ANSI/ASHRAE Standard 15-2013
`(Supersedes ANSI/ASHRAE Standard 15-2010)
`Includes ANSI/ASHRAE addenda listed in Appendix F
`
`Safety Standard for
`Refrigeration Systems
`
`See Appendix F for approval dates by the ASHRAE Standards Committee, the ASHRAE Board of Directors, and the American
`National Standards Institute.
`
`This standard is under continuous maintenance by a Standing Standard Project Committee (SSPC) for which the Standards Com-
`mittee has established a documented program for regular publication of addenda or revisions, including procedures for timely,
`documented, consensus action on requests for change to any part of the standard. The change submittal form, instructions, and
`deadlines may be obtained in electronic form from the ASHRAE website (www.ashrae.org) or in paper form from the Manager of
`Standards. The latest edition of an ASHRAE Standard may be purchased from the ASHRAE website (www.ashrae.org) or from
`ASHRAE Customer Service, 1791 Tullie Circle, NE, Atlanta, GA 30329-2305. E-mail: orders@ashrae.org. Fax: 678-539-2129.
`Telephone: 404-636-8400 (worldwide), or toll free 1-800-527-4723 (for orders in US and Canada). For reprint permission, go to
`www.ashrae.org/permissions.
`
`© 2013 ASHRAE ISSN 1041-2336
`
`p
`
`
`
`
`
`
`
`
`
`
`
`6
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
` N
`
` p
`
`
`
`b
`
` p
`
` D
`
`b
`
`
`
`
`
` b
`
`
`
`
`
`
`
`
`
`Arkema Exhibit 1110
`
`1 of 82
`
`

`
`ASHRAE Standing Standard Project Committee 15
`Cognizant TCs: TC 10.1, Custom Engineered Refrigeration Systems,
`and TC 9.1, Large Building Air-Conditioning Systems
`SPLS Liaison: Mark P. Modera
`Staff Liaison: Douglas K. Tucker
`
`Dennis R. Dorman, Chair
`Martin L. Timm, Vice Chair
`Gregory A. Scrivener, Secretary
`A. Bruce Badger
`Els Baert
`Wayne K. Borrowman
`James M. Calm
`Jim Caylor
`
`Paul L. Doppel
`Stephen W. Duda
`Danny M. Halel
`Phillip A. Johnson
`Jay A. Kohler
`C. Dominic Kolandayan
`Scott M. MacBain, Sr.
`Chun-cheng Piao
`
`ASHRAE STANDARDS COMMITTEE 2013–2014
`
`William F. Walter, Chair
`Richard L. Hall, Vice-Chair
`Karim Amrane
`Joseph R. Anderson
`James Dale Aswegan
`Charles S. Barnaby
`Steven F. Bruning
`John A. Clark
`Waller S. Clements
`
`David R. Conover
`John F. Dunlap
`James W. Earley, Jr.
`Steven J. Emmerich
`Julie M. Ferguson
`Krishnan Gowri
`Cecily M. Grzywacz
`Rita M. Harrold
`Adam W. Hinge
`Debra H. Kennoy
`
`Stephanie C. Reiniche, Manager of Standards
`
`Douglas T. Reindl
`Brian J. Rodgers
`Jeffrey M. Shapiro
`Eric M. Smith
`Ganesan Sundaresan
`Russell C. Tharp
`Ronald P. Vallort
`John I. Vucci
`Kyle D. Wessells
`
`Malcolm D. Knight
`Rick A. Larson
`Mark P. Modera
`Cyrus H. Nasseri
`Janice C. Peterson
`Heather L. Platt
`Douglas T. Reindl
`Julia A. Keen, BOD ExO
`Thomas E. Werkema, Jr., CO
`
`SPECIAL NOTE
`This American National Standard (ANS) is a national voluntary consensus standard developed under the auspices of ASHRAE.
`Consensus is defined by the American National Standards Institute (ANSI), of which ASHRAE is a member and which has approved this
`standard as an ANS, as “substantial agreement reached by directly and materially affected interest categories. This signifies the concurrence
`of more than a simple majority, but not necessarily unanimity. Consensus requires that all views and objections be considered, and that an
`effort be made toward their resolution.” Compliance with this standard is voluntary until and unless a legal jurisdiction makes compliance
`mandatory through legislation.
`ASHRAE obtains consensus through participation of its national and international members, associated societies, and public review.
