throbber

`
`
`
`
`
`
`
`Hayward Industries, Inc.
`
`
`EXHIBIT 1020
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`Hayward Exhibit 1020
`Inter Partes Review of
`US Patent No. 8,019,479
`
`

`

`
`
`nipower®
`HPL'I 'I o, HPL420
`Programming Suggestions for
`Centrifugal Pumps
`
`General Principles
`Centrifugal pumps are constant head -
`variable flow systems with a power
`consumption which basically tracks
`flow rate as shown in Fig. 1.
`
`Since power consumption tracks flow,
`power monitoring is an effective
`basis 'or monitoring and protection.
`
`
`
`
`
`For seal-less centrifugal pumps, it is
`partic larly important to protect against
`dry—running since without fluid, the rotor
`rubs directly against the stator housing.
`Whe
`dry running occurs, the power
`consumed by the pump immediately drops
`to a very low level — well below the zero flow
`powe and approaching the idle power of
`the rrotor. This characteristic makes power
`
`monitoring particularly useful for protecting
`seal-less pumps from dry—running.
`
`Figure 1
`
`Alarm functions required for centrifugal pump protection are:
`Low Power:
`
`— Dry-running due to lack of fluid, blocked inlet, air induction,
`— Operation below l\/lin. Safe Flow leading to over—heating and fluid vaporization,
`
`High Power:
`- Operation above Max. Safe Flow leading to cavitation and unstable operation,
`—
`lammed impeller.
`
`The Unipower HPLi 10 and HPL420 models both incorporate high/low power alarm
`functions suitable for pump protection applications. Please refer to the relevant
`data sheet for overall information and instructions; this guide is solely intended to
`
`provide suggestions on limit setting for centrifugal pumps.
`
`HAYWARD EXHIBIT 1020
`
`Page 1 of 4
`
`

`

`Unipower Alarm Objectives
`for Centrifugal Pumps
`Once the Unipower system has been installed and basic set-up completed, there are five
`parameters which must be set for effective pump protection:
`
`Ts -
`
`Start Delay Timer: Delays active monitoring until the pump/motor have reached
`normal operating speed (or in the case of self—priming pumps, until prime is
`established).
`
`L1 - Max. Limit Alarm: Alarm when Max. Safe Flow is exceeded.
`
`L2 - Min. Limit Alarm: Alarm when I\/|in. Safe Flow is not met.
`
`Tr1 - Trip Delay for L1: Time duration for which an alarm condition must exist before
`alarm is declared; avoids nuisance tripping due to normal process fluctuations.
`
`Tr2-
`
`Trip Delay for L2: As above for the L2 Min. Alarm.
`
`Setting Ts Start Delay
`While Ts is active, monitoring is disabled so this parameter should be set as short as possible.
`
`For normal primed applications, a typical power vs. time plot is shown in Fig. 2. The motor
`is started at time i and the system settles to a running normal value at time 4.
`In this case,
`Ts is set at 3.5 seconds resulting in normal monitoring becoming active at time 4.5.
`
`Typical Ts values for primed centrifugal pump applications are in the range 1 to 5 seconds;
`default of 2 seconds is a good starting point.
`
`For self-priming applications, the pump starts by running dry until prime is established. This
`results in a period on start-up where the power is below the normal L2 Min. Power alarm
`level and an extended Ts period must be used.
`In these cases, set Ts to the value suggested
`
`by the pump manufacturer (contact WEN Technology if extended Ts options are required).
`
`Setting L1 - L2 Max. and Min. Alarm Limits
`The objective is to set these values to the Max. and Min. Safe Flow power values for the
`pump system. Unipower models HPLI IO and HPL420, however, are programmed in units of
`%kW; programming L1 — L2 in %kW for these models is achieved as follows:
`
`Empirical Peak Detect Method
`First disable the L1 & L2 alarms by setting them to 101% and 0% respectively.
`Run the pump and first open the outlet valve to normal full flow setting then close the
`outlet valve to the normal minimum flow setting. Return the valve setting to normal flow.
`
`Depress the A key and note the max. power experienced by the pump in %kW — set L1
`appropriately above (slightly) this value.
`
`Depress the V key and note the min. power experienced by the pump in %kW - set L2
`appropriately below (slightly) this value.
`
`HAYWARD EXHIBIT 1020
`
`Page 2 of 4
`
`

