transformers. One employs the conventional
`transformer that transmits the energy to the output circuit by
`flux linkages; the other uses the transmission line transformer to trans(cid:173)
`mit the energy by a transverse transmission line mode. With techniques
`exploiting high magnetic efficiency, conventional transformers have
`been constructed to perform over wide bandwidths. Losses on the order
`of one decibel can exist over a range from a few kilohertz to over
`200 MHz. Throughout a considerable portion of this band, the losses
`are only 0.2 dB.
`On the other hand, transmission line transformers exhibit far
`wider bandwidths and much greater efficiencies. The stray inductances
`and interwinding capacitances are generally absorbed into the charac(cid:173)
`teristic impedance of the transmission line. As such, they form no
`resonances that could seriously limit the high-frequency response. Here
`the response is limited by the deviation of the characteristic impedance
`from the optimum value; the parasitics not absorbed into the character(cid:173)
`istic impedance of the transmission line; and, in some transformer
`configurations, the length of the transmission line.
`With transmission lines, the flux is effectively canceled out in the
`core and extremely high efficiencies are possible over large portions of
`the passband-losses of only 0.02 to 0.04 dB with certain core materials.
`Therefore, the power ratings of transmission line transformers are
`determined more by the ability of the transmission lines to handle the
`voltages and currents than by the size and conventional properties of
`the core.
`The earliest presentation on transmission line transformers was
`by Guanella in 1944 (ref 1). 1 He proposed the concept of coiling
`
`1 Each reference in this chapter can be found in Chapter 15.
`
`Analysis
`
`1-1
`
`Ex.1029 p.7
`
`

`
`transmission lines to form a choke that would reduce the undesired
`mode in balanced-to-unbalanced matching applications. Before this
`time, this type of device, known as a balun, was constructed from
`quarter- or half-wavelength transmission lines and, as such, had very
`narrow bandwidths. By combining coiled transmission lines in parallel(cid:173)
`series arrangements, he was able to demonstrate broadband baluns with
`ratios of 1 :n2, where n is the number of transmission lines. Other writers
`followed with further analyses and applications of the balun transformer
`introduced by Guanella (refs 2-8). In 1959, Ruthroff published another
`significant work on this subject (ref 9). By connecting a single trans(cid:173)
`mission line such that a negative or a positive potential gradient existed
`along the length of the line, he was able to demonstrate a broadband 1 :4
`balun or unun (unbalanced-to-unbalanced) transformer. He also intro(cid:173)
`duced in his paper the hybrid transformer. Many extensions and appli(cid:173)
`cations of his work were published and are included in the reference list
`(refs 10-28).
`In a general comparison, it can be said that the transmission line
`transformer enjoys the advantage of higher efficiency, greater
`bandwidth and simpler construction. The conventional transformer,
`however, remains capable of de isolation. The purpose of this chapter
`is twofold: to review Guanella's and Ruthroff's approaches to the
`analysis and understanding of these new wide-band transformers, and
`to present additional material to form a basis for the chapters that follow.
`
`Sec 1.2 The Basic Building Block
`The single bifilar winding, shown in Fig 1- 1, is the basic building
`block for the understanding and design of all transmission line trans(cid:173)
`formers. Higher orders of windings (trifilar, quadrifilar and so on) also
`perform in a similar transmission-line fashion and will be discussed in
`Chapter 7, which treats the subject of fractional-ratio transformers.
`The circuit of Fig 1- 1 can perform four different functions de(cid:173)
`pending upon how the output load, RL, is grounded. The functions are:
`(A) a phase-inverter when a ground is connected to terminal 4, (B) a
`balun when the ground is at terminal 5 or left off entirely (a floating
`load), (C) a simple delay line when a ground is at terminal 2, and (D) a
`"boot-strap" when + V 1 is connected to terminal 2. The operation of
`these four functions can be explained by simple transmission line theory
`and the choking reactance of the transmission lines. This choking
`reactance, which isolates the input from the output, is usually obtained
`
`1-2 Chapter 1
`
`Ex.1029 p.8
`
`

