throbber
introduction
`
`[5000 anda
`feasibilityashuijh
`developed wit11h ‘
`St ten times lar
`Irequiremms 0;
`28d In Fig 24 A
`'presently bein
`ue courSe
`
`recently [12“
`of heatextractedl
`ansion in the
`nation ofniixin
`dried the coolirI
`earn plant. Such
`quires additional
`near the leading
`re insufficientIII
`ce steam cooling
`=se critical areas.
`-shuttle solution
`Jerfot‘l'l'llng heat
`stigation or this
`sor is one being
`
`urbo Ill [13”,]
`CCPs. A noyel
`combustion of
`has a very high
`terated by also
`periods of low
`es is achieved.
`elopment of an
`mber as a first
`
`riahren," Austrian
`'onference, Vienna,
`Power Conl'erencc.
`
`es." Panel Discus
`lice, Vienna £010.
`
`“tilt: GasT‘nggm
`M: C‘;:‘l‘:’mam'l..
`erma! energy pro-
`
`u“ STlG LMSOOO
`ENGWEEWGM
`nine.” presented 3*
`ion by Novel High
`I, Montreux. l9“-
`a High Efficient!
`.5 am
`Ised Circutt
`It
`ant," presented a!
`ants From Stored
`In ference. Vienna.
`
`|
`
`I. S. Undryas
`Project Manager.
`
`D. A. Wilson
`Project Engineer.
`
`M. Kawamoto
`Engineer.
`
`Fluor Daniel Power,
`twine, CA 92730
`
`G. L. Hauh
`Proiect Engineer.
`Kern River Cogeneration Company,
`Bakerstield. CA 93380
`
`Options in Gas Turbine Power
`Augmentation Using Inlet Air
`Chilling
`Gas turbine power augmentation in a cogeneration plant using inlet air chilling is
`investigated. Options include absorption chillers, mechanical (electric driven) chill-
`ers, thermal energy storage. Motive energy for the chillers is steam from the gas
`lurbineexhaust or electrical energyfor mechanical chillers. Chilled water distribution
`in the inlet air system is described. The overall economics of firepower augmentation
`benefits is investigated.
`
`—
`Recent rapid growth in summer electricity demand experi‘
`enced by most of the US. utilities results in the need to build
`power plants that generate maximum output at summer am-
`bient temperature ratings. Due to their short installation time
`and low installation cost, gas turbines are often used to meet
`this peak demand, One disadvantage, however, penalizes the
`gas turbine peaking plant rating, namely the inversely pro-
`portional effect of the ambient temperature on the gas turbine
`output, which is depicted in Fig. 1. The gas turbines typically
`produce 30 percent higher output at 20°F than at 95°F. Thus
`the cost of installing a gas turbine or combined cycle plant
`rated at 95"F is 20—30 percent higher than that rated at 20°F.
`This inherent disadvantage of reduced gas turbine output at
`high ambient temperatures can be mitigated by the reduction
`of the GT compressor inlet air temperature, which w0uld result
`in increase of GT output at a given ambient temperature.
`The traditional way to decrease the compressor inlet air
`[Emperature is the Incorporation of an Inlet arr evaporattve
`cooler. whtch can reduce the inlet air dry bulb ambtent tem-
`Perature by up to 90 percent of the dry bulb—wet bulb tem-
`Dcrature difference. To achieve additional inlet air temperature
`reduction, alternative methods of inlet air cooling must be
`“594, referred here as inlet air chilling.
`.
`.
`ObjecIlVeS
`' Develop a GT power augmentation concept based on
`reducing the GT inlet air temperature below the ambient air
`dew point.
`‘ The power augmentation may be available anytime when
`—__
`Contributed by the International Gas Turbine Institute and presented a! the
`35th International Gas Turbine and Aeroengine Congress and Exposition, Brus
`“15. Belgium, June 11-14, 1990. Manuscript received by the International Gas
`Turbine institute January 16,1990 Paper No. 90-GT250.
`
`the chilled air temperature is below the ambient temperature,
`but especially during summer on-peak hours.
`I GT exhaust heat should be used to generate cooling of
`the cooling media (chilled water), via absorption chilling; how-
`ever, other means (electrically driven chillers) may be used for
`peaking.
`
`'
`
`Application of Inlet Air Chilling
`The GT inlet air chilling, i.e., air cooling below the ambient
`wet bulb temperature, can increase the GT capacity needed
`during peak hours and improve the GT heat rate. Selection of
`the temperature of the chilled air is important. The temperature
`at the compressor inlet must be above 32'F to prevent ice
`buildup on the compressor blades, since the chilled inlet air
`shall be at 100 percent relative humidity due to moisture con-
`densation during the air chilling process. Due to a major in-
`crease in air velocity in the compressor inlet the static
`
`120.
`
`110.
`9
`E d
`W —7"UI:
`E .8
`
`DESIGN HEAT RATE
`
`DESIGN AIRFLOW
`
`nesnn DUTPU'I
`
`da
`
`E 0.
`
`20.
`
`120.
`100.
`80.
`60.
`40.
`COMPRESSOR INLET TEMPERATURE DEG. F
`FRAME 7E GT OUTPUT VERSUS COMPRESSOR INLET TEMPERATURE
`Fig. 1
`
`140.
`
`’f the ASME
`
`J°umal ot Engineering tor Gas Turbines and Power
`
`APRIL 1991, Vol. 113 l 203
`
`Page 1 of 9
`
`GE Exhibit 1008
`
`