`

`PW»)
`
`P=f(t)
`
`100%
`
`
`
`
`Ll
`Max. Limit
`
`L2
`Min. Limit
`
`
`
`PowerOn
`
`Relay On
`MotorOn
`
`Figure 2
`
`Emplrlcal Mm. Safe Flow Settlng
`An accurate setting of the critical l\/|in. Safe Flow trip point in %kW can be achieved with
`a slight variation on the above procedure.
`
`Instead of running the pump with the outlet valve set at normal minimum flow, close the
`outlet valve completely and record the power value in %kW with the valve closed — Zero
`Flow %kW (ZF%kW).
`(Be sure to re-open the outlet valve immediately)
`
`From the pump curve, note the power consumption at Zero Flow (ZFP) and at Min. Safe
`Flow (MinP). Use this data to establish the Min. Safe Flow setting for the Unipower unit
`as follows:
`
`Min. Safe Flow (%kW)=ZF°/okW x MinP / ZFP (%kW)
`
`Set L2 to this calculated l\/lin. Safe Flow value in %kW.
`
`Note: This method is quite accurate for setting Min. Safe Flow. However, for basic
`protection from dry—running, any L2 setting which is equal to or above the zero flow —
`dead-headed — power of the pump will be effective.
`
`Setting Tr1 - Tr2 Trip Delays
`The Trl
`- Tr2 Trip Delay timers ensure that the measured power remains above or below the
`respective LI
`- L2 Limits continuously for the time set by the Tr timer; see Fig. 2. As such,
`they reduce sensitivity to short duration process fluctuations and are used to reduce nui-
`sance tripping of the system.
`
`Setting these parameters is empirical. The default values for the Unipower systems are 0.1
`seconds. For pumping applications, it is usual to use a longer Tr time and values in the
`range 1 to 5 seconds are typical.
`
`HAYWARD EXHIBIT 1020
`
`Page 3 of4
`
`

`

`Settlng Protection
`Once the settings have been determined and set, protect the program by setting DIP
`Switch 1 to the “ON” position.
`
`Q: Why are the HPL110 and 420 models not programmed in units of HP?
`
`A: The Unipower motor load monitors measure the input power to the motor whereas
`pump curve data is related to motor output power. And quite a bit more data must be
`entered and processed in order to display and function in engineering units.
`
`Programming based on observed %I<W values is an easy and safe method without
`requiring a detailed knowledge of the motor efficiency curve.
`
`Two options exist for programming from the pump curve in real units of power
`The first option is Unipower model PCU4123 which is programmable in units of kW
`and includes a scaling function which can be used for motor efficiency correction.
`
`The second option is to convert %kW into kW using the equation:
`
`P [100%kW] = i/3 . U .|
`
`is the
`where U is the rated voltage of the unit (e.g. for HPL110/460. V is 460V) and I
`effective primary current (see System Configuration section in Installation Manual).
`Remember that this is the input power to the motor; to convert to output power,
`
`adjust these values based on the efficiency curve for the motor.
`
`A conversion chart for your application can be supplied based on receiving aII the
`information Iisted in the setup log sheet found on the back of the Installation Manual:
`
`for Limits L1 and L2. give the desired Max. and Min. Safe Flow ratings in units of HP or
`kW (please denote which are being given).
`
`Document Number: W199EOO3
`© 1999 Wen Technology. Inc. Raleigh. NC USA
`
`
`WENiechnoIogy
`
`8411 Garvey Drive / Suite 117
`Raleigh, North Carolina 27616
`(919) 954—1004 I Fax (919) 954-1009
`www.wentec.com
`
`HAYWARD EXHIBIT 1020
`
`Page 4 of 4
`
`

This document is available on Docket Alarm but you must sign up to view it.


Or .

Accessing this document will incur an additional charge of $.

After purchase, you can access this document again without charge.

Accept $ Charge
throbber

Still Working On It

This document is taking longer than usual to download. This can happen if we need to contact the court directly to obtain the document and their servers are running slowly.

Give it another minute or two to complete, and then try the refresh button.

throbber

A few More Minutes ... Still Working

It can take up to 5 minutes for us to download a document if the court servers are running slowly.

Thank you for your continued patience.

This document could not be displayed.

We could not find this document within its docket. Please go back to the docket page and check the link. If that does not work, go back to the docket and refresh it to pull the newest information.

Your account does not support viewing this document.

You need a Paid Account to view this document. Click here to change your account type.

Your account does not support viewing this document.

Set your membership status to view this document.

With a Docket Alarm membership, you'll get a whole lot more, including:

  • Up-to-date information for this case.
  • Email alerts whenever there is an update.
  • Full text search for other cases.
  • Get email alerts whenever a new case matches your search.

Become a Member

One Moment Please

The filing “” is large (MB) and is being downloaded.

Please refresh this page in a few minutes to see if the filing has been downloaded. The filing will also be emailed to you when the download completes.

Your document is on its way!

If you do not receive the document in five minutes, contact support at support@docketalarm.com.

Sealed Document

We are unable to display this document, it may be under a court ordered seal.

If you have proper credentials to access the file, you may proceed directly to the court's system using your government issued username and password.


Access Government Site

We are redirecting you
to a mobile optimized page.





Document Unreadable or Corrupt

Refresh this Document
Go to the Docket

We are unable to display this document.

Refresh this Document
Go to the Docket