`
`Chapter 11
`
`Materials and Power
`Ratings
`
`Sec 11.1 Introduction
`
`I n Chapter 2 it was shown that the role of a transmission line
`
`transformer core is to enhance the choking action of the coiled
`windings to better isolate the input from the output circuit. Even
`though calculations were made for only the low-frequency performance
`of these transformers, experimental results demonstrated that the core
`influenced most of the operating region (see Sec 3.4).
`The analysis for toroidal cores confirms that the low-frequency
`response is directly related to the permeability of the core material. With
`higher permeabilities, fewer turns are required, allowing for higher-fre(cid:173)
`quency operation. It was also shown that rods, although not yielding the
`high reactance of the toroids, exhibit good low-frequency response and
`can be used in many applications. At low frequencies, the rod was found
`to be relatively insensitive to the permeability of the rod material
`because of the high reluctance of the air path around the core.
`Accurate loss measurements have shown that only a limited
`number of ferrite materials are useful in power applications, where high
`efficiency is an important consideration. This chapter describes trans(cid:173)
`mission line transformers that use nickel-zinc ferrite cores with per(cid:173)
`meabilities in the moderately low range of approximately 50 to 300, to
`yield efficiencies in excess of 98%. No conventional transformer can
`approach this performance. The losses are not a function of current as
`in the conventional transformer, but are, in most cases, related to the
`impedance levels at which the transformers are operated. This suggests
`a dielectric loss, rather than the conventional magnetic loss caused by
`core flux.
`Included in this chapter are: (A) a history of ferrites, (B) experi(cid:173)
`mental results on many of the typical ferrites when used with Ruthroff
`
`Materials and Power Ratings
`
`11·1
`
`Ex.1029 p.9
`
`

`
`l :4 unbalanced-to-unbalanced transformers, (C) new concepts in power
`ratings, and (D) suppliers of materials used in transmission line trans(cid:173)
`formers. Although no efficiency measurements have been obtained on
`Guanella transformers, it can be safely assumed that the results would
`be as good as those found on Ruthroff transformers.
`
`Sec 11.2 History of Ferrites
`With the discovery of magnetic ferrites by T. Takei in Japan, and
`the excitement brought about by the 1947 publication of work done at
`the Philips Research Laboratories in the Netherlands during World War
`II, new and improved devices emerged in the field of magnetics (refs
`30, 31). 1 The chemical formula for ferrites is MFe204, where M stands
`for any of the divalent ions: magnesium, zinc, copper, nickel, iron,
`cobalt or manganese, or a mixture of these ions. Except for compounds
`containing divalent iron ions, ferrites can be made with bulk resistivities
`in the range of 102 to 109 n-cm, compared to 10-5 n-cm for the
`ferromagnetic metals (such as powdered iron). This increase in bulk
`resistivity represents a major step forward for applications in frequency
`ranges heretofore unobtainable.
`Ferrite compositions are made by ceramic technology. This in(cid:173)
`volves intimate mixing of fine powders of appropriate oxides, com(cid:173)
`pressing the mixture and firing it in carefully controlled atmospheres at
`temperatures of about 1100 °C to 1200 °C. Single crystals have been
`made by several techniques. By using different combinations of oxides
`previously listed and variations in ceramic processing, the mixtures can
`be tailored to fit a wide variety of technical requirements. In fact, ferrites
`with similar specifications by various manufacturers have been found
`to exhibit different efficiencies in transmission line transformers. This
`is because the ferrite is not completely defined by its chemistry and
`crystal structure; it is also defined by its processing, that is, powder
`preparation, compact formation, sintering and machining the ferrite to
`its final shape.
`By the early 1950s, it was generally recognized that inductor
`cores of Permalloy dust had reached the point of diminishing returns in
`their application to higher and higher frequencies. A major contribution
`to the solution of the problem was made in 1952 by F. J. Schnettler and
`A. G. Ganz of Bell Labs, who developed a high-permeability manga-
`
`1 Each reference in this chapter can be found in Chapter 15.
`
`11 ·2 Chapter 11
`
`Ex.1029 p.10
`
`