`

`
`
`55....--
`:.-
`'.r;i
`
`new:
`r...‘._—,u.av;.5—
`
` mA-'
`=2=a=g......_..L.A,_.
`
`
`
` m—_-w-
`
`111111
`‘ ‘. _.1iiiiii'
`
`Fig. 2 GT Inlet alr cooling process
`
`mcan-tun
`WW" EVWIAM
`, 000m.1ore-mm
`
`3"...m'"°'um nuul- m m,
`Im IAN]
`N
`8
`
`
`
`
`3
`
`or menu"
`mmflll'wumv:
`MOLEIIIDDEIAMN
`
`
`
`
`
`a
`
`“WREINI
`GT.GENERATORCADILITV.NW 3
`
`
`b
`
`In
`
`20
`
`M
`
`‘0
`
`W
`In
`9
`ancient veurenavune. “F
`noun: a
`
`Ill
`
`IO
`
`loll
`
`Ila
`
`In
`
`temperature of air may drop as much as lO‘F. To safeguard
`against this drop the chilled air temperature should be a min—
`imum of 45°F, which includes a 3'F margin.
`Figure 1 shows that the output can be increased by 0.36
`percent with each 1°F inlet air temperature reduction. If the
`chilled air temperature is selected at 52‘F, then the temperature
`drop from 95°F is 43°F or 15.5 percent power boost. If the
`GT unit is or could be equipped with an evaporative cooler,
`which could reduce the ambient (95°F, 20 percent RH.) to
`72"F (85 percent RH.) the benefit of air chilling is only (72 — 52)
`or 20'F or 7.2 percent power boost. The cost of the inlet air
`chilling equipment must be amortized by the economic benefits
`from additional power sales during peak or during operation
`when ambient temperature is above the chilled air temperature.
`
`Inlet Air Heat Exchange
`The ambient conditions (temperature and relative humidity)
`are important factors. The typical summer average on-peak
`ambient temperature in the US. is 95°F dry bulb. In eastern
`and midwest locations the relative humidity (R.H.) may be at
`90 percent level (wet bulb temperature is ~ 90°F) and the air
`enthalpy is ~59 Btu/lb dry air. In the western United States
`(dry climate), the same 95°F dry bulb temperature shall be
`associated with 20 percent R.H. (66°F wet bulb) and enthalpy
`of 34.7 Btu/lb dry air. If the compressor inlet temperature is
`to be lowered to 52°F dry bulb, 95 percent R.H., the enthalpy
`is 20.9 Btu/lb dry air. The required heat removal at high
`humidity location shall be (59u20.9) = 38.] Btu/lb and in
`the dry climate it will be (34.7—20.9) = 13.8 Btu/lb. Thus,
`the duty of the inlet cooling system in humid climates is much
`higher than in the dry climates. In either case, moisture sep-
`aration apparatus should prevent carryover. The cooling pro-
`cess is shown in Fig. 2.
`The temperature at the compressor inlet must be above 32°F
`to prevent ice buildup on the compressor blades, since the
`chilled inlet air shall be at 100 percent relative humidity due
`to moisture condensation during the air chilling process. Due
`to a major increase in air velocity in the compressor inlet. the
`static temperature of air may drop as much as 10°F, which
`includes temperature drop in the compressor bellmouth (At =
`4° F) and in the (open) inlet guide vanes (variable or stationary)
`(AT = ~4°F). Closed variable inlet guide vanes would result
`in additional pressure drop (~5°F) but this would not apply
`while inlet air chilling is used. To safeguard against this drop
`the chilled air temperature should be a minimum of 45‘F.
`Increased wetness in the compressor inlet may induce corro-
`sion, which may require more frequent inspections of com-
`pressor inlet.
`
`Fig. 3 Generator capability
`
`GT Inlet Air Cooling Concepts
`Several concepts may be offered. The GT operates either in
`the simple cycle or in the cogeneration or combined cycle.
`Simple cycle GT shall be able to use all exhaust heat for chilled
`water generation. For a GT in cogeneration or in combined
`cycle service, we may need to evaluate the tradeoff of using
`the exhaust heat for power augmentation in the GT inlet versus
`the economic benefits of exhaust heat sales.
`
`.
`Generator Capability
`The generator rating has to be verified. [f the generator is
`cooled by cooling water it can be provided from two sources:
`cooling tower/river, and dry coolers (fin fan type).
`Since the generator capability is indirectly proportional to
`the cooling water temperature, it is possible in the case of dry
`cooling that the GT output may be increased via inlet air
`chilling while the generator capability would not increase. This
`could result in GT exceeding the generator capability with
`potential overtemperature on the generator winding. The gen-
`erator rating must be carefully checked. The same applies for
`air-cooled generators. Examples of the GT and generator ca-
`pability are shown in Fig. 3.
`
`Systems Options
`The complete inlet air cooling system consists of several
`systems, such as:
`' Water chilling system
`0 Absorption chiller thermal source
`0 Chilled water system
`0 Cooling system
`The following options exist for each system;
`Chilling System
`C Absorption chiller utilizing:
`(a) Lithium bromide absorbent.
`(b) Ammonia absorbent.
`0 Mechanical chilling utilizing compression with freon re-
`frigerant.
`Steam jet refrigeration.
`' Hybrid chilling system utilizing both absorption and me-
`chanical chilling systems.
`0 TBS (Thermal Energy Storage)
`
`204 I Vol. 113l APFllL 1991
`
`Transactions of the ASME
`
`Journal
`
`Absorpl
`provide or:
`on using:
`0
`LOW
`in a
`o Tie-i
`plict
`exch
`- Gen
`amn
`0 Dire
`absc
`cyclt
`Chilled
`ing schem
`turbine in
`-
`Inst:
`cool
`botl'
`Inst:
`prin
`Inst:
`prin
`
`0
`
`-
`
`DONG“
`SOLUTII
`
` nILUTE
`
`SOLUTION
`
`Flg. 4
`
`“MI
`«mg m
`
`mom.“ i;
`"I I: bur-M
`
`Page 2 of 9
`
`GE Exhibit 1008
`
`

