throbber
SA-96-12-2
`
`Design Issues of Variable Chilled-Water
`Flow Through Chillers
`
`Thomas B. Hartman, P.E.
`,\1ember ASHRAE
`
`ABSTRACT
`
`Variable-speed alternating current (AC) drive technolo(cid:173)
`gies are of particular interes!for heating, ventilating, and air(cid:173)
`conditioning (H VA C) designs because controlling motor
`speed with variable-frequency AC drives to achieveflow mod(cid:173)
`ulation provides an opportunity to capture exceptionally high
`part-load operating efficiencies. Since HVAC systems spend
`long hours operating at part-load conditions, improvement in
`part-load efficiency results in substantial energy savings.
`Applying variable flow to chilled-water systems is particularly
`attractive because chilled-water pumping has !Yro associated
`power costs, directly as pumping power and also as a load on
`the chiller plant. The small temperature differentials associ(cid:173)
`ated with chi/led-wata systems mean load-side stratification
`is generally not a concern. but the small temperature dijferen(cid:173)
`tials do raise concerns about heat transfer at reduced flows.
`
`Presently, typical rariable-flow chilled-water systems are
`designed with flvo chilled-water circuits: primary and second(cid:173)
`ary. The primary circuit is usually a low-head circuit that
`maintains a constant chilled-water flow through the chiller,
`while the secondary chilled-water pump(s) provide variable
`flow to the loads based on their demand for cooling. Because
`the primary circuit is low head and requires relatively low
`power, it is often reasoned that /lVo-circuit configurations
`involve only a small pumping energy penalty and only when
`operating at low loads. However, closer analysis uncovers the
`following true penalties ..
`
`a first-cost penalty for employing two separate pumps,
`
`a part-load chiller efficiency penalty from mixing bypassed
`supply chilled water with the return chilled water, and
`
`a chiller capacity penalty of underutilizing the full chiller
`capacity during high cooling demands at conditions not
`precisely congruent to the design peak conditions.
`
`For many building cooling applications, it is possible to
`design a chilled-water supply and distribution system with only
`a single variablejlow circuit. Such designs can avoid the prob(cid:173)
`lems listed here. However; there are potential pi!falls that must
`be considered before such a system can be successful. This paper
`discusses the benefits and problems associated with a single(cid:173)
`circuit variable-chilled-water-:Ji 'ow system and offers a chiller
`plant control strategy that can provide safe, stable, and reliable
`chiller operation over the entire operating range employed in
`typical HVAC applications.
`
`INTRODUCTION
`
`Traditional chilled-water plant design utilizing variable
`chilled-water flow involves primary/secondary loops with sepa(cid:173)
`rate pumps, as shown in Figure 1. Typically, one low-head
`primary loop pump for each chiller in the primary circuit provides
`aconstant flow through the chiller, while one or more higher head
`variable-flow secondary loop pumps modulate to adjust second(cid:173)
`ary chilled-water Jlow to meet actual cooling demand. The imbal(cid:173)
`ance in Jlow between the primary and secondary circuits results
`in Jlow through the bypass piping circuit. While this configura(cid:173)
`tion satisfies the objective of maintaining constant chilled-water
`flow through thechiller, it may not achieve the highest chiller effi(cid:173)
`ciency at part loads and can limit chiller capacity due to the fact
`that under almost all operating conditions, the flows in the tvvo
`loops are not equal.
`To achieve the full potential of variable chilled-water flow
`in an environment of integrated HV AC equipment operating
`under high-performance control strategies, it is necessary to
`rethink the physical configuration of variable-flow chilled-water
`systems. Recent work (Hartman 1993) has shown that integrated
`control strategies can be employed to operate variable-flow
`chilled-waterdistribution systems at much higher efficiencies by
`coordinating the pump speed directly to the load demands with(cid:173)
`out employing pressure control. It is prudent also to analyze the
`
`Thomas B. Hartman is a principal of The Hartman Company, Marysville, Wash.
`
`Page 1 of 5
`
`GE Exhibit 1007
`
`