`
`nese-zinc ferrite for use at telephone carrier frequencies of 100 kHz and
`higher (ref 32). This material has also found widespread use at lower
`frequencies in power transformers, fly back transformers and deflection
`yokes.
`In the 1960s and 1970s, Bell Labs scientists also made several
`important advances in linear ferrite properties, in response to the rising
`need for high-quality linear devices in the transmission area. This
`resulted in the development of a process for making suitable nickel-zinc
`ferrites capable of operating up to 500 MHz (ref 33). These advances
`were made by using cobalt additives and carefully controlled cooling.
`This form of ferrite is the best one for high-power transmission line
`transformers, and it is commercially available.
`While the use of ferrites in inductors and transformers for carrier
`frequencies had a major impact on communications, its impact on
`microwave and computer technology is of equal importance. The avail(cid:173)
`ability of magnetic oxides eventually led to the large family of non(cid:173)
`reciprocal magnetic devices that play a key role in microwave
`technology. The materials effort is credited largely to L. G. Van Uitert
`of Bell Labs. He proposed the substitution of nonmagnetic ions for
`magnetic ions in the ferrite structure to reduce internal fields and
`thereby lower the ferromagnetic resonance frequency.
`In the computer field, A. Schonberg of Steatit-Magnesia AG in
`Germany, and workers at MIT's Lincoln Laboratories, found a family
`of magnesium-manganese ferrites with remarkably square hysteresis
`loops for use in memory and other computer and switching applications.
`These devices subsequently gave way to the semiconductor logic and
`memory circuits of the mid-l 970s.
`Although considerable information is available on the theory and
`application of transmission line transformers, dating back to the classic
`papers of Guanella in 1944 and Ruthroff in 1959, virtually no investi(cid:173)
`gations have been made on the use of ferrites in power applications (refs
`1, 9). Discussions by the author with scientists and engineers from major
`laboratories working in the ferrite field confirm this lack of develop(cid:173)
`ment. The following sections will show the results obtained by the
`author on readily available ferrites and their use in high-power trans(cid:173)
`mission line transformers. It is of some interest to note the differences
`in the properties of ferrites resulting from variations in processing
`techniques used by the different manufacturers.
`
`Materials and Power Ratings
`
`11-3
`
`Ex.1029 p.11
`
`

`
`Sec 11.3 Experimental Results
`
`Early experiments by the author indicated that the bulk resistivity
`of ferrite material could be related to high-efficiency operation. There(cid:173)
`fore, many of the major suppliers were asked to supply samples of their
`highest-resistivity material. Table 11 -1 is a list of suppliers who pro(cid:173)
`vided samples, the code symbol for their materials, the low-frequency
`(initial) permeabilities and the bulk resistivities. Powdered iron was
`included because it has been used for some applications, but as will be
`shown, it suffers by comparison because of its very low permeability.
`All of the data presented in this book on loss as a function of
`frequency were obtained at Bell Labs on a computer-operated transmis(cid:173)
`sion measuring set with an accuracy of one to two millidecibels over a
`frequency range of 50 Hz to 1000 MHz (refs 34, 35, 36). As a reference,
`it should be noted that a loss of 44 millidecibels represents a loss of I%,
`or an efficiency of 99%. Actual data shows that many of the transform(cid:173)
`ers, made using the best ferrite materials, exhibit losses over a consid-
`
`Table 11-1
`
`Cores, Suppliers and Specifications
`
`Material
`
`Supplier
`
`01 (NiZn)
`
`Allen-Bradley
`(formerly Indiana General)
`Allen-Bradley
`G (NiZn)
`Allen-Bradley
`02 (NiZn)
`H (NiZn)
`Allen-Bradley
`Ferroxcube
`4C4 (NiZn)
`3C8 (MnZn)
`Ferroxcube
`K5 (NiZn)
`MH&W Intl (TDK)
`KR6 (NiZn)
`MH&W Intl (TDK)
`CMD5005 (NiZn) Ceramic Magnetics
`C2025 (NiZn)
`Ceramic Magnetics
`CN20 (NiZn)
`Ceramic Magnetics
`C2050 (NiZn)
`Ceramic Magnetics
`E (Powdered
`Arnold Engineering,
`Iron)
`Amidon Associates
`
`11-4 Chapter 11
`
`Permeability Bulk Resistivity
`(Q-cm)
`108
`
`125
`
`300
`40
`850
`125
`2700
`290
`2000
`1400
`175
`800
`100
`10
`
`106
`
`109
`104 -105
`
`107 - 108
`102 - 103
`2 x 108
`105 -106
`7 x 109
`5 x 106
`106
`3 x 107
`10-2
`
`Ex.1029 p.12
`
`