`

`Absorption Chiller Thermal Source. A thermal source to
`provide operating force to absorption chillers was studied based
`on using:
`
`Low-pressure steam generated in a new HRSG installed
`in a simple cycle GT exhaust.
`Tie-in to existing steam export line in cogeneration ap-
`plications to generate steam through a low-pressure heat
`exchanger (i.e., reboiler).
`Generation of hot water from the above methods for the
`ammonia absorption chiller.
`Direct integration of HRSG preheat coil with ammonia
`absorption chillcr to provide desorption heat in simple
`cycle GTs.
`
`Chilled Water Distribution System. Review of the foIIOW-
`ing schemes to provide chilled water to/from the chilled gas
`turbine inlet air:
`
`.
`
`Installation of PVC media similar to the evaporative
`cooler media downstream of the inlet air filter, using
`both the evaporative and direct contact principle.
`Installation of chilled water coils using the convection
`principle (indirect cooling).
`Installation of freon-cooled coils using the convection
`principle.
`
`
`
`ABSORBER
`
`
`
`40F
`AIR CONDITIONING
`LOAD
`55F
`
`REFRIGERAN‘I’
`
`
`SOLUTION PUMP5
`REFRIGERANT PUMP
`Flg. 4 Absorption chiller schematics (courtesy of Trans Corp.)
`
`0
`
`Indirect evaporative cooling for distribution of chilled
`water within the inlet air filter.
`
`Cooling System. Study of the following cooling water sys-
`tems:
`
`0 Mechanical draft cooling tower.
`- Closed-loop water to air cooled system (tin fan).
`
`Description of Considered System
`The system evaluation is based on retrofitting four General
`Electric Frame 7E GTGs with inlet air chilling system.
`Existing System: 4x Frame 7E GTGs
`
`65.000 kW
`12.200 Btu/kWh-LHV
`70 GPM
`Natural gas
`14.31 psia
`95°F
`70.8“F
`30 percent
`34.7 Btu/lb d.a.
`700 ft.
`2,074,982 Ib/h each
`
`5 in. WC
`
`0 Power output
`0 Heat rate
`' NO; control—water injection
`O Fuel
`0 Barometric air pressure
`0 Ambient dry bulb temperature
`0 Ambient wet bulb temperature
`. Relative humidity
`'
`Inlet air enthalpy
`'
`Site elevation (ASL)
`I
`'
`Inlet air flow rate
`Inlet system pressure drop (filter.
`evaporative cooler, silencer)
`' Openings available:
`Inlet duct, I opening (Wx H) 25’ x 25'
`Filter house, 6 openings 25 ’ X 5'
`80 percent
`0 Evaporative cooler efficiency
`72°F
`Temperature after evaporative cooler
`80 percent
`Humidity
`Heat Recovery: 80 percent steam quality HRSG for EOR
`Inlet temperature
`970°F
`Stack temperature
`260°F
`Feedwater temperature
`150°F
`Steam output @ 800 psig, 80 percent quality
`418,000 1b/h each
`10 in. WC
`
`Gas side pressure dr0p
`Retrofit With Inlet Air Chilling:
`' Retrofitted inlet air temperature (dry bulb)
`Retrofitted inlet air humidity
`Inlet air enthalpy
`Air chilling duty
`or
`
`52°F
`95 percent
`21 Btu/lb d.a.
`28 mm Btu/H each
`2333 tons each
`
`emurn vuu salts
`
`AIR
`
`mLEr
`
`I'ILIER
`
`vnl'll
`Ia um:
`I ___—_l
`
`mun wire a»
`
`
`
`
`as Hr. urn-a
`
`we use:
`
`LlInn-nuns
`
`
`Alifllllm mur-
`
`
`-
`T
`
`murmur mswn
`m
`
`
`
`r
`
`
`
`-.-
`
`van.
`
`1
`
`“i
`
`_—.-— —u-\I «ID
`.1run-s In.
`
`an...
`
`
`
`:rates either in
`.
`.mbined cycle.
`1eat for chilled -.
`.r in combined
`.deoff of using
`GT inlet versus
`
`the generator is
`om two sources:
`
`rigportional to
`n the case of dry
`sed via inlet at!
`not increase. Thisl
`r capability With-
`vinding. The gen-i
`: same applies for
`and generator ca-I
`
`:onsists of several.
`
`(
`:ssion wrth freon w
`
`1 absorption and ff.
`
`In: Min I———
`'- lsm ill-01
`
`___
`
`“ill-om new-
`"‘ K KIEIHIKIIH
`
`[Ml
`
`-.._......
`nmncw
`
`E 2 _
`commit M
`
`Fig. 5 Absorption chllllng diagram
`
`-tlons 0' the Asulhumal 0! Engineering lor Gas Turbines and Power
`
`APRIL 1991, Vol. 113 I 205
`
`Page 3 of 9
`
`GE Exhibit 1008
`
`