`ASHRAE Standards are prepared by a Project Committee appointed specifically for the purpose of writing the Standard. The Project
`Committee Chair and Vice-Chair must be members of ASHRAE; while other committee members may or may not be ASHRAE members, all
`must be technically qualified in the subject area of the Standard. Every effort is made to balance the concerned interests on all Project
`Committees.
`The Manager of Standards of ASHRAE should be contacted for:
`a. interpretation of the contents of this Standard,
`b. participation in the next review of the Standard,
`c. offering constructive criticism for improving the Standard, or
`d. permission to reprint portions of the Standard.
`
`DISCLAIMER
`ASHRAE uses its best efforts to promulgate Standards and Guidelines for the benefit of the public in light of available information and
`accepted industry practices. However, ASHRAE does not guarantee, certify, or assure the safety or performance of any products, components,
`or systems tested, installed, or operated in accordance with ASHRAE’s Standards or Guidelines or that any tests conducted under its
`Standards or Guidelines will be nonhazardous or free from risk.
`
`ASHRAE INDUSTRIAL ADVERTISING POLICY ON STANDARDS
`ASHRAE Standards and Guidelines are established to assist industry and the public by offering a uniform method of testing for rating
`purposes, by suggesting safe practices in designing and installing equipment, by providing proper definitions of this equipment, and by providing
`other information that may serve to guide the industry. The creation of ASHRAE Standards and Guidelines is determined by the need for them,
`and conformance to them is completely voluntary.
`In referring to this Standard or Guideline and in marking of equipment and in advertising, no claim shall be made, either stated or implied,
`that the product has been approved by ASHRAE.
`
`© ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution,
`or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
`
`p
`
`
`
`
`
`
`
`
`
`
`
`6
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
` N
`
` p
`
`
`
`b
`
` p
`
` D
`
`b
`
`
`
`
`
` b
`
`
`
`
`
`
`
`
`
`2 of 82
`
`

`
`CONTENTS
`ANSI/ASHRAE Standard 15-2013,
`Safety Standard for Refrigeration Systems
`
`PAGE
`SECTION
`Foreword .....................................................................................................................................................................2
`1 Purpose.............................................................................................................................................................3
`2 Scope ................................................................................................................................................................3
`3 Definitions .........................................................................................................................................................3
`4 Occupancy Classification ..................................................................................................................................5
`5 Refrigerating System Classification ..................................................................................................................6
`6 Refrigerant Safety Classification .......................................................................................................................7
`7 Restrictions on Refrigerant Use ........................................................................................................................7
`8 Installation Restrictions .....................................................................................................................................9
`9 Design and Construction of Equipment and Systems.....................................................................................11
`10 Operation and Testing .....................................................................................................................................22
`11 General Requirements ....................................................................................................................................22
`12 Precedence with Conflicting Requirements.....................................................................................................23
`13 Listed Equipment.............................................................................................................................................23
`Informative Appendix A—Informative References ................................................................................................24
`
`Normative Appendix B—Normative References ...................................................................................................24
`
`Informative Appendix C—Method for Calculating Discharge Capacity of
`Positive Displacement Compressor Pressure-Relief Device .............................................................25
`
`Normative Appendix D—Allowable Equivalent Length of Discharge Piping .........................................................27
`
`Informative Appendix E—Emergencies in Refrigerating Machinery Rooms .........................................................28
`
`Informative Appendix F—Addenda Description Information .................................................................................30
`
`Approved addenda, errata, or interpretations for this standard can be downloaded free of charge from the ASHRAE
`Web site at www.ashrae.org/technology.
`
`NOTE
`
`© 2013 ASHRAE
`1791 Tullie Circle NE · Atlanta, GA 30329 · www.ashrae.org · All rights reserved.
`ASHRAE is a registered trademark of the American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
`ANSI is a registered trademark of the American National Standards Institute.
`
`© ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution,
`or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
`
`p
`
`
`
`
`
`
`
`
`
`
`
`6
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
` N
`
` p
`
`
`
`b
`
` p
`
` D
`
`b
`
`
`
`
`
` b
`
`
`
`
`
`
`
`
`
`3 of 82
`
`

`
`(This foreword is not part of this standard. It is merely
`informative and does not contain requirements necessary
`for conformance to the standard. It has not been pro-
`cessed according to the ANSI requirements for a standard
`and may contain material that has not been subject to
`public review or a consensus process. Unresolved objec-
`tors on informative material are not offered the right to
`appeal at ASHRAE or ANSI.)