`
`erable portion of their passbands of only 20 millidecibels, equivalent to
`efficiencies of 99.S%. Since short windings (wire lengths of 10 to lS
`inches) are generally used, very little loss is attributed to the windings.
`In fact, wires as thin as no. 18 can easily handle a kW of power. Although
`the previous chapters stress theory and design, many of the experimental
`results presented do display the high efficiency of the transmission line
`transformer. This section reveals the differences between the various
`ferrites and, in particular, stresses the effect of operation at impedance
`levels greater than 100 n.
`Figs 11-1, 11 -2 and 11-3 show the loss results of three 4:1
`transformers operating at three different impedance levels. Two are
`transmission line transformers and one is an autotransformer. The cores
`are similar in size, varying from 2.4 inches in OD for the Q 1 cores and
`2.62S inches for the KS core. The two transmission line transformers
`had S tightly wound bifilar turns of no. 14 wire, and the autotransformer
`had 10 tightly wound turns of no. 14 wire. Fig 11-4 depicts this type of
`winding. Fig 11 - 1 shows that the two transmission line transformers had
`about the same loss above 2 MHz. Below 2 MHz, the KS material was
`
`(/)
`
`0
`0.1
`0.2
`m 0.3
`'O 0.4
`(/) 0.5
`9 0.6
`a:::
`0.7
`LL.I u
`:::> 0.8
`0
`(/)
`z
`0.9
`<(
`a:::
`1.0
`.....
`1 .1
`1.2
`1.3
`1.40.1
`
`4:1 (50:12.5fi)
`TRANSFORMERS
`e TRANSMISSION LINE,
`K5
`6 TRANSMISSION LINE,
`Q1
`o AUlO, Q1
`
`I
`I
`
`1.0
`
`10
`FREQUENCY (MHz)
`
`100
`
`Fig 11 -1- Performance of 4:1 transformers operating at the 50:12.5-n
`level.
`
`Materials and Power Ratings
`
`11 -5
`
`Ex.1029 p.13
`
`

`
`J::r
`
`/a-0.00 ..
`
`t~f
`.
`
`.
`
`Q ••
`·q
`
`...
`
`tl.
`\
`q
`
`t
`I
`t
`1
`I
`~
`. i • TRANSMISSION LINE,
`K5
`~
`TRANSMISSION LINE,
`6 Q1
`~
`0 Aum, Q1
`
`4:1 (75:18.75il)
`TRANSFORMERS
`