`

`nun Mm um:
`
`nouns:- In"a ll
`
`mm non um
`
`
`
`—-. «“an
`- urinal“! rm-
`
`— twin ISIWI‘II
`CI we: IEIIMEfllnY
`
`E nm
`
`Fig. 6 Mechanlcal chlller schematics (courtesy Carrier Air Condltlonlng
`Co.)
`
`and York. Cost may be estimated at $250 per ton of refrig-
`eration.
`
`Two Stage (LiBr).
`The two-stage lithium bromide absorp—
`tion chiller system will operate with saturated steam pressures
`of approximately 114 to 128 psig allowing the unit to consume
`less steam than a single-stage chiller at l5 psig. The two-stage
`steam consumption is estimated at 9.9 lb per ton versus 19 lb
`per ton for the single stage; thus. less steam will be consumed
`during chiller operation, resulting in a net savings of thermal
`energy over the single-stage chillers.
`The cost estimate for the two-stage chillers is $330 per ton,
`which is approximately 30 percent more than the single stage I
`and twice the cost of a centrifugal chiller. The chiller size is
`limited to 1500 tons for the larger chillers. Manufacturers of
`the two-stage absorption chillers are Hitachi Paraflow, Sanyo-
`Bohn, and The Trane Company.
`‘
`
`Water Chilling via Absorption Chillers (Fig. 5)
`Absorption Chilling System. Absorption chilling systems
`operate with a low-grade thermal source to provide chilled
`water at 44°F. The system contains refrigerant and absorbent
`that cycles at low internal pressures. This pressure in the evap-
`orator section will allow evaporation of the refrigerant liquid
`at a low temperature providing the chilling effect for the in-
`coming chilled water. At slightly higher pressures, the refrig-
`erant vapor and absorbent liquid are combined in the absorber
`section by their strong affinity for combining. As the vapor
`is condensed, heat is released into the condenser water coils
`(cooling water). The resulting solution will be a “strong" ab-
`sorbing solution of refrigerant and absorbent. This solution
`is pumped into the absorbing section where the refrigerant is
`evaporated from the absorbent by a thermal source, either
`low-pressure steam or hot exhaust gases. In the condenser, the
`refrigerant vapor is condensed to liquid by cooling water, and
`the refrigerant liquid is pumped back into the evaporator. The
`“weak” absorbing solution is recirculated into the absorbing
`section. An example is shown in Fig. 4.
`Ammonia and lithium bromide (LiBr) are two types of ab-
`sorption chiller that are available for this chilling service.
`Lithium Bromide Absorption Chilling Systems. The lith-
`ium bromide absorption chilling system can be designed as a
`single or two-stage chiller. These chillers utilize a design with
`a lithium bromide water absorption refrigeration cycle. The
`chilling systems typically provide chilled water at 44°F with
`return water at 54‘F. Consideration was made to lower the
`chilled water temperature to 42°F; however, this would have
`reduced the chiller’s cooling capacity and efficiency. Chilled
`water temperatures less than 42°F are not considered practical
`for absorption units. This is due to the water-based refrigerant
`used in the chiller, which, when operating between 34°F and
`36°F, provides 42°F chilled water and may potentally freeze
`the chilling unit.
`Typical flow calculations for each of the absorption chiller
`units are based on the following:
`0 Leaving chilled water temperature = entering temper-
`ature — temperature drop
`0 Leaving condenser water temperature = entering tem-
`perature + temperature rise
`
`Cooling load (tons) x 24
`temperature drop
`0 Chilled water flow (gpm) =
`- Steam Flow (lb/hr)
`Cooling load (tons)x9.9 (two
`stage)