`
`FOREWORD
`ASHRAE Standard 15-2013 is the most recent edition of
`one of ASHRAE’s oldest standards. Standard 15 is under con-
`tinuous maintenance, which means it is modified and updated
`based on feedback from users, changes in the science originat-
`ing from ASHRAE and industry research, and industry changes
`that respond to the global interest in improved environmental
`responsibility. Interested parties can recommend changes to the
`standard by submitting a change proposal using the continuous
`maintenance form included in the back of the standard. Stan-
`dard 15-2013 includes all of the published addenda to the 2010
`version as shown in Informative Appendix F.
`ASHRAE Standard 15 must be used with its sister stan-
`dard, ANSI/ASHRAE Standard 34, Designation and Safety
`Classification of Refrigerants.1 Standard 34 prescribes the
`Refrigerant Classification System, as well as refrigerant con-
`centration limits (RCL), that are vitally important in applying
`this standard. Although changes to Standard 15 are closely
`coordinated with those to Standard 34, users of Standard 15
`should also review the most recent version of Standard 34 and
`its associated addenda for the latest information related to
`refrigerant designations and safety classifications.
`ASHRAE Standard 15 gives a method for determining the
`amount of refrigerant in a given space that, when exceeded,
`requires a machinery room. When a refrigerant is not classi-
`fied in ASHRAE Standard 34 or its addenda, it is the respon-
`sibility of the owner of a refrigerating system to make this
`judgment.
`Users of ASHRAE Standard 15 may also find it useful to
`refer to the Standard 15-2001 User’s Manual. The user’s man-
`ual was developed as a companion document to ASHRAE
`Standard 15. Though it does not reflect the addenda and
`changes incorporated into Standard 15 since its original pub-
`lication, it still serves to clarify the intent of the standard and
`provides an explanation of the rationale behind its creation.
`Its purpose is to assist in use of the standard by including
`illustrations and examples of accepted industry practice, as
`well as explanations of and supporting references for formu-
`las in the standard. The user’s manual also covers building,
`system, and refrigerant classifications, restrictions on refrig-
`erant use, installation restrictions, and equipment and system
`design and construction for commercial, residential, and
`industrial applications.
`ASHRAE Standard 15 is directed toward the safety of
`persons and property on or near the premises where refriger-
`ation facilities are located. It includes specifications for fabri-
`cation of refrigerating systems but does not address the effects
`of refrigerant emissions on the environment. For information
`on the environmental effects of refrigerant emissions, see
`
`ANSI/ASHRAE Standard 147, Reducing the Release of Halo-
`genated Refrigerants from Refrigerating and Air-Condition-
`ing Equipment and Systems.2
`The hazards of refrigerants are related to their physical
`and chemical characteristics as well as to the pressures and
`temperatures that occur in refrigerating and air-conditioning
`systems. Personal injury and property damage from inadequate
`precautions may occur from a number of origins, such as
`
`(cid:129)
`(cid:129)
`
`(cid:129)
`
`rupture of a part with risk from flying debris;
`release of refrigerant from a fracture, due to a leaking
`seal or incorrect operation; or
`fire resulting from or intensified by burning or deflagra-
`tion of escaping refrigerant or lubricant.
`
`Personal injury resulting from the accidental release of
`refrigerants may also occur from
`
`(cid:129)
`
`(cid:129)
`(cid:129)
`
`(cid:129)
`(cid:129)
`
`suffocation from heavier-than-air refrigerants in inade-
`quately ventilated spaces;
`narcotic and cardiac sensitization effects;
`toxic effects of vapor or the decomposition products due
`to vapor contact with flames or hot surfaces;
`corrosive attack on the eyes, skin, or other tissue; or
`freezing of tissue by contact with liquid.
`
`Care should be taken to avoid stagnant pockets of refrig-
`erant vapors by properly locating ventilation supply air inlets
`and exhaust outlets. All commonly used refrigerants, except
`ammonia (R-717) and water (R-718), are heavier than air.
`Leaked refrigerant vapor will concentrate near the floor if
`undisturbed. Floor-level exhaust-air outlets are appropriate
`for heavier-than-air refrigerants. The user’s manual may pro-
`vide useful guidance for the design of ventilation systems and
`the location of supply air inlets and exhaust outlets.