`
`~
`
`1.0
`
`10
`FREQUENCY (MHz)
`
`100
`
`Fig 11-2- Performance of 4:1 transformers operating at the 75:18.75-Q
`level.
`
`0
`
`0 .1
`
`0 .2
`0.3
`m 0.4
`~
`(/) 0.5
`(/)
`0 0.6
`...J
`a::: 0.7
`w
`B 0.8
`(/) 0.9
`z
`<{ 1.0
`a:::
`I-
`1.1
`
`1.2
`
`1 .3
`
`1.4
`
`0.1
`
`0
`0 .1
`0.2
`0.
`ID 0.4
`~
`(/) 0 .5
`(/) g 0 .6
`a:::
`w 0 .7
`u 25 0 .8
`~ 0.9
`<{ 1.0
`a:::
`I-
`1.1
`1.2
`1.3
`1.4
`0.1
`
`I
`
`~
`'lt:r.0-0·0-o
`f/f
`..
`•
`l
`I
`
`G..
`
`~
`
`'\
`\
`~
`
`\
`
`4:1 ( 100: 25n)
`TRANSFORMERS
`•
`TRANSMISSION LINE,
`K5
`TRANSMISSION LI~,
`6 Q1
`0 AUTO,Q1
`
`~~
`f
`fl
`!/
`
`1.0
`
`10
`FREQUENCY (MHz)
`
`100
`
`Fig 11-3-Performance of 4:1 transformers operating at the 100:25-n
`level.
`
`11 -6 Chapter 11
`
`Ex.1029 p.14
`
`

`
`superior because of its higher permeability (290 compared to 12S for
`Ql material). The autotransformer showed not only a much narrower
`bandwidth, but also the greater loss of the conventional transformer
`(0.2 dB), which transmits the energy by coupling through flux linkages.
`Figs 11-2 and 11-3 show an interesting phenomenon of the KS material.
`At about 7 MHz, another loss mechanism comes into play. At the higher
`impedance levels of 100:2S Q of Fig 11-3, the loss beyond 10 MHz is
`more than double that of the Q 1 material. In fact, at 10 MHz, the loss is
`only 3S millidecibels for the Ql material and 80 millidecibels for the
`KS material. Fig 11-3 also shows that the 100:2S-Q impedance level
`yields the better high-frequency response for the type of winding used
`in the test. Although it is difficult to see from the idealized drawings in
`these figures, actual data shows that the midband loss of the autotrans(cid:173)
`former decreases from 0.22 dB to 0.19 dB in going to the higher
`impedance level of 100:25 n. This confirms the expected decrease in
`core loss at the higher impedance levels, where the currents are lower.
`To examine further the increase in the loss of transmission line
`transformers as a function of impedance levels, four 4: 1 transformers,
`using different core materials with windings similar to Fig 11-4, were
`
`Fig 11·4-The type of winding used In the 4:1 transformers of Figs 11-1,
`11-2 and 11 ·3.
`
`Materials and Power Ratings
`
`11·7
`
`L
`
`Ex.1029 p.15
`
`

`
`constructed and tested at the 200:50-Q level. The transformers used KS
`'
`Q 1, Q2 and Carbonyl E materials. The Q2-core transformer has 9 bifilar
`turns instead of 6 because of its lower permeability of 40. The results
`of the experiment are shown in Fig 11-5. The K5 and Ql cores show
`more loss at the higher impedance level. Also, there is a considerable
`slope in the passband for these two materials, which shows that the loss
`is frequency dependent. But the Q2 material exhibited the same constant
`low-loss characteristic of the Ql material at the lower impedance
`levels-about 40 millidecibels. The Carbonyl E core again exhibited a
`much poorer low-frequency response because of its low permeability
`of 10. Note that although the core's percentage bandwidth was small,
`the powdered iron exhibited a midband loss of only 0.07 dB at 50 MHz.
`This is still less than most of the ferrites listed in Table 11-1 operating
`at the 200:50-Q level. And finally, the Carbonyl E core exhibited the
`highest frequency response because its core had a smaller cross sec(cid:173)
`tional area, allowing a shorter transmission line with 6 turns. Con(cid:173)
`versely, the high-frequency response of the Q2 core was the poorest
`because of its much longer transmission line (9 turns).
`
`(,)
`
`ffi 0.7
`i5 0.8
`~ 0.9
`ct a: 1.0
`.... 1.1
`1.2
`1.3
`1.4L-~~~~~L..-...&.L..~~~~~~_.__~~~~~~.L--J
`0.1
`1.0
`10
`100
`FREQUENCY ( MHz)
`
`Fig 11-5-Loss v frequency of four 4:1 transformers at the 200:50-Q
`level.
`
`11-8 Chapter 11
`
`Ex.1029 p.16
`
`