`Cooling load (tons)>< 19 (single
`stage)
`
`Ammonia Absorption Chilling System. The ammonia ab-
`sorption system is an engineered refrigeration system specif-
`cally designed for the tons of cooling required. The ammonia
`system can produce lower chilled water temperature than Iith—
`ium bromide systems, from +50°F through —50°F chilled
`medium temperatures. Low-pressure steam (175 to 265 psig)
`or turbine exhaust gases can be used as the thermal source for
`the ammonia absorption cycle. However, the ammonia system
`requires higher capital costs, approximately 3650/ton of cool-
`ing. Also, larger plot space is required, approximately 30 ‘ X 30'
`for a 1,000 ton chiller installation. The ammonia system field
`installation requires significant structural steel to support the
`various ammonia storage tanks, heat exchangers, and other
`Cooling load (tons)><44 vessels. Manufacturers of the Ammonia Absorption Chillers
`are: Lewis Refrigeration Co., Houston, Texas, and Borsig
`temperature drop
`GmbH.
`
`- Condenser water flow (gpm) =
`
`Single Stage (LiBr). The chiller design utilizes a single shell
`hermetic construction that will enhance the integrity of the
`unit. These chillers operate on low-pressure saturated steam
`at 15 psig, consuming approximately 19 [b/hr per ton of chill-
`ing. Hot water at 270T can also be used as the thermal energy
`source. The single-shell design helps prevent air leakage, which
`can cut the capacity and promote corrosion. A pro-packaged
`system can be delivered completely assembled with available
`size range from 101 to 1,660 tons. The single-stage system will
`operate at a vacuum and may be susceptible to air leakage,
`which could cause some damage. However, if the proper op—
`erating and maintenance procedures are followed, i.e. , periodic
`purging of the system and operation above 42°F, there should
`be no problems during normal operation. A total loss of power
`would cause the solution of the absorption chiller to solidify
`into a solid mass within one hour. Manufacturers that currently
`produce the single-stage absorption chillers are Trane, Carrier.
`
`Water Chilling Via Mechanical Chillers (Fig. 7)
`The Mechanical Chiller is a vapor compression cycle with a
`compressor, liquid cooler (evaporator), condenser, and com-
`pressor drive. Water at 54°F returning from the inlet cooling
`coils enters the chiller (evaporator) where it is cooled to 44°F
`by the refrigerant liquid evaporating at a lower temperature-
`The refrigerant gas produced is compressed to a higher pressure
`and temperature so that it may be condensed by the cooling
`water in the condenser. The condensed refrigerant is returned
`to the evaporator through an expansion/metering valve.
`Mechanical chillers may be provided with different types of
`compressors: reciprocating, screw, or centrifugal. Recipro-
`cating and screw type compressors are generally used for sizes
`less than 1000 tons. Centrifugal liquid chillers are used for
`sizes greater than 1000 tons, with factory-assembled units 1113
`
`to 1600 tons
`tons.
`Chillers fr
`shelf units th
`to 3000 tons
`chillers. The
`compressor :
`unit. Three
`Manufacture
`of providing
`chiller will c
`system.
`Typical fl
`are based or
`
`0 Leavin
`ature
`' Leavir
`peratu
`
`' Chiller
`
`' Conde
`
`The temp
`This value <
`chiller unit.
`ing water fr
`of the chilIt
`The selec
`on the cost
`Based on n
`Chillers wer
`
`1000—1
`1500—5
`Over 5
`
`The smal
`Chase based
`and require
`Chillers. Th
`required a
`Chiller wou
`
`206 I Vol. 113, APRIL 1991
`
`Transactions of the ASME
`
`Journal 0
`
`Page 4 of 9
`
`GE Exhibit 1008
`
`

