throbber
Applications
`Engineering
`Manual
`
`Multiple-Chiller-System
`Design and Control
`
`SYS-APM001-EN (March 2001}
`
`PAGE 1 of 98
`
`PETITIONER'S EXHIBIT 1222
`
`

`
`Multiple-Chiller-System
`Design and Control
`
`Mick Schwedler, applications engineer
`Ann Yates, information designer
`
`PAGE 2 of 98
`
`PETITIONER'S EXHIBIT 1222
`
`

`
` TRAN?
`
`Preface
`
`This manual examines chilled-water-system components, configurations,
`options, and control strategies. The goal is to provide system designers with
`options they can use to satisfy the building owners‘ desires, but this manual is
`not intended to be a complete chiller-system design manual.
`
`System designers may get the most use from this manual by familiarizing
`themselves with chilled-water-system basics and understanding the benefits of
`various options. Thereafter, when a specificjob will benefit from these
`advantages, consult appropriate sections of the manual in detail.
`
`The Engineers Newsletters that are referenced in this manual are available at:
`www.trane.com/commercial/Iibrary/news|etters.asp
`
`The Trane Company, in proposing these system design and application
`concepts, assumes no responsibility for the performance or desirability of any
`resulting system design. System design is the prerogative and responsibility of
`the system designer.
`
`SYS-APM001-EN
`
`(9 2001 American Standard Inc. All rights reserved
`
`PAGE 3 of 98
`
`PETITIONER'S EXHIBIT 1222
`
`

`
` rmusr
`
`Contents
`
`Introduction ......................................................................................... ..1
`
`Chilled-Water-Plant Basics ............................................................. ..2
`
`Chilled-water distribution system ........... ..
`Condenser-water system .............................. ..
`Controls .................................................................................................. .. 11
`
`Chilled-Water-System Options .................................................. ..13
`Chi||ed— and condenser—water temperatures ................ ..
`Chi||ed- and condenser-water flow rates ...................... ..
`
`Misconceptions about low-flow rates . . . . . .
`
`.
`
`. .
`
`. . . . .
`
`.
`
`. . . . . . .
`
`.
`
`. . . ..24
`
`System Configurations ................................................................. ..27
`Parallel chillers ....................... ..
`Series chillers ................................................ ..
`
`Primary—secondary (decoupled) systems ............................................ ..31
`
`Pumping Arrangements ................................................................. .. 36
`Flow-based control ................................................................................. ..38
`
`Chiller sequencing ................................................................................. ..39
`
`Variable-Primary-Flow Systems ................................................ .. 40
`VPF advantages ...................................................................................... ..4’l
`VPF caveats ............................................................................................ ..4’l
`
`Chiller sequencing ................................................................................. ..43
`
`Chilled-Water-Control Options ................................................. .. 47
`Chi||ed—water reset—raising and lowering ........................................... ..47
`Critical valve reset .................................................................................. ..48
`
`Design Considerations .................................................................. ..49
`Chilled-water pump configurations ....................................................... ..49
`Bypass line sizing .................................................................................... ..50
`Amount of fluid in the loop .................................................................... ..50
`Plant expansion ....................................................................................... ..5’l
`
`SYS—APM001—EN
`
`PAGE 4 of 98
`
`PETITIONER'S EXHIBIT 1222
`
`

`
` TRAN?
`
`Contents
`
`Chi||ed-Water- System Variations .... ..
`Heat recovery ......................................................................................... .. 54
`Preferential loading ............................................................................... ..54
`Unequal chiller sizing ............................................................................ ..58
`Series-counterflow application .............................................................. ..58
`Applications outside the chi||er's range ............................................... ..60
`
`Chilled-Water-System Issues ...................................................... .. 63
`Low AT syndrome .......................................... ..
`Check valve in the bypass line ............................................................... ..63
`Failure recovery ...................................................................................... ..64
`Alternative energy sources .................................................................... ..64
`Contingency ........................................................................................... ..66
`
`Condenser-System Variations .................................................... .. 69
`Condenser flow configurations ............................................................ ..69
`Coo|ing—tower—fan control methods ..................................................... ..71
`Plate-and-frame heat exchanger .......................................................... .. 72
`Well, river, or lake water ........................................................................ ..72
`
`Condenser-water temperature control ................................................. .. 72
`Condenser—water pump options ............................................................ ..73
`Retrofit opportunities ............................................................................ .. 75
`
`Conclusion .......................................................................................... .. 78
`
`Glossary ............................................................................................... .. 79
`References .......................................................................................... .. 82
`
`Index ...................................................................................................... .. 85
`
`SYS—APM001—EN
`
`PAGE 5 of 98
`
`PETITIONER'S EXHIBIT 1222
`
`