`The following short publishing history of this code traces
`the origins of these safety provisions. In 1919, the American
`Society of Refrigerating Engineers (ASRE) proposed a Tenta-
`tive Code for the Regulation of Refrigerating Machines and
`Refrigerants. Over the next 11 years, representatives from the
`American Gas Association, American Institute of Electrical
`Engineers, American Institute of Refrigeration, American
`Chemical Society, American Society of Heating and Ventila-
`tion Engineers, American Society of Mechanical Engineers,
`National Electrical Refrigerator Manufacturers Association,
`National Fire Protection Association, and ASRE met to expand
`the code to address all of the issues raised on the use of refrig-
`eration equipment. The first Safety Code for Mechanical
`Refrigeration, recognized as American Standard B9 in Octo-
`ber 1930, appeared in the first edition, 1932–1933, of the
`ASRE Refrigerating Handbook and Catalog. ASRE revisions
`designated ASA B9 appeared in 1933 and 1939. ASRE revi-
`sions designated ASA B9.1 appeared in 1950, 1953, and 1958.
`After the formation of ASHRAE, editions appeared as ASA
`B9.1-1964, ANSI B9.1-1971, ANSI/ASHRAE 15-1978, ANSI/
`ASHRAE 15-1989, ANSI/ASHRAE 15-1992, ANSI/ASHRAE
`15-1994, ANSI/ASHRAE 15-2001, ANSI/ASHRAE 15-2004,
`ANSI/ASHRAE 15-2007, and ANSI/ASHRAE 15-2010.
`
`2
`
`ANSI/ASHRAE Standard 15-2013
`
`© ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution,
`or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
`
`p
`
`
`
`
`
`
`
`
`
`
`
`6
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
` N
`
` p
`
`
`
`b
`
` p
`
` D
`
`b
`
`
`
`
`
` b
`
`
`
`
`
`
`
`
`
`4 of 82
`
`

`
`1. PURPOSE
`This standard specifies safe design, construction, installa-
`tion, and operation of refrigeration systems.
`
`2. SCOPE
`2.1 This standard establishes safeguards for life, limb, health,
`and property and prescribes safety requirements.
`2.2 This standard applies to
`
`a.
`
`the design, construction, test, installation, operation, and
`inspection of mechanical and absorption refrigeration sys-
`tems,
`including heat-pump systems used in stationary
`applications;
`b. modifications, including replacement of parts or compo-
`nents if they are not identical in function and capacity; and
`substitutions of refrigerant having a different designa-
`tion.
`
`c.
`
`3. DEFINITIONS
`administrative control: the use of human action aimed at
`achieving a safe level of performance from a system or sub-
`system. Compare to engineering control.
`approved: acceptable to the authority having jurisdiction
`(AHJ).
`approved, nationally recognized laboratory: a laboratory that
`is acceptable to the AHJ and provides uniform testing and
`examination procedures and standards for meeting design,
`manufacturing, and factory testing requirements of this code;
`is organized, equipped, and qualified for testing; and has a
`follow-up inspection service of the current production of the
`listed products.
`back pressure: the static pressure existing at the outlet of an
`operating pressure-relief device due to pressure in the dis-
`charge line.
`balanced relief valve: a pressure-relief valve that incorpo-
`rates means of minimizing the effect of back pressure on the
`operational characteristics of the valve (opening pressure,
`closing pressure, and relieving capacity).
`blends: refrigerants consisting of mixtures of two or more
`different chemical compounds, often used individually as
`refrigerants for other applications.
`brazed joint: a gas-tight joint obtained by the joining of metal
`parts with metallic mixtures or alloys that melt at tempera-
`tures above 1000°F (537°C) but less than the melting temper-
`atures of the joined parts.
`cascade refrigerating system: a refrigerating system having
`two or more refrigerant circuits, each with a pressure-impos-
`ing element, a condenser, and an evaporator, where the evapo-
`rator of one circuit absorbs the heat rejected by another (lower-
`temperature) circuit.
`companion or block valves: pairs of mating stop valves that
`allow sections of a system to be joined before opening these
`valves or separated after closing them.
`compound refrigerating system: a multistage refrigerating
`system in which a single charge of refrigerant circulates
`
`through all stages of compression. See multistage refrigerat-
`ing system.