`

`It Condltionlng
`
`on of refrig.
`
`nide absorp.
`am pressures
`t to consume
`'he two-stage
`
`be consumed
`
`Flg. 7 Mechanical chllltng dlagram
`
`mine rn-r-
`
`to 1600 tons, and field-assembled machines to about 10,000
`tons.
`Chillers from 100 tons to 1500 tons are packaged off-the‘
`shelf units that are hermetically sealed. Chillers from 1500 tons
`to 3000 tons are generally the open-drive centrifugal water
`chillers. These units are not hermetically sealed because the
`compressor and motor drive are mounted outside the chiller
`unit. Three thousand tons and larger are customized units.
`Manufacturers such as Carrier, Trane, and York are capable
`of providing chillers in the 1000 ton to 3000 ton size. Each
`chiller will operate in ‘parallel, to increase availability of the
`system.
`Typical flow calculations for each centrifugal chiller unit
`are based on the following:
`
`0 Leaving chilled water temperature = entering temper-
`ature
`temperature drop
`' Leaving condenser water temperature = entering tem-
`perature + temperature rise
`
`' Chilled water flew (gpm)=
`
`° Condenser water flow (gpm)=
`
`Cooling load (tons) x 24
`temperature drop
`Cooling load (tons) x 29
`temperature drop
`
`The temperature rise and drop is generally limited to 10°F.
`This value can be increased at the expense of derating of the
`chiller unit. For example, the increase temperature of the cool-
`ing water from 10°F to 15'F will derate the chilling capacity
`01' the chiller by approximately 5 percent.
`The selection of the 1500 ton centrifugal chiller was based
`on the cost per ton, delivery, and electrical load requirements.
`Based on manufacturer's information, the costs per ton for
`chillers were:
`
`1000—1500 ton chillers
`1500-5000 ton chillers
`Over 5000 ton chillers
`
`$133/ton
`$320/ton
`$145/ton
`
`The smaller centrifugals would be the most economical pur-
`chase based on capital cost; however, the cost of the installation
`and required area would be much greater than for the large
`Chillers. The larger tonnage chillers were either too costly or
`required a large motor driver far their operation. A 5000 ton
`Chiller would require a motor size of approximately 4300 hp.
`
`This type of motor would be custom built and associated with
`long delivery. In addition,
`these units would require high-
`voltage electrical devices.
`The mechanical chillers need only electricity and condenser
`water to provide all chilled water requirements; there is no
`need to provide steam or another thermal energy source. Also,
`the mechanical chillers provide more tons of cooling in one
`machine than in other types of chillers. This will result in lower
`installation costs and less plot space required.
`However, the consumption of electricity will reduce the po-
`tential output of the plant, reducing the electrical energy gen-
`erated. Although chlorinated fluorocarbons (CFC) have been
`in use for years as part of refrigerants used in direct expansion
`refrigeration such as centrifugal chillers, these CFCs may po-
`tentially be banned from use because of their damaging effect
`on the ozone layer in the atmosphere, The mechanical chillers
`will require high-voltage electrical devices to support the chiller
`motors, MCCs, relays, motor starters, etc. This additional cost
`will increase the overall price of the chillers. Manufacturers
`of the Mechanical Chillers are: Carrier Corp., The Trane Com-
`pany, and York, Division of Borg-Warner.
`
`Thermal Energy Storage Systems
`The GT can take advantage of on—peak and midpeak energy
`costs by using mechanical chillers and the Thermal Energy
`Storage Systems or TES. The TES system is based on a storage
`medium with high specific or latent heat, ice, water, or eutectic
`salts. This storage will contain the cooling produced during
`the low-cost off-peak hours for utilization during the high-
`cost on-peak hours.
`
`Chilled Water Storage. The design basis requires chilled
`water to be provided during the peak months of the year, from
`March to November, during the peak hours, averaging 10 hours
`per day. During the off-hours, the operator can take advantage
`of the lower electrical rates by operating the mechanical chill-
`ers, producing 44°F chilled water for the TES system. The size
`of the storage capacity will depend on an economic evaluation
`of the chilling profile. A full-size TES tank would provide all
`of the cooling load during the midpeak and peak hours. A
`partial, load-leveling TES tank will reduce the Overall size of
`the peak cooling load profile and levelize the production of
`chilled water over the 10 hour period. Estimated size of the
`TES tank will be:
`
`Journal of Engineerlng lor Gas Turbines and Power
`
`APRIL 1991, Vol. 113 I 207
`
`Page 5 of 9
`
`GE Exhibit 1008
`
`