`
` rmust
`
`Contents
`
`Figures
`Figure 1
`Figure 2
`Figure 3
`Figure 4
`Figure 5
`Figure 6
`Figure 7
`Figure 8
`Figure 9
`Figure 10
`Figure 11
`Figure 12
`Figure 13
`Figure 14
`Figure 15
`Figure 16
`Figure 17
`Figure 18
`Figure 19
`Figure 20
`Figure 21
`Figure 22
`Figure 23
`Figure 23a
`Figure 24
`Figure 25
`Figure 26
`Figure 27
`Figure 28
`Figure 29
`Figure 30
`Figure 31
`
`2
`Typical vapor—compression chiller ..................................... ..
`Valve-controlled loads ........................................................ .. 6
`Uncontrolled coil ................................................................. ..
`7
`
`Simplified distribution system ........................................... .. 9
`Chi||ed—water—system performance at part load ............... .. 19
`Annual system operating costs ......................................... .. 23
`System energy comparison (no pipe) ............................... .. 25
`Parallel chillers with single, common pump .................... .. 27
`Parallel chillers with separate, dedicated chiller pumps
`28
`Series chillers ...................................................................... .. 29
`
`Decoupled arrangement ..................................................... .. 31
`Production loop ................................................................... .. 33
`Distribution loop ................................................................. .. 34
`Campus pumping arrangement ........................................ .. 36
`Tertiary pumping arrangement .......................................... .. 37
`Decoupled system supply tee ............................................ .. 37
`Temperature-sensing .......................................................... .. 38
`Variable-primary-flow system ............................................ .. 40
`Doub|e—ended decoupled system ...................................... .. 53
`Parallel preferential loading arrangement ........................ .. 55
`Sidestream preferential loading arrangement ................. .. 56
`Plate-and-frame heat exchanger ....................................... .. 57
`Series—counterf|ow arrangement ....................................... .. 59
`Equal lift concept ....................................................... .. 59
`Flow rate out of range for equipment ............................... .. 60
`Temperatures out of range for equipment ....................... .. 61
`Precise temperature control, multiple chillers ................. .. 62
`Failure recovery ............................................................ .. 64
`Manifolded condenser-water pumps ................................ .. 69
`Chiller-tower energy consumption .................................... .. 73
`Decoupled condenser-water system ................................. .. 74
`Chi||er—tower selection with different chiller capacities..... 76
`
`SYS—APM001—EN
`
`PAGE 6 of 98
`
`PETITIONER'S EXHIBIT 1222
`
`

`
` TRAN?
`
`Contents
`
`Tables
`Table 1
`
`Table 2
`Table 3
`Table 4
`Table 5
`Table 6
`Table 7
`Table 8
`Table 9
`Table 10
`Table 11
`
`Recommended chi||er—monitoring points per
`ASHRAE Guideline 3-1996 ................................................. ..11
`
`Standard rating conditions for absorption chillers ........... ..15
`Standard rating conditions for chilled-water systems ..... ..16
`Low—f|ow conditions for chi||ed—water pump .................... ..17
`Low—f|ow conditions for cooling tower .............................. ..17
`Low-flow conditions for condenser-water pump .............. .. 17
`Total system power ............................................................. ..18
`Effect of decreased water temperature
`Retrofit capacity changes .................................................... ..21
`Reduced flow-rate effect ..................................................... ..24
`
`Flow-rate-fluctuation examples .......................................... ..44
`
`SYS—APM001—EN
`
`PAGE 7 of 98
`
`PETITIONER'S EXHIBIT 1222
`
`

`
` TRANEE
`
`Introduction
`
`Many building owners continually search for solutions that allow their
`businesses to offer higher quality, and to be more competitive and profitable.
`HVAC systems designers often use chi||ed—water systems to provide high-
`quality, cost-effective air conditioning for building owners. With the advent of
`more flexible chillers, system-level controls, and software analysis tools, the
`number of chilled-water-systems options has exploded.
`
`SYS-APM001-EN
`
`PAGE 8 of 98
`
`PETITIONER'S EXHIBIT 1222
`
`