`compressor: a machine used to compress refrigerant vapor.
`compressor unit: a compressor with its prime mover and
`accessories.
`condenser: that part of the refrigerating system where refrig-
`erant is liquefied by the removal of heat.
`condenser coil: a condenser constructed of pipe or tubing, not
`enclosed in a pressure vessel.
`condensing unit: a combination of one or more power-driven
`compressors, condensers, liquid receivers (when required),
`and regularly furnished accessories.
`containers, refrigerant: a cylinder for the transportation of
`refrigerant.
`corridor: an enclosed passageway that limits travel to a single
`path.
`critical pressure, critical temperature, and critical volume:
`a point on the saturation curve where the refrigerant liquid
`and vapor have identical volume, density, and enthalpy and
`there is no latent heat.
`design pressure: the maximum gage pressure for which a
`specific part of a refrigerating system is designed.
`two pressure-relief devices
`dual pressure-relief device:
`mounted on a three-way valve that allows one device to
`remain active while the other is isolated.
`duct: a tube or conduit used to convey or encase.
`air duct: a tube or conduit used to convey air (air pas-
`sages in self-contained systems are not air ducts).
`pipe duct: a tube or conduit used to encase pipe or tubing.
`engineering control: the use of sensors, actuators, and other
`equipment to achieve a safe level of performance from a sys-
`tem or subsystem without the aid of human interaction. Com-
`pare to administrative control.
`evaporator: that part of the refrigerating system designed to
`vaporize liquid refrigerant to produce refrigeration.
`evaporator coil: an evaporator constructed of pipe or tubing,
`not enclosed in a pressure vessel.
`fusible plug: a plug containing an alloy that will melt at a
`specified temperature and relieve pressure.
`header: a pipe or tube (extruded, cast, or fabricated) to which
`other pipes or tubes are connected.
`heat pump: a refrigerating system used to transfer heat into a
`space or substance.
`highside: those portions of the refrigerating system that are
`subject to approximate condensing pressure.
`horsepower: the power delivered from the prime mover to the
`compressor of a refrigerating system.
`immediately dangerous to life or health (IDLH): the maxi-
`mum concentration from which unprotected persons are able
`to escape within 30 minutes without escape-impairing symp-
`toms or irreversible health effects.1
`
`ANSI/ASHRAE Standard 15-2013
`
`3
`
`© ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution,
`or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
`
`p
`
`
`
`
`
`
`
`
`
`
`
`6
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
` N
`
` p
`
`
`
`b
`
` p
`
` D
`
`b
`
`
`
`
`
` b
`
`
`
`
`
`
`
`
`
`5 of 82
`
`

`
`informative appendix: an appendix that is not part of the
`standard but is included for information only.
`
`inside dimension: inside diameter, width, height, or cross-
`sectional diagonal.
`
`internal gross volume: the volume as determined from inter-
`nal dimensions of the container with no allowance for the vol-
`ume of internal parts.
`
`limited charge system: a system in which, with the compres-
`sor idle, the design pressure will not be exceeded when the
`refrigerant charge has completely evaporated.
`
`liquid receiver: a vessel, permanently connected to a refriger-
`ating system by inlet and outlet pipes, for storage of liquid
`refrigerant.
`
`listed: equipment or materials included in a list published by
`an approved, nationally recognized testing laboratory, inspec-
`tion agency, or other organization concerned with product
`evaluation that maintains periodic inspection of production of
`listed equipment or materials and whose listing states either
`that the equipment or material meets nationally recognized
`standards or has been tested and found suitable for use in a
`specified manner.
`
`lithium bromide/water absorption system: an absorption sys-
`tem where water (R-718) is the refrigerant and lithium bro-
`mide (LiBr) is the absorbent.
`
`lobby: a waiting room or large hallway serving as a waiting
`room.
`
`lower flammability limit (LFL): the minimum concentration
`of the refrigerant that propagates a flame through a homoge-
`neous mixture of refrigerant and air.
`
`lowside: the portion of a refrigerating system that is subjected
`to approximate evaporator pressure.
`
`machinery: the refrigerating equipment forming a part of the
`refrigerating system, including, but not limited to, any or all
`of the following: compressor, condenser,
`liquid receiver,
`evaporator, and connecting piping.
`
`machinery room: a space, meeting the requirements of Sec-
`tions 8.11 and 8.12, that is designed to house compressors and
`pressure vessels.