`

`1
`-~'---CH_IL_LE_R-1
`
`co"'''"'
`
`Speed
`Pr1mary
`Pump
`
`VO.r"•O.blt>
`Speed
`S.econdory
`Pvnp
`
`LOAD 1
`
`LOAD 2
`
`LOAD 3
`
`Fig11re I Primary/secondary chilled-ux1ter loop.
`
`operation of the primary circuit before a particular configuration
`and control scheme is adopted.
`The striking feature of Figure I is the necessity of having
`two separately powered chilled-water circuits. Designers should
`ask themselves whether this is really necessary. The constant(cid:173)
`flow primary circuit has become accepted design practice
`because it is well known that below certain velocities of flow
`through heat exchangers, a switch to laminar flow may cause
`sudden substantial reductions in heat transfer capacity. The
`purpose of the primary pump is to ensure such a condition never
`troubles the system. However, at very low cooling capacity
`requirements, the heat transfer requirements are also greatly
`reduced, and by monitoring the chiller load, chilled-water
`temperature, and refrigerant temperatures, a properly integrated
`control system can easily adjust the overall system operation if
`water flow becomes too low to provide efficient heat transfer or
`may cause the chiller to approach operating limits If the control
`system is operating with suitable high-performance control algo(cid:173)
`rithms, it can promptly make the necessary corrections to ensure
`efficient and stable operation of the entire system at all load
`conditions. With this in mind, consider the simpler piping
`configuration in Figure 2.
`
`In Figure 2, the chiller itself may be a variable-speed unit,
`but in any case, it is one that offers a high turndown ratio and an
`
`VARIABLE SPEED
`CHILLER
`
`Variable Speed
`Chilled Water
`Pvnp
`
`LOAD 2 1- - &1- . -
`
`~
`I
`
`L 0 A D
`
`. - &1- . -
`
`31
`
`LOAD 4
`
`Figure 2 Single-circuit variable-flow flow chilled-water loop.
`
`increasing coefficient of performance (COP) as the cooling load
`is reduced. The required rate of flow through the chiller depends
`on the cooling load being delivered. This is a good design fit
`because the loads are connected with two-way valves such that
`load-side flow also varies with load. In such a scheme, both the
`chilled-water flow and chiller capacity are adjusted to effectively
`meet all load conditions. A threshold cooling capacity limit is
`defined below which the system does not operate, just as is the
`case with present chiller systems. The potential benefits of a
`single-circuit variable-flow chiller system as shown in Figure 2
`are:
`
`lower tirst cost and lower maintenance costs,
`higher overall chiller plant operating efficiencies, and
`greater flexibility in utilizing full chiller capacity at peak
`conditions.
`
`Before discussing these benefits in detail, let us consider the
`critical issues of such a design.
`
`SINGLE-CIRCUIT VARIABLE-FLOW
`SYSTEM CONSIDERATIONS
`
`Configuring a variable-flow chilled-water system as shown
`in Figure 2 does not mean it will work adequately under all load
`conditions without specific attention to the chilled-water flow
`0\er the wide range of potential operating conditions. To ensure
`effective and efficient operation of the Figure 2 configuration,
`several basic requirements must be met. First, the system must
`not be permitted to operate unless the cooling requirement is
`above a minimum threshold load. The threshold cooling load
`requirement is the lowest stable chiller operating load.
`
`SA-96- 12-2
`
`Page 2 of 5
`
`GE Exhibit 1007
`
`