`
`Chilled-Water-Plant Basics
`
`Chillnrl-walor plants consist of Those flJ|'If!TiI.".mfl| parts:
`
`Chillers that produce chilled water
`
`Loads, often satisfied by soils. that transfer heat from air to water
`
`Chilled-water distribution pumps and pipes that send chilled water to the
`previously mentioned loads
`
`Cr.-nrlnnsrer-wntr.-r pumps. pipes. and cooling towers that rrgjricl hunt
`(for wa1.or—r;oo|eLi chillers}
`
`Controls that coordinate the operation of the mechanical con'iponer'-ls
`together as a systrsrn
`
`Chiller
`
`Thorn arr! :1 variety nl watt.-r r:hI||r:r typos. Most commonly, they arr! ahsnrpllnn,
`ceritrifugal. |'1Is|i:.'a| rotary. and scroll. Surm-J recipruuatirig LIl"|i”l:.'FS are also
`available. Chillers can be either air- or water-cooled. Major vapor-compression
`chillr.-r cnrnpnnnnts il'1¢‘.|lJdI': an Evaporator, :1 cnmprnssorfis}, .1 cnnrlrsnsrsr, and
`an exparislori deuicolsj. This manual discusses the r;hil|er's evaporator and
`condenser and their relationship to the chi||ed—i.n.-ater plant.
`
`Figaro 1 Typical vapor-compression chiller
`
`Compressor
`
`I-
`
`:-
`
`I._
`
`Cond on star
`
`Eva porat-or
`
`SVSAPMGU1-EN
`
`PAGE 9 of 98
`
`PETITIONER'S EXHIBIT 1222
`
`

`
` TRANEE
`
`Chilled-Water-Plant Basics
`
`Evaporator
`
`The evaporator section of a water chiller is a shell-and-tube, refrigerant-to-
`water heat exchanger. Depending on the chi||er's design, either the refrigerant
`or the water is contained within the tubes.
`
`In a flooded she||—and—tube evaporator, cool, liquid refrigerant at low-
`pressure enters the distribution system inside the shell and moves
`uniformly over the tubes, absorbing heat from warmer water that flows
`through the tubes.
`
`In a direct-expansion (DX) shell-and-tube evaporator, warmer water fills the
`shell while the cool, |ower—pressure liquid refrigerant flows through the
`tubes.
`
`In either design, there is an approach temperature, which is the temperature
`difference between the refrigerant and exit water stream. The approach
`temperature is a measure of the heat transfer efficiency of the evaporator.
`
`Effect of chilled-water temperature
`
`For a given chiller, as the leaving chi||ed—water temperature drops, the
`refrigerant temperature and pressure must also drop. Conversely, as the
`leaving chilled-water temperature rises, so do the refrigerant temperature and
`pressure. When the leaving chilled-water temperature changes, the work a
`compressor must do also changes. The effect of leaving chilled-water
`temperature change on power consumption can be 1.0 percent to 2.2 percent
`per degree fahrenheit [1.8 percent to 4.0 percent per degree Celsius]. Always
`consider the energy consumption of the entire system—not only the chiller. It is
`important to remember that although reducing leaving chilled-water
`temperature penalizes the chiller, it may benefit the pumps because less water
`is pumped through the system. System interactions are covered in more detail
`in the next section Chilled—Water—System Options.
`
`Effect of chilled-water flow rate
`
`Since the evaporator is a heat exchanger, it is sensitive to water flow rate.
`Excessive flow may result in high water velocity, erosion, vibration, or noise.
`Insufficient flow reduces heat-transfer efficiency and causes poor chiller
`performance. Some designers have concerns over low flow rates causing
`fouling. Generally, as Webb and Li?’ noted, these concerns are unwarranted
`since the chilled-water loop is a closed system, thus reducing the chances of
`materials entering the system and causing fouling. Chi||ed—water flow through
`the chiller must be kept within specific minimum and maximum limits. Contact
`the manufacturer for these limits.
`
`SYS-APM001-EN
`
`PAGE 10 of 98
`
`PETITIONER'S EXHIBIT 1222
`
`