`
`manufacturer: the company or organization that evidences
`its responsibility by affixing its name, trademark, or trade
`name to refrigerating equipment.
`
`means of egress: a continuous and unobstructed path of travel
`from any point in a building or structure to a public way.
`
`mechanical joint: a gas-tight joint obtained by joining metal
`parts with a positive-holding mechanical construction such as
`flanged, screwed, or flared joints or compression fittings.
`
`multistage refrigerating system: a refrigerating system in
`which compression of refrigerant is carried out in two or more
`steps.
`
`nonpositive displacement compressor: a compressor in which
`the increase in vapor pressure is attained without changing the
`internal volume of the compression chamber.
`
`normative appendix: an appendix including integral parts of
`the mandatory requirements of the standard, which, for rea-
`sons of convenience, are placed after all other normative ele-
`ments.
`occupancy: for class of occupancy, see Section 4.
`occupied space: that portion of the premises accessible to or
`occupied by people, excluding machinery rooms.
`pilot-operated relief valve: a pressure-relief valve in which
`the major relieving device is combined with and is controlled
`by a self-actuated auxiliary pressure-relief valve.
`piping: the pipe or tube used to convey fluid from one part of
`a refrigeration system to another. Piping includes pipe,
`flanges, bolting, gaskets, valves, fittings, pipe-supporting fix-
`tures, structural attachments, and the pressure-containing
`parts of other components, such as expansion joints, strainers,
`filters, and devices that serve such purposes as mixing, sepa-
`rating, muffling, snubbing, distributing, metering, or control-
`ling flow.
`positive displacement compressor: a compressor in which the
`increase in pressure is attained by changing the internal vol-
`ume of the compression chamber.
`premises: a tract of land and the buildings thereon.
`pressure-imposing element: any device or portion of the
`equipment used to increase refrigerant pressure.
`pressure-limiting device: a pressure-responsive electronic or
`mechanical control designed to automatically stop the opera-
`tion of the pressure-imposing element at a predetermined pres-
`sure.
`pressure-relief device: a pressure- (not temperature-) actu-
`ated valve or rupture member designed to automatically
`relieve pressure in excess of its setting.
`pressure-relief valve: a pressure-actuated valve held closed
`by a spring or other means and designed to automatically
`relieve pressure in excess of its setting.
`pressure vessel: any refrigerant-containing receptacle in a
`refrigerating system. This does not include evaporators where
`each separate evaporator section does not exceed 0.5 ft3
`(0.014 m3) of refrigerant-containing volume, regardless of the
`maximum inside dimension. This also does not include evap-
`orator coils, compressors, condenser coils, controls, headers,
`pumps, and piping.
`pumpdown charge: the quantity of refrigerant stored at some
`point in the refrigeration system for operational, service, or
`standby purposes.
`reclaimed refrigerants: refrigerants reprocessed to the same
`specifications as new refrigerants by any means, including
`distillation. Such refrigerants have been chemically analyzed
`to verify that those specifications have been met.
`recovered refrigerants: refrigerants removed from a system
`in any condition without necessarily testing or processing
`them.
`recycled refrigerants: refrigerants for which contaminants
`have been reduced by oil separation, removal of noncondens-
`able gases, and single or multiple passes through filter driers
`
`4
`
`ANSI/ASHRAE Standard 15-2013
`
`© ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution,
`or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
`
`p
`
`
`
`
`
`
`
`
`
`
`
`6
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
` N
`
` p
`
`
`
`b
`
` p
`
` D
`
`b
`
`
`
`
`
` b
`
`
`
`
`
`
`
`
`
`6 of 82
`
`

`
`or other devices that reduce moisture, acidity, and particulate
`matter.
`
`refrigerant: the fluid used for heat transfer in a refrigerating
`system; the refrigerant absorbs heat and transfers it at a higher
`temperature and a higher pressure, usually with a change of
`state.
`
`refrigerant concentration limit (RCL): the refrigerant con-
`centration limit in air, determined in accordance with ANSI/
`ASHRAE Standard 341and intended to reduce the risks of
`acute toxicity, asphyxiation, and flammability hazards in nor-
`mally occupied, enclosed spaces.
`
`refrigerant detector: a device that is capable of sensing the
`presence of refrigerant vapor.
`
`refrigerating system: a combination of interconnected parts
`forming a closed circuit in