`
`An interesting observation can be made on an earlier experiment
`which was described in Chapter 3. Fig 3-7 shows the performance of
`two transformers with optimized windings operating at the 40: 10-Q and
`200:50-Q level, each using 4C4 material. Although the higher-imped(cid:173)
`ance transformer exhibited the better high-frequency response, which
`was the point of the experiment, the transformer also maintained about
`the same low-loss characteristic of the lower-impedance transformer. In
`other words, 4C4 material appears to be less sensitive to impedance
`levels. This difference between Ql and 4C4 material may be caused by
`differences in processing. The 4C4 material is known to exhibit the
`normal B-H loop, while the Ql material exhibits the perminvar loop,
`which has steeper sides and a smaller enclosed area.
`Chapter 3 also shows data on G material (Fig 3-6). Losses of
`about 0.1 dB were noted at impedance levels of 75:18.75 n. This is
`about three times the loss of the Q 1 and 4C4 materials. The permeability
`of the G material is also about three times larger than the other two.
`Four ferrite toroids from Ceramic Magnetics were also investi(cid:173)
`gated. The results are shown in Fig 11 -6. These transformers used 6
`
`0
`
`0.2
`
`0.4
`
`Ill
`-0
`
`en 0.6
`en
`0
`....J
`a:: 0.8 -
`w
`u
`::::::>
`0
`en
`z
`<(
`a::
`I-
`
`1.0
`
`1.2
`
`4: 1 TRANSFORMERS I 50: 12.5 .0.
`N =6 TURNS STRIPLINE,
`w = 7/64 11 ,t=0.0028 11
`CERAMIC MAGNETICS
`CORES,OD =1.5"
`• c 2050-66-165-5,µ. = 100
`0 c 2025-18-172-4,µ. =175
`A CN 20-127-16-6, µ.=800
`o CMD 5005-R-107-8,µ.=1400
`
`0.1
`
`10
`1.0
`FREQUENCY (MHZ)
`
`100
`
`Fig 11-6-Loss v frequency for four core materials from Ceramic
`Magnetics with optimized windings for the 50:12.5-n level.
`
`Materials and Power Ratings 11-9
`
`Ex.1029 p.17
`
`

`
`CD
`~
`Cf)
`
`Cf) g
`a:
`w
`u
`::::>
`0
`Cf)· z
`<! a:
`I-
`
`MAGNETIC CERAMICS-5005
`N=G, L= 10.511
`N0.18 WIRE INSULATED
`
`•-100,25S1
`0-150, 37.5S1
`t;- 200'50S1
`o- 250,62.5S1
`
`1.0
`
`10
`
`100
`
`FREQUENCY (MHZ)
`
`Fig 11-7-Loss v frequency for a CMD5005 toroid from Ceramic
`Magnetics with optimized winding for the 200:50-n level.
`
`bifilar turns of 7/64-inch stripline, with Scotch no. 92 insulation, which
`is optimum for operation at the 50: 12.5-Q level. The cores had an OD
`of 1 V2 inches. Although their permeabilities ranged from 100 to 1400,
`the losses were about the same for the four different cores-less than
`0.08 dB over their passbands. This is particularly noteworthy for the
`CMD5005 material, which has a permeability of 1400. It is the lowest
`loss measured by the author on any of the higher-permeability materials.
`Coincidentally, its bulk resistivity of 7 x 109 0-cm is the highest of any
`of the ferrites. Fig 11-7 shows the results of the CMD5005 material at
`higher impedance levels. This transformer used 6 bifilar turns of
`Teflon-covered no. 18 wire, optimized for the 200:50-Q level. Note that
`the CMD5005 material shows an increased loss similar to that which
`most ferrites exhibit at higher impedance levels.
`These measurements on Ceramic Magnetics materials also bring
`out another important fact about transmission line transformers. Con(cid:173)
`ventional wisdom has stated that increased coupling between transmis(cid:173)
`sion lines is necessary for better low-frequency response. The results in
`Fig 11-6 show that the differences in low-frequency responses between
`these four materials are due to the differences in their permeabilities.
`
`11-10 Chapter 11
`
`Ex.1029 p.18
`
`