`
` TRAN?
`
`Chilled-Water-Plant Basics
`
`Some chiller controls can accommodate very little flow variation during
`machine operation.2 Other, more sophisticated, chiller controls allow some
`flow variation. Some chillers can tolerate f|ow—rate variations of as much as 30
`
`percent per minute or greater, while others can only tolerate up to 2 percent per
`minute. It is important that chiller capabilities are matched to system
`requirements. Contact the chiller manufacturer to determine allowable rate of
`flow variation before varying the flow through the evaporator in a chiller. Flow
`variation is discussed in detail in the section VariabIe—Primary—FIOw Systems,
`page 40.
`
`Water-cooled condenser
`
`To cool a building or process, the transferred heat must ultimately be rejected.
`The total amount of heat rejected includes the sum total of the evaporator load,
`the compressor work, and the motor inefficiency. In a hermetic chiller, where
`the motor and compressor are in the same housing, these loads are all rejected
`through the condenser. In an open chiller, where the motor is separate from the
`compressor and connected by a shaft, the motor heat is rejected directly to the
`surrounding air. The evaporator load and the compressor work are rejected
`through the condenser and the motor heat must be taken care of by the air-
`conditioning system.
`
`Effect of condenser-water temperature
`
`For a given chiller, as the leaving condenser-water temperature rises,
`refrigerant temperature and pressure also rise. Conversely, as leaving
`condenser-water temperature drops, so do refrigerant temperature and
`pressure. As the refrigerant pressure and temperature changes, the work a
`compressor must do also changes. The effect of |eaving—condenser—water
`temperature change on power consumption can be 1.0 percent to 2.2 percent
`per degree fahrenheit [1.8 percent to 4.0 per degree celsius]. Always consider
`the energy consumption of the entire system—notjust the chiller. It is
`important to remember that although raising the leaving condenser-water
`temperature penalizes the chiller, it may benefit the pumps and cooling tower
`through the use of reduced flow rates and higher thermal driving-forces on the
`tower. System interactions are covered in more detail in the section Condenser-
`System Variations, page 69.
`
`Effect of condenser-water flow rate
`
`Since the condenser is a heat exchanger, it is sensitive to water flow rate. For
`example, excessive flow may result in high water velocity, erosion, vibration, or
`noise, while insufficient flow reduces heat transfer efficiency and causes poor
`chiller performance. Therefore, condenser-water flow through the chiller should
`be kept within a specific range of limits, except during transient startup
`
`SYS-APM001-EN
`
`PAGE 11 of 98
`
`PETITIONER'S EXHIBIT 1222
`
`

`
`Chilled-lllilater-Plant Basics
`
`eonrlitions. Contact the manutaeturer tor these limits. Some ehillers may allow
`extended operation below the selected flow rates.
`
`It water velocity through the condenser tu hes is too low for significant periods
`of lime and the water is extremely hard, |ong—term fouling of lhe tubes may
`also occur. Webb and Li!’ tested a number of internall3r—enhanced oendenser
`tubes at low velocity [351 ftfs [‘l.lC|'.i' rri.ls]} and high water hardness. While they
`found that some of the internally-enhanced tut:-es fouled. in the long term they
`concluded:
`
`El-ecause of the high hardness and low water velocity used in ttiese
`tests. we do not believe that the fouling experienced is typical of that
`expected in eomrnereial installations. With use 01 good maintenance
`practices and water quality corilrol, all of the tubes tested are probably
`stiitaole for lor1g—terrTi-fouling applications.
`
`It is iiripuitaril to remernber that a chillei selected For low Flow {as discussed ir1
`the next section Cl:i'lIecI-Water-System Options] does not rtecessarilgr have low
`velocity through its tubes. It tube toulinq is a ITIBJDT eoneern, eonsieler the use of
`srnuoth. rather than inter riaI|y—erihar1ced. tubes in the contleriser for ease of
`cleaning.
`
`Air-cooled condenser
`
`Dtwiotisly. all-cooled chillers do not use cu-nderiser-water. since they FBJECI their
`heat by having ambiertt air passed across refrigerant-to-air heat exchangers Ir‘-
`paelcagerl air-eoolerl ehillers, the manufacturers attempt to provide optimal
`perforrttarice by slagi rig fans in resporise to chiller load and amtiient. t.1ry—t:u|l:r
`temperature.
`
`Loads
`
`In comfort-cooling applications. loads are usually satisfied by air handlers
`equi paper] with eoils to transter heat from eonrlitionerl spaee air to eireulating
`chilled-water. Air is thus cooled and Lletitirtiidified as it passes across the finned
`surface of the cooling coils. Since the psychrometric process of cenditieriing air
`takes plaee at the coils, selection of the optimum I.".DIl sire and type trorn the
`wide variety available is important for proper system perforrriarice.
`
`Ei‘r"':'r-.-5'.F'|"..I'||3I|I|l -EN
`
`PAGE 12 of 98
`
`PETITIONER'S EXHIBIT 1222
`
`