`

`Next the water flow through the chiller evaporator heat
`exchanger must always be sufficient to maintain evaporator
`temperature within suitable limits. Typically, the chiller manu(cid:173)
`facturer recommends a varying evaporator temperature range as
`a function ofthe chiller load, and the relationship between chiller
`efficiency and e\ aporator temperature is an important consider(cid:173)
`ation as well.
`Finally, for the Figure 2 system configuration to be effec(cid:173)
`tive, the nature of the loads must be such that chilled-water
`temperature can rise as the load decreases. Chilled-water
`systems that require low chilled-water temperature under low(cid:173)
`load (low-flow) conditions must be carefully considered before
`such a configuration is adopted. Examples of systems with such
`special requirements are those that may be called upon to provide
`significant dehumidification at low loads or those supplying a
`variety of loads. a significant number of which may be shut off
`during peak-load conditions.
`In many HVAC applications, these limitations do not pose an
`absolute bmTier to employing the system configuration in Figure
`2. However, a complete analysis under the entire variety of oper(cid:173)
`ating conditions that could be encountered must be accomplished
`to be certain the single-circuit scheme will perfotm satisfactorily
`under all conditions. In typical North American single-building
`applications, even though portions of the building may be unoc(cid:173)
`cupied under certain conditions, the single-circuit configuration
`is usually a good candidate for effective and economical space
`cooling.
`In addition to the load requirements listed above, a single(cid:173)
`circuit variable-flow chiller system will be successful only as
`long as the direct digital control (DOC) system has the capacity
`to integrate the operation ofthe chiller(s), pump(s), and the loads
`the system serves with high-performance control algorithms. The
`start -up sequence for a single-circuit chiller system must provide
`calculations of present and upcoming cooling load requirements
`for all loads served. The cooling system is held off until the sum
`of the calculated load requirements reaches a threshold value that
`depends in part on anticipated upcoming conditions. Once
`enabled, high-performance control algorithms must be employed
`to coordinate the cooling loads, pump speed, and chiller capacity
`to meet the demand for cooling at the loads and meet the opera(cid:173)
`tional constraints of the chiller and other system components.
`
`SINGLE-CIRCUIT VARIABLE-FLOW
`CHILLED-WATER SYSTEM CONTROL
`
`Even if it were feasible, it is not optimal to operate the chiller
`in a single-circuit variable-flow system to maintain a constant
`chilled-water temperature. However, without a clear connection
`between chiller capacity and chilled-water pump flow, control
`can become indeterminate and result in erratic operation as the
`changes in chiller capacity and t1ow affect each other. One of the
`great resistances chiller manufacturers have to varying the flow
`of chilled water through chillers is the ditliculty in establishing
`smooth chiller capacity control under varying flow conditions.
`To control the chiller(s) and pump(s) most effectively, some
`simple mechanism of correlating the operation of the two
`
`together is required. Some approaches have been previously
`discussed (Hartman 1 995). One approach that shows a great deal
`of promise is the use of coordinated chiller and pump (CCP)
`control.
`In coordinated chiller and pump control, both the chilled(cid:173)
`water pump and chiller capacity are controlled to react to
`changes in cooling demand at the loads, so that as loads change,
`pump speed and chiller capacity are adjusted in unison (percent
`chiller electric load is set proportionately to the pump motor
`load). This is a simple and effective way to coordinate the oper(cid:173)
`ation of the chiller and pump. The chiller capacity is adjusted in
`proportion to chilled-water pump power (or to the cube of pump
`speed). In this scheme, at approximately 93% of the design water
`flow through the chiller (and the loads), the chiller is operated at
`80% of maximum electrical demand (0.933). At approximately
`60% of the design maximum chilled-water flow, the chiller is
`operated at approximately 22% of maximum electrical demand
`(the same percentage of maximum electrical demand as required
`by the chilled-vvater pump).
`It is important to note that because the COP of the chiller
`rises as the load decreases, the cooling capacity of the chiller (in
`most typical circumstances) does not fall by the same amount as
`its electrical load reduction (which is controlled to adjust chiller
`capacity). The exact change of chiller capacity with respect to
`electrical draw depends on the type of chiller (variable-speed or
`constant-speed) and evaporator and condenser conditions.
`Furthermore, there may be limits to the capacity adjustment range
`that depend on current operating conditions. For this reason, a
`minimum (and in some cases maximum) evaporator and chilled(cid:173)
`water temperature algorithm and minimum capacity algorithm
`operate in parallel with the direct pump control algorithm as a
`limit to the primary chiller capacity control algorithm.
`CCP control does not directly control chilled-water temper(cid:173)
`ature. However, in regions where it may be required, the CCP
`control strategy may be extended to provide some flexibility in
`adjusting chilled-water temperatures for more or less dehumid(cid:173)
`ification under part-load conditions. In this way, the chilled(cid:173)
`water flow to chiller capacity algorithm can be adjusted slightly,
`depending on humidity conditions, to provide more or less latent
`cooling. A sample algorithm in the operators' control language
`(THC 1988) for a simple CCP control is shown in Figure 3.
`
`BENEFITS OF SINGLE-CIRCUIT VARIABLE-FLOW
`CHILLED-WATER SYSTEMS
`
`Because traditional design has steadfastly adhered to the
`concept of constant chilled-water flow through chillers, the
`industry has never had adequate discussion on the benefits of
`employing variable-flow schemes. Generally,
`it has been
`assumed that the benefits are limited to savings in the cost of the
`primary pump and a small energy reduction. At part-loads,
`however, if one focuses on a comparison between the operation
`of the systems under various conditions, the potential benefits are
`seen to be far more substantial.
`Consider the tlow difference between the primary and
`secondary circuits in a traditional two-circuit system as repre-
`
`SA-96-12-2
`
`3
`
`Page 3 of 5
`
`GE Exhibit 1007
`
`