`

`
`
`The i1
`tempera
`to 52‘F
`both sen
`water at
`midity il
`existing
`air syste
`corrosio
`structior
`cooling
`Please
`accompl
`Wetted 11
`energy a
`atures. '1
`from set
`medium
`The w
`must pa,
`full com
`Utilized :
`
`Chiller
`ceIJtual a
`44°F Chi
`
`cmu mu can:
`
`All?
`
`rll. it?
`
`5;;
`.......
`,____________|
`
`
`
`
`nun
`
`
`
`-
`m...
`113%?
`
`
`
`tum-unmet
`awn-m can."
`
`
`
`_________—. .1.“ m, m“,
`
`_-...] no- m- IP05
`
`”nits! sit»-
`sum-u:
`
`wet-c mm
`.. n... ,‘fl
`
`mull “It.“ in ___.__. ———
`Inluutih nrr- np"
`
`_ » ——.-—<__—
`__
`stmum
`mac-mu M
`
`_“
`
`emu: In.
`
`mm r»-
`
`Fig. 8 Hybrid chilling diagram
`
`
`
`Fig. 9 Chilled water coils (courtesy ol Coll Co. Inc.)
`
`5
`i
`i
`
`| iF
`
`inlet air coils to cool the air from 95°F to 52°F or to 46‘F.
`Application of the hybrid system results in lower chilled water
`temperatures in the chilled water system associated with less
`piping and pumping costs. Also, the cooling coils will be mote
`effective, decreasing the overall size requirements.
`
`F.
`
`Chilled Water Distribution System
`The chilled water distribution system will circulate 44":
`chilled water from the chilled water plant and into each GTG
`inlet filter house and return with 54°F water. The inlet cooling "_
`system will distribute the chilled water through an indirect Of
`"
`a direct contact heat exchanger that should be installed across
`the inlet air flow cross section.
`The installation of the inlet cooling system will result in ii
`Permanent increased pressure loss to the inlet of the GTG‘
`"
`General Electric's performance curves have indicated thaté
`4" water column pressure drop will result in a 1.45 perm“i
`decrease in power output, 0.45 percent increase in heat rate.
`and an increase in exhaust gas temperature of TR We antiC'
`ipate that the inlet pressure loss should not exceed 2“ watel
`column.
`
`3
`-
`i
`
`1'
`
`Transactions of the ASME .
`
`_
`
`Tank Capacity (gal.)
`(be)
`Chiller size (tons)
`Stored cooling (ton/hr)
`Notes:
`
`Full
`Partial
`
`size (1)
`size (2)
`15,120,000
`8,820,000
`360,000
`210,000
`7,500
`4,375
`105,000
`61,250
`
`1 These values assume that the mechanical chillers will not
`operate during midpeak and on-peak.
`2 These values assume mechanical chiller operation 24 hr/
`day at an average load.
`
`The size of the tank that will be required for the TES system
`may result in space constraints and large costs.
`
`Ice Storage. The ice storage system can also be used in a
`scenario similar to the chilled water storage system. The volume
`of ice required will be from 7 to 14 times less than the water
`system (based on 144 Btu/lb ice latent heat of fusion versus
`10 to 20 Btu/lb water heat capacity). However, the equipment
`to provide the 85,000 ft3 to 168,000 ft3 of ice will require large
`real estate.
`
`Hybrid System (Mechanical/Absorption) (Fig. 8)
`The hybrid system is a combination of the lithium-bromide
`(LiBr) and the mechanical centrifugal chiller systems. The LiBr
`system will chill the return water from S4“F to 44°F and the
`mechanical chiller will further reduce the temperature to 38 “F.
`This will be a series type system: two 50 percent capacity trains
`of absorption and mechanical chillers (reference drawing Fig.
`8).
`This system will initially take advantage of the steam avail~
`able at the facility and will enable the mechanical chillers to
`consume less power during the production of colder chilled
`water. The system is sized for one-half of the cooling by ab-
`sorption and the other by centrifugal chilling, which will con-
`sume approximately one-half of the total required power than
`the mechanical chiller system. The 38°F chilled water supply
`will increase the temperature differential of the cooling coil
`inlet and outlet (38"F to 54"F). The larger differential tem-
`perature will reduce the overall chilled water flow rate, reducing
`pumping costs as well as piping requirements.
`The lower chilled water temperature can be used in the GTG
`
`208 I Vol. 113, APRIL 1991
`
`Page 6 of 9
`
`GE Exhibit 1008
`
`