`
`Chilled-Water-Plant Basics
`
`Sr.-me sp-eeralizeel process leads do not Involve enoling air. Instead, they may
`irwulve heat trarisfer directly within a piece of process eq uiprne I'll. such as the
`coollrtgjacl-tet ofan in_jectiort-molding machine Heat transferred from the loads
`een be controlled In F; number of ways:
`
`I Three—way valve
`
`Two-way value
`
`Varial}Ie—speed pump
`Uncontrolled coils
`
`Three-way valve load control
`
`Pl three-way control valve regulates the amount of water passing through a coil
`in response reloads. The valve bypasses unused water around the cell and
`requires i:l cortstartt flow of water in the systerrt. regardless of load. A drawback
`of this |:r_\.-pass is that the temperature of the water lean-irtg the three—wa3,r value
`is reduced at part-lnael conditions. This can he a m:1_jnr cause of Sn-Called "low
`AT 5_\,rridrurrIe" dis-r:LIsset.1 on page 63 in the settler: Ctri'iIed-Water-Systerrt
`Issues. Three-way "l.|'£I|'u"E5 are used in nteny existing systems
`
`Figure 2 Value-controlled loads
`
`§' Three-Way Valve
`
`9 r"""'w“3" 1"'“'"°
`
`Two-way value load control
`
`A two-way, water In odulaling valve at the coil p-erforrns the same water
`throttling function as the three-way valve. The coil sees no difference between
`these two meth eds. The ehi llerl—watr:r system. however. sees a great difference.
`In the ease of the two-way value. all flow in the coil i'.2Ilt.'L.llt Is thruttled. No water
`is bypassed Cortseciuentlg-,r. a system using two-way valves is a variable-flow
`ehillerl-water system. The temperature nt the water leaving the cell is net
`diluted by bypass water so at parl-Iuatzl l'_2U-fIL1l1.lU-l'1‘_i. the syslern returrrwater
`[El"I'lp€l'EI[L.li'E i5 hlgt'IE'.I' [t'IEii"l With [t'Ii'€€-WW3)‘
`VBIVE CDl"'lIi'O|.
`
`S'fS..'.'.P|'v'lflU1-EN
`
`PAGE 13 of 98
`
`PETITIONER'S EXHIBIT 1222
`
`

`
`Chilled-llllater-Plant Basics
`
`Variable-speed pumping load control
`
`By using a pump for each coil. the flow may be controlled by varying the pump
`speed. In such systems, there may be no central values at the cell. This can
`reduce both the value and the valve lfl‘_i[i:lHi:ll.IL.‘Irl costs.
`
`Uncontrolled coils
`
`Figure 3 stiuws ::i Liurttrul '|i'i:lFI-E:I1.lUrl using an uricorttiulled or "wild "i;ui|. In this
`53.-stern. control of the conditioned air supply is executed by face-artd-bypass
`dampers that permit a portion nt the air to bypass the cell surface. Advantages
`L31" the strategy are the eliriiiriatiori of curitrul values and llTI[.‘rl|'..'I‘.I'EI:.l part-load
`dehumidification. P. disadvantage is that all the water is puinpecl all the time:
`however, in systems with uergi small water pressure drops, this system
`at rarigerrieril rriay work ecoriornically.
`
`Fig: re 3 Uncontrolled coil
`
`Hype ss Damper
`
`Air I lancllcr
`
`Ctmlrzd Air l|.I'li itture
`
`Face Damper
`
`Chilled-water distribution system
`
`Chilled water is circulated through fixed piping—rncst commonly steel. copper,
`pr p|astic—that connects the chiller with uarir.-us load terrninals. Piping is sited
`to meet a project's pressure less. water velocity. and coristructiuri cost
`parameters Pressure drop is overcome by the use of a chilled-water pump.
`
`S‘r".~'r-.-5.F'|"'..I'||II|I|1-El\.|
`
`PAGE 14 of 98
`
`PETITIONER'S EXHIBIT 1222
`
`