`
`0 ..----------------------~
`0.1
`0.2
`0.3
`
`'° o.4
`
`A~£:'0.
`IY"°~.~~·~·fYfY~
`·r. .. ~."°'
`... 'i
`~ ,..£!.·l':s·
`I i'
`,{:!
`"·
`\
`~ \
`"O
`Cf) 0.5
`~ /;
`~-b
`l
`I
`:'
`~ 0.6
`': \
`:p
`),
`_J
`a:: 0.7
`'(
`:. I
`I
`/
`': I
`~ 0.8
`f'
`" \
`:::::>
`I
`9 /
`~ 0.9
`~
`~ 1.0
`I
`:
`~ 1.1
`f
`I
`1.2
`I
`,:
`I
`1.3
`1.4..___-u-...._ __ __ _,_ _ _ __ _ __ ..__ _ __ __ ----1--J
`0.1
`1.0
`10
`100
`FREQUENCY (MHz)
`
`4:1 (200:50.0.)
`TRANSMISSION LINE
`TRANSFORMERS
`NO.
`MATERIAL TURNS
`5
`3C8
`5
`KR6
`5
`H
`
`•
`
`0
`6
`
`. .
`
`Fig 11-8-Measurements of 3C8, KR6 and H materials at the 200:50-n
`level.
`
`The transmission lines, and hence couplings, are the same. What is
`taking place here is that the reactance of the windings (and hence
`choking action) increases with permeability, thus resulting in better
`low-frequency response.
`Finally, Fig 11-8 shows measurements taken on 3C8, KR6 and H
`materials at the 200:50-n level. Even at lower impedance levels, these
`materials exhibit considerably more loss than the other materials al(cid:173)
`ready described. Incidentally, the 3C8 material is a manganese-zinc
`ferrite and has a high permeability of 2700. It is used extensively at low
`frequencies in power transformers, TV fly back transformers and deflec(cid:173)
`tion yokes. Ruthroff used this type of ferrite in his original work on
`transmission line transformers, but it is unsuitable for applications at
`power levels, where efficiency becomes a factor (ref 9).
`
`Sec 11.4 Power Ratings
`Power ratings are generally determined by two conditions: ( 1) the
`temperature rise due to losses, and (2) the exceeding of some maximum
`value of operating parameter by accident, which can create a cata(cid:173)
`strophic failure. A failure caused by an increase in temperature is usually
`
`Materials and Power Ratings
`
`11 -11
`
`Ex.1029 p.19
`
`

`
`time dependent, while the breakdown of a device operated over its
`preset value is instantaneous.
`With conventional transformers, losses can be separated into
`three categories: eddy-current losses, hysteresis losses and residual
`losses. These losses, together with the permeability of ferrite material,
`generally increase with temperature to create a possible runaway con(cid:173)
`dition. Catastrophic failures can occur with some ferrite materials at
`flux densities greater than 500 gauss. This is particularly true of ferrites
`exhibiting the perminvar loop; they become excessively lossy. Each of
`these conditions are related to flux densities and hence ampere-turns.
`Increasing the size of the core can, therefore, increase the power rating.
`Different conditions exist when a transmission line transformer's
`power rating is determined. Because of the canceling effect of the
`transmission line currents, little flux is generated in the core. This holds
`true even when tapped multiwindings are involved. Since losses with
`certain ferrites are only on the order of 20 to 40 millidecibels, very small
`transmission line transformers can handle surprisingly high power
`levels. Further, as was shown in the previous section, losses in most
`ferrite materials increase with impedance levels, and these levels must
`be considered when designing a transmission line transformer. Most
`failures in transmission line transformers are of the catastrophic type,
`and are usually caused by poorly terminated (or unterminated) trans(cid:173)
`formers. Such conditions create high voltages and a breakdown in the
`insulation between the windings. This is particularly true of close(cid:173)
`wound enameled or Formvar-type wires.
`Standards for setting power ratings for transmission line trans(cid:173)
`formers have not appeared in the literature, nor are they available from
`any of the suppliers of ferrite material. To the author's knowledge, the
`data presented in this book is the only quantitative information available
`on the losses of these transformers. Because limited reliability informa(cid:173)
`tion is available on transmission line transformers, and losses generally
`increase with impedance levels, an exact formulation of power ratings
`is difficult to make as of this writing. But as a result of the findings by
`the author, some general guidelines can be offered when considering
`ratings. They are:
`1) The power capability of these devices (when energy is trans(cid:173)
`mitted from input to output by a transmission line mode) is determined
`more by the size of the conductors, and not by the cores. Very small
`structures can handle amazingly high power levels. Thus, larger wires
`
`11-12 Chapter 11
`
`Ex.1029 p.20
`
`