`

`"'ETEAMINE IF CHI'll...ER PUN1 SHOULD RUN"
`00E\I£RY 1 tr.A
`Q.G..oAAO-ll .. MAX((AHU1MAT·AHU1SAT..sP')•J.oas•AHt.JlFLO'M. 0)
`a.G..oMCH...2 .. W.X{(I\HU2MAT-.AHU1SA.T-SPJ"I.086'"AHU2f1..0W). O)
`O..G..OMO-Ln ... MAX{(AHlX\MAT-#'\Ur\SAT.sPj•l Dae"'AH\JI'IFLOW), 0)
`... ClG...OMC..U .....
`0..G..Q1.l0 - CtG..{)t.U).-U + Cl,G...{)M()....(...2
`U.G-DMD • ClG·DMO • (PROJ-HIGH· TEMP 1 70)
`"STAAT AND SiOPQ;!LLER BAS~D ON OEMAJ-.10
`IF Cl.G.p<J..Nl OFF-FOR 30M AND ClG.OMD > 0 4"CAPACITYTHEN
`STAATD..G--Pt..N-If
`
`END
`IF CLG...f>i...ANT ON ANO CLG...oMO < O.:r CAPACITY OA P'UMP..s.PEED <50
`00 EVAP-TEMP < 3.5 OR CONO-TEMP > M THEN
`STC>' O..G.f>V.Nl
`
`END
`
`'WHEN COOUNG: PlANT IS ON QPE'AATE PVMP ACCORDING TO VA.t..VE PO$ffi0N$'"
`!FOr= CLG-PW<r 00 THEN 1'\JW'-SPEED • ~
`IF ct.G-Pt....ANT ON THEN
`If W.X.VAlVE..POS > ~THEN
`PU~P-sf"EEO ... PUMP-SPEED -t 1
`
`PUMP-SPEED • PUMP-SPEED. {10. AV£-VJ,J...vE.p()S} /10
`
`ELSE
`
`END
`• OI'ERATE CH!Ll.S1 CAPt.CtTY IN ;.ccoAOANC!: l'mH PUMP SPEED
`If Cl().-.PI.).NT ON..fOO < 10M THEN
`Q-lt.R..{)t,(D • 0..4
`
`<>Ul"""D • (>'l)I.IP.sPfi'D/100) ~3
`IF EVAP-TE.IrAP < -40 ~ CHI..A-t:::f..t0/2S THEN C>U.A..ot.ID • CHLR.OOD 10
`IFCONO-TEW' > SOTHENCHl.A-OMO • W.X(CHI.R..,.,.D, "')
`•
`
`END<F
`
`ENDOO
`
`O..G-C>UC-t 1 .. D..G-OMO-ln AAE Thf CUAAENT COOUNG DEMANDS FOR EACH OF THE COOl·
`JN(il.OAO$ SEFivECBYTHECHII.l.ER
`
`PROJ-HIGH-tEMP tS TH£ DAY'S PROJECtED HIGH OUtSIDE TEMP'ERATVRe AS CAl.CVLATEO
`6Y THE DOC SYSTEM
`
`Figure 3 Sample variable-flow single-circuit chilled-
`water plant control program.
`
`sented in Figures 4a and 4b. Figure 4a represents !low at low
`demands for cooling, Under this condition, the tlow in the
`primary loop is substantially higher than that in the secondary.
`The higher temperature chilled water returning from the loads
`mixes with bypassed supply chilled water, which reduces the
`chilled-water inlet temperature, which adversely impacts the
`overall chiller operating efficiency at part-load conditions. To see
`hoi\ important this part-load energy penalty can be, consider
`Figure 5. which shows occurrences of various chiller load condi(cid:173)
`tions in typical oftice buildings in four different regions in North
`America. Notice that for an overwhelming majority of the time.
`the chiller plants in all regions operate at low loads. The right(cid:173)
`hand portion of FigureS shows the annual chiller operating hours
`as a percentage of total building operating hours. Note from
`Figure S that although chillers in warm climates of North Amer(cid:173)
`ica operate longer hours, chiller plants in all climates operate at
`roughly the same overall annual load profile. Note also that the
`North American chiller load profile includes chiller plant opera(cid:173)
`tion at less than 60% of design load form ore than 70% of the
`chiller operating hours. The loss of chiller efficiency because of
`primary/secondary tlow differences at part-load conditions can
`be a substantial penalty in many building HV AC applications.
`
`Now, consider Figure 4b for tlow at high loads. For energy
`efficiency, the tlow of the primary circuit is likely to be less than
`the maximum flow capacity of the chiller. Such a selection
`reduces primary pump horsepower from two perspectives(cid:173)