`
` TRAN?
`
`Chilled-Water-Plant Basics
`
`Chilled-water pump
`
`The purpose of the chilled-water pump is to circulate chilled water within the
`loop. Generally, the pump must overcome the frictional pressure losses caused
`by the piping, coils, and chiller and the pressure differential across open control
`valves in the system. The pump, while working at the system static pressure,
`does not need to overcome this static pressure. For example, in a forty—story
`building the pump need not overcome the static pressure due to those forty
`stories.
`
`The pump is typically located upstream of the chiller, however it may be
`anywhere in the system, provided that the pump:
`
`I meets the minimum pump net positive suction—head requirements. That is,
`the system pressure at the pump inlet must be both positive and high
`enough to allow the pump to operate properly;
`
`maintains the minimum dynamic pressure head at critical system
`components (usually the chiller). If the dynamic pressure head is not high
`enough at these components, proper flow will not be established through
`them;
`
`accommodates the total pressure (static head plus dynamic head) on
`system components such as the chi||er's evaporator, valves, etc.
`
`Note that the pump heat is added to the water and must be absorbed by the
`chiller. Generally, this represents a very small temperature increase.
`
`Multiple pumps are often used for redundancy. Depending on the terminal
`control devices and system configurations, the chilled-water pumps may be
`either constant or variable-flow.
`
`SYS-APM001-EN
`
`PAGE 15 of 98
`
`PETITIONER'S EXHIBIT 1222
`
`

`
`Chilled-Water-Plant Basics
`
`Distribution piping
`
`By itself. the distribution system is easy to understand. Figure Ji shows a
`simplified distribiitinn system consisting not multiple er.-nlinri coils, rraeh
`coritmlled by e Lrierrnostet trial regulates the flow in its respective coil. The
`valves may be either three-way or two-way. es pre-i-iously discussed. three-way
`valves rndiiirn constant watnr tlr.-w, whlln two-way values allow the water flow
`in the systerrl to vary. As. flow var ies, the [_'lL|rl1[J rrlay sirriply FIIJI-_'.' its curve U-I use
`a method orflow control such as a variable-speed drive See the section System
`Cnn.figiJ'rarinit5, on page 2?. tor a detailed diseiissinn of distrihiitinn-system
`LJ[JLILJrIS.
`
`Figire ll Simplified distribution system
`
`Expansion
`
`Di Htri huti nun
`
`Piping
`
`25.35 ASHRAE “Ix.-_4C 5J_,_,:mm_,; and
`fqu.-';_}_r;.;-;_~,u;-;.Ii;.-,1.;.';_i.-_wi¢_ cmpmr 12_
`I |_i"Jr0nI': | lf-‘atirig and Cslollng S}'='=lDrT1
`|1'n-aigrii c:nn|e'IInH 'eI:liiItmrIr'I| ri:lc‘.rnrI='.t‘.
`lFlhZJFl'i1.5Ill[iFll2l[1H'l[!l2i2lI'l'l[H2li1|Z!I'II£!-i|ZJi.=I
`r:hi||i:i1w;|ti:r tli-stritiiititzuri 5-:3,”-.lt:rri.
`
`The distribution system may contain other components, such as an expansion
`
`tank, control valves, [1-alanci rig valves. check valves, and an air separator. to
`name at
`|'e'.'u'_ The Llerisily. arid llieielure Lhe '-."IJ|L||'l1B. ul Lhe water in .3 "c|useLl"
`chilled-water ciistribiitiort system varies as it undergoes changes in
`tnmpnratiirn. The oi-:pai‘i'.-'.inn tank allows fnr this nxpaitsmn and |.':l‘H‘ITf£'1CTll‘.l|‘I nt
`.,u._.j._E[ uulunle
`
`S‘r":i-.¢iF'|"'.I'||IIE|1-EN
`
`PAGE 16 of 98
`
`PETITIONER'S EXHIBIT 1222
`
`