`

`ysis utilizing PVC cooling tower media in direct contact with
`44‘F chilled water for gas turbine inlet cooling was performed.
`The medium is cooling tower packing placed in the straight
`crossflow position and sprayed with chilled water to create a
`direct contact chilled water evaporative cooler with an ap-
`proximately 90 percent relative humidity saturation capacity,
`shown in Fig. 10.
`A computer multiple alternative analysis examined three
`flow rate conditions consisting of 8, 12, and 16 gallons per
`square foot of face area and comparing two face veloeities of
`500 and 750 feet per minute, respectively.
`To obtain the 52"F inlet temperature requirement necessi—
`tates a face velocity of 500 feet per minute and 12 gallons per
`square foot, i.e., 12,000 gallons per minute and 1000 square
`feet of surface area or 750 feet per minute and 16 gallons per
`square foot, i.e., 650 square feet of surface area and 10,000
`gallons per minute, respectively.
`The advantage of direct contact cooling is lower first cost
`and relatively low pressure drop. The disadvantage is the need
`for extensive water treatment associated with continuous blow-
`down, Potential for biological buildup exists, resulting in higher
`maintenance than a closed system. Also, large circulation water
`quantities are required, depending on performance, from 8 to
`16 gallons per square foot.
`
`Indirect Evaporative Cooling. The indirect evaporative
`cooling method lowers the dry bulb temperature without the
`increased moisture content of the GTG inlet supply air, ef-
`fectively reducing the wet bulb temperature of the air and the
`Overall energy content.
`The indirect method is accomplished by using a plate-type
`air-to-air heat exchanger, shown schematically in Fig. 11:
`c On one side, outside air is directed to one end of the
`exchanger as scavenger air. Water is sprayed onto the plate
`surface in contact with this air stream where evaporation takes
`place, cooling the plate approaching the wet bulb temperature.
`The water is collected in a sump and is recirculated back into
`the exchanger. The air is then exhausted above the unit into
`the atmosphere by an axial fan unit.
`' 0n the other side, the GTG inlet air supply passed across
`the plate and is cooled by convection to near the wet bulb
`temperature and passes into the gas turbine.
`
`This type of cooling is effective when there is adequate water
`available. The dry bulb air temperature can be reduced without
`increasing the latent heat at minimal cost of water and elec~
`tricity.
`For example, if the outside ambient air temperature is 95°F
`dry bulb and 71 aF wet bulb, the indirect evaporative method
`of cooling will reduce the GTG inlet dry bulb air temperature
`to approximately 74‘F, effectively reducing the total cooling
`load by 40 percent. This would translate into approximately
`4000 tons of cooling.
`Although the indirect cooling system will reduce the inlet
`air temperature to 75 °F, cooling coils will be required to reduce
`the air temperature further to 52°F. The pressure drop through
`the indirect cooler is estimated to be from 3” to 4” of water,
`which would reduce the gas turbine power output by approx-
`imately 1.45 percent. In addition, the cooling coils will add
`another 1" to 1.5” of water pressure drop.
`Due to the overall size of the cooling unit, there may be
`some problems of system installation. There is limited space
`available within the filter house for an installation of this type
`and significant GTG downtime.
`The saturated air exhaust from the indirect cooler is located
`at the filter house, which would defeat the purpose of this
`system; the air will potentially recirculate back into the inlet,
`adding the latent heat that was absorbed. Ducting

This document is available on Docket Alarm but you must sign up to view it.


Or .

Accessing this document will incur an additional charge of $.

After purchase, you can access this document again without charge.

Accept $ Charge
throbber

Still Working On It

This document is taking longer than usual to download. This can happen if we need to contact the court directly to obtain the document and their servers are running slowly.

Give it another minute or two to complete, and then try the refresh button.

throbber

A few More Minutes ... Still Working

It can take up to 5 minutes for us to download a document if the court servers are running slowly.

Thank you for your continued patience.

This document could not be displayed.

We could not find this document within its docket. Please go back to the docket page and check the link. If that does not work, go back to the docket and refresh it to pull the newest information.

Your account does not support viewing this document.

You need a Paid Account to view this document. Click here to change your account type.

Your account does not support viewing this document.

Set your membership status to view this document.

With a Docket Alarm membership, you'll get a whole lot more, including:

  • Up-to-date information for this case.
  • Email alerts whenever there is an update.
  • Full text search for other cases.
  • Get email alerts whenever a new case matches your search.

Become a Member

One Moment Please

The filing “” is large (MB) and is being downloaded.

Please refresh this page in a few minutes to see if the filing has been downloaded. The filing will also be emailed to you when the download completes.

Your document is on its way!

If you do not receive the document in five minutes, contact support at support@docketalarm.com.

Sealed Document

We are unable to display this document, it may be under a court ordered seal.

If you have proper credentials to access the file, you may proceed directly to the court's system using your government issued username and password.


Access Government Site

We are redirecting you
to a mobile optimized page.





Document Unreadable or Corrupt

Refresh this Document
Go to the Docket

We are unable to display this document.

Refresh this Document
Go to the Docket