`lower tlow through the primary circuit and also lower pressure
`drop through the chiller. However, the penalty for less primary
`pump horsepower is that the secondary tlow during peak cooling
`requirements may exceed the primary loop flow. During these
`
`periods. return water fi·om the loads is mixed with chilled-water
`supply. Such conditions occur frequently in chilled-water-to-air
`coils because the load conditions (airflow or air psychrometric
`conditions) do not match the design assumptions precisely.
`With the warmer chilled-water supply, the loads may not be
`satisfied and the chiller may not be capable of operating at full
`load because it cannot compensate below its minimum chilled(cid:173)
`water temperature limit. Such a condition results in chiller
`underutilization. The cooling capacity of the chiller may be
`adequate, but the limitations of the primary circuit do not enable
`the full capacity to be utilized. The only.way to eliminate the
`possibility of this problem in a primary/secondary chilled-water
`distribution system is to increase the flow and pressure capacity
`of the primary pump(s). This then results in an increased energy
`penalty for the overwhelming majority of the hours the plant
`operates below peak capacity.
`In the single-circuit scheme there is no bypass. All return
`chilled water enters the chiller without bypassed supply water.
`Furthennore, the variable-speed pump can be sized for a maxi(cid:173)
`mum flow that is somewhat above the design load assumptions.
`This way the designer is ensured that the full capacity of the
`chiller can be utilized when peak loads occur at conditions that do
`not match design conditions exactly.
`
`SUMMARY AND CONCLUSIONS
`While there are limitations to the employment of single(cid:173)
`circuit variable-flow chilled-water systems for building cooling
`applications, the opportunities available to designers -with the
`expertise necessary to apply integrated high-perfonnance DDC
`to these systems make compelling reasons to consider such
`systems. Single-circuit variable-flow chilled-water systems that
`are carefully designed and operated with integrated high-perfor(cid:173)
`mance controls offer the following:
`
`1. Simpler equipment configurations with accompanying first(cid:173)
`cost savings that can reduce the system costs or be invested
`in higher quality, longer lasting components.
`2. Lower total system energy use than what is possible with
`nonintegrated configurations and control strategies.
`3. Control precision that is superior to that of nonintegrated
`traditional control approaches.
`
`To fully exploit the benefits of emerging integration of
`HV AC equipment with high-pe1formance DDC systems, design(cid:173)
`ers should consider single-circuit variable-flow chilled-water
`systems. For many typical applications, the benefits can be
`substantial.
`
`REFERENCES
`Hartman, T. 1993. Direct digital controls for HVAC systems,
`chapter I. New York: McGraw-Hill.
`Hartman, T. 1995. New horizons for HVAC control. Heating1
`Piping1Air Conditioning, March.
`THC. 1988. Operators' control language: A guide to program(cid:173)
`ming functions for DDC systems. Seattle: The Hartman
`Company.
`
`4
`
`SA-96-12-2
`
`Page 4 of 5
`
`GE Exhibit 1007
`
`