`
` TRAN?
`
`Chilled-Water-Plant Basics
`
`Condenser-water system
`
`As in chi||ed—water distribution systems, condenser—water system piping—most
`commonly steel, copper, or p|astic—is sized to meet a project's operating
`pressure, pressure loss, water velocity, and construction cost parameters.
`Pressure drop through piping and the chi||er's condenser, plus the cooling-
`tower static lift, is overcome by use of a condenser-water pump.
`
`Cooling tower
`
`To reject heat, water is passed through a cooling tower where a portion of it
`evaporates, thus cooling the remaining water. A particular cooling tower's
`effectiveness at transferring heat depends on water flow rate, water
`temperature, and ambient wet bulb. The temperature difference between the
`water entering and leaving the cooling tower is the range. The temperature
`difference between the leaving water temperature and the entering wet-bulb
`temperature is the approach.
`
`Effect of load
`
`As the building |oad—or heat rejection—decreases, range and approach also
`decrease. This means that when the building is at part load, the cooling tower
`can provide colder water at the same ambient wet—bu|b temperature.
`
`Effect of ambient conditions
`
`As ambient wet—bu|b temperature drops, the approach—at a constant load—
`increases. This must be considered when cooling-tower-control strategies are
`developed. Detailed descriptions of these conditions appear in the subsection,
`Chiller-tower energy balance, page 72. For additional information, refer to 2000
`
`ASHRAE1HVAC Systems and Equipment Handbook, Chapter 36, “Cooling
`Towers."
`
`SYS-APM001-EN
`
`PAGE 17 of 98
`
`PETITIONER'S EXHIBIT 1222
`
`

`
` TRANEE
`
`Chilled-Water-Plant Basics
`
`Controls
`
`The chi||ed—water supply temperature is usually controlled at the chiller. Most
`commonly, supply water temperature is used as the sensed variable to permit
`control of chiller capacity to meet system load demand. Supply-temperature
`control strategies may be used on either constant- or variable-flow systems. As
`previously discussed, flow control is executed at the load terminals using three-
`way or two—way valves, or separate pumps for each coil.
`
`Control capabilities run the gamut from slow-acting pneumatic controls, to
`electromechanical controls, to sophisticated digital controls that use algorithms
`tuned to give superior performance.
`
`Chiller control
`
`Today's chiller controls are capable of doing more than simply turning the
`chiller on and off. At a minimum, these controls should monitor:
`
`I Safety points such as bearing temperatures and electrical points that, when
`out of range, may cause motor failure.
`
`Data points that may cause operational problems if corrective action is not
`taken. An example is low chi||ed—water or refrigerant temperature, which
`may result in freezing in or around the evaporator tubes.
`
`General points that should be logged daily to ensure proper chiller
`performance.
`
`Table 1 lists the ASHRAE-recommended monitoring points.
`
`Table 1 Recommended chiller-monitoring points per ASHRAE Guideline 3-1996
`Flow
`Flow
`
`chmed
`Water
`
`Inlet Pressure
`Inlet Temperature
`Outlet Pressure
`
`condenser
`Water
`
`Inlet Pressure
`Inlet Temperature
`Outlet Pressure
`
`Outlet Temperature
`Approach Temperature
`EvaporatorT Condenser
`Refrigerant Pressure
`Refrigerant Temperature
`Level
`
`Outlet Temperature
`Approach Temperature
`_
`Refrigerant Pressure
`Refrigerant Temperature
`Level
`
`Pressure
`Temperature
`Additional Required
`
`Refrigerant Compressor Discharge Temperature
`Additional Required
`Vibration Levels
`
`SYS-APM001-EN
`
`PAGE 18 of 98
`
`PETITIONER'S EXHIBIT 1222
`
`