`
`or the use of coaxial cable or stripline can more than double the power
`ratings.
`2) The voltage ratings can be increased significantly by the
`use of polyimide-coated wires. Some commercial brands are ML
`and H Imideze wires. In many cases, in order to optimize the charac(cid:173)
`teristic impedance of the windings, extra layers of Scotch no. 92 tape
`(another polyimide insulation) are used. This also increases the break(cid:173)
`down voltage.
`3) Generally, the lowest-permeability nickel-zinc ferrites yield
`the highest efficiencies. These have permeabilities in the range of 40 to
`50. But, these ferrites can limit the low-frequency response. When
`operating at impedance levels below 100 n, permeabilities as high as
`300 should yield very high efficiencies (98% to 99%). When operating
`at impedances above 100 n, the trade-off is low-frequency response for
`efficiency. Actually, most of the ferrites with permeabilities of 200 to
`300 can still yield acceptable efficiencies (at least 97%) at the 200- to
`300-Q impedance level.
`4) Very few differences in efficiency were observed from the
`ferrites supplied by the manufacturers listed in Sec 11.5. Limited mea(cid:173)
`surements on 4C4 material (µ = 125) from Ferroxcube showed the best
`efficiency at the 200-Q level. This material is also reported to be f

This document is available on Docket Alarm but you must sign up to view it.


Or .

Accessing this document will incur an additional charge of $.

After purchase, you can access this document again without charge.

Accept $ Charge
throbber

Still Working On It

This document is taking longer than usual to download. This can happen if we need to contact the court directly to obtain the document and their servers are running slowly.

Give it another minute or two to complete, and then try the refresh button.

throbber

A few More Minutes ... Still Working

It can take up to 5 minutes for us to download a document if the court servers are running slowly.

Thank you for your continued patience.

This document could not be displayed.

We could not find this document within its docket. Please go back to the docket page and check the link. If that does not work, go back to the docket and refresh it to pull the newest information.

Your account does not support viewing this document.

You need a Paid Account to view this document. Click here to change your account type.

Your account does not support viewing this document.

Set your membership status to view this document.

With a Docket Alarm membership, you'll get a whole lot more, including:

  • Up-to-date information for this case.
  • Email alerts whenever there is an update.
  • Full text search for other cases.
  • Get email alerts whenever a new case matches your search.

Become a Member

One Moment Please

The filing “” is large (MB) and is being downloaded.

Please refresh this page in a few minutes to see if the filing has been downloaded. The filing will also be emailed to you when the download completes.

Your document is on its way!

If you do not receive the document in five minutes, contact support at support@docketalarm.com.

Sealed Document

We are unable to display this document, it may be under a court ordered seal.

If you have proper credentials to access the file, you may proceed directly to the court's system using your government issued username and password.


Access Government Site

We are redirecting you
to a mobile optimized page.





Document Unreadable or Corrupt

Refresh this Document
Go to the Docket

We are unable to display this document.

Refresh this Document
Go to the Docket