`

`~
`
`C\1 R(Tl.RN
`fROH LOADS
`
`S[C[t.IDARY PuMP rLOV IS L(SS TKA.N PR)HARY ?t..HP f'LOV AT LOV LOAD CONDfT!t:NS...
`AT TH[S:[ T !1-f:S:, A rlOV OF VAT(R EOI.W.. TQ T~ Dtrr(R(NC( IN tt,.O\/S
`'&E TV([N
`P! AND PZ BYPASSES TH( SECCNDARY Cl~UH AND MIXES VlT~ RETuRN VAT(R rRQH
`:,.QAl1S. LDW'ERI~C.. THE R(TURI-l T(l'f>(RA fl..~( TO TH( CHllL(R ti.NO RCOVC!NG TH(
`POSSIBL( Crf"!CICNcY or TH(. CHILl(~.
`
`Figure 4a Chiller flow at load conditions.
`
`tv R( TURN
`TO CHILLER
`
`S(CDNMR'f PVHP
`
`~ v.-RJ>\Bl( r't,.OV
`
`~
`
`PZ
`
`CV SlRPL Y
`TO LQ.i.DS
`
`SECONDAI.?Y f>t)~P rLOV IS C.RfAT(R THAN PRlHARY ?UkP fLO\/ AT P(AK LOAD
`CONDITION$.. AT
`f>'((S( TIHES. A rLO\ol Of VATER (IAJAL lO lHC OlfTER£NCE
`IN fLOVS 3(1\J((N P2 AND Pl f\.OW'S FROM. lHC SECONDARY ROtJRN TO TK(
`HCONDAR'" SuPPLY. RAIS:ING
`lHE SVf'f't,...Y T(]·IP{:RATt.:R( TO LOADS AND
`lHE P(A.X CAPACITY AND EfriCl£1-f:Y OF r;< (NT!kE S'fS.TEt-1
`R(IJUClNG
`
`Figure 4b Chiller flow at peak load conditions.
`
`Figure 5 Office building chiller operation
`
`SA-96-12-2
`
`Page 5 of 5
`
`GE Exhibit 1007
`
`

This document is available on Docket Alarm but you must sign up to view it.


Or .

Accessing this document will incur an additional charge of $.

After purchase, you can access this document again without charge.

Accept $ Charge
throbber

Still Working On It

This document is taking longer than usual to download. This can happen if we need to contact the court directly to obtain the document and their servers are running slowly.

Give it another minute or two to complete, and then try the refresh button.

throbber

A few More Minutes ... Still Working

It can take up to 5 minutes for us to download a document if the court servers are running slowly.

Thank you for your continued patience.

This document could not be displayed.

We could not find this document within its docket. Please go back to the docket page and check the link. If that does not work, go back to the docket and refresh it to pull the newest information.

Your account does not support viewing this document.

You need a Paid Account to view this document. Click here to change your account type.

Your account does not support viewing this document.

Set your membership status to view this document.

With a Docket Alarm membership, you'll get a whole lot more, including:

  • Up-to-date information for this case.
  • Email alerts whenever there is an update.
  • Full text search for other cases.
  • Get email alerts whenever a new case matches your search.

Become a Member

One Moment Please

The filing “” is large (MB) and is being downloaded.

Please refresh this page in a few minutes to see if the filing has been downloaded. The filing will also be emailed to you when the download completes.

Your document is on its way!

If you do not receive the document in five minutes, contact support at support@docketalarm.com.

Sealed Document

We are unable to display this document, it may be under a court ordered seal.

If you have proper credentials to access the file, you may proceed directly to the court's system using your government issued username and password.


Access Government Site

We are redirecting you
to a mobile optimized page.





Document Unreadable or Corrupt

Refresh this Document
Go to the Docket

We are unable to display this document.

Refresh this Document
Go to the Docket