`
` TRAN?
`
`Chilled-Water-Plant Basics
`
`In addition to monitoring data, it is vital that the chiller controls alert operators
`to possible problems. Diagnostic messages are necessary for the operator to
`respond to safety issues and data points that are outside normal operating
`ranges.
`
`While communicating these diagnostic messages is a requirement, some chiller
`controls include factory-installed programming that responds to the diagnostic
`messages. For example, when the chi||ed—water temperature nears freezing, the
`chiller sends a diagnostic message and adapts its operation by reducing the
`compressor capacity, raising the chilled-water temperature to a safer condition.
`
`Finally, the chiller controls should communicate with a system-level controller.
`There are many system aspects that are outside the chi||er's direct control, such
`as condenser—water temperature and the amount of fluid flowing through the
`evaporator and condenser. To minimize the system energy costs, the system
`controls must coordinate chiller, pump, cooling-tower, and terminal-unit
`controls. This can only be done if adequate information is communicated from
`each system component to the system-level controls.
`
`Pump control
`
`In so-called constant flow systems, the pumps are either on or off, providing
`relatively constant flow when in the on position. In practice, some flow
`variation will occur as system pressure drop changes. In a variab|e—f|ow system,
`pump control is most often performed by maintaining a pressure differential at
`a selected point in the system. For example, a variable-speed drive will increase
`its speed if the sensed pressure differential is too low, or slow down if the
`pressure differential is too high. The control point is selected to minimize over-
`pressuring the system and to assure adequate flow at all critical loads. Optimal
`pumping control strategies are addressed in Critical valve reset, page 48.
`
`Chapter references
`
`1
`
`2000 ASHRAE HVAC Systems and Equipment Handbook, Chapter 12,
`Hydronic Heating and Cooling System Design and Chapter 36, Cooling
`Towers, American Society of Heating, Refrigeration and Air-Conditioning
`Engineers.
`
`Schwedler, M., PE and Bradley, B.; “An Idea for Chi||ed—Water Plants Whose
`Time Has Come...Variab|e-Primary-Flow Systems,” Engineers Newsletter,
`Volume 28, No. 3, The Trane Company, 1999.
`
`Webb, R.L. and Li, W.; “Fou|ing in Enhanced Tubes Using Cooling Tower
`Water, Part I: Long-Term Fouling Data," International Journal of Heat and
`Mass Transfer, 2000.
`
`SYS-APM001-EN
`
`PAGE 19 of 98
`
`PETITIONER'S EXHIBIT 1222
`
`

`
` TRIKE
`
`Chilled-Water-System Options
`
`There arr: many chilled-walnr-system design option s; however. In a ha sic snnsn.
`eacli option is a furi:.'Lir.:r1 of flow. Lerrrp-erature. systerri Liurtfiguratiurr. and
`control. This section discusses the effect of flow rate and temperature
`decisions.
`
`It is important to remember that temperatures and flow rates are variables By
`_jur:li:Inus snlr.-min-n pl tl'rr.=sr.- unrrahlns. chillr.-r:l-watt.-r plants can be designed tr.-
`lJDLl'1 satisfy r:hil|et.l-water req Liirerneriis and operate cost effectively.
`
`Chilled-water systnnts arr: nttrtn t'l£'.‘filtj|‘If.‘l'l using tlriiar rates and trrrnprtraturns
`applied

This document is available on Docket Alarm but you must sign up to view it.


Or .

Accessing this document will incur an additional charge of $.

After purchase, you can access this document again without charge.

Accept $ Charge
throbber

Still Working On It

This document is taking longer than usual to download. This can happen if we need to contact the court directly to obtain the document and their servers are running slowly.

Give it another minute or two to complete, and then try the refresh button.

throbber

A few More Minutes ... Still Working

It can take up to 5 minutes for us to download a document if the court servers are running slowly.

Thank you for your continued patience.

This document could not be displayed.

We could not find this document within its docket. Please go back to the docket page and check the link. If that does not work, go back to the docket and refresh it to pull the newest information.

Your account does not support viewing this document.

You need a Paid Account to view this document. Click here to change your account type.

Your account does not support viewing this document.

Set your membership status to view this document.

With a Docket Alarm membership, you'll get a whole lot more, including:

  • Up-to-date information for this case.
  • Email alerts whenever there is an update.
  • Full text search for other cases.
  • Get email alerts whenever a new case matches your search.

Become a Member

One Moment Please

The filing “” is large (MB) and is being downloaded.

Please refresh this page in a few minutes to see if the filing has been downloaded. The filing will also be emailed to you when the download completes.

Your document is on its way!

If you do not receive the document in five minutes, contact support at support@docketalarm.com.

Sealed Document

We are unable to display this document, it may be under a court ordered seal.

If you have proper credentials to access the file, you may proceed directly to the court's system using your government issued username and password.


Access Government Site

We are redirecting you
to a mobile optimized page.





Document Unreadable or Corrupt

Refresh this Document
Go to the Docket

We are unable to display this document.

Refresh this Document
Go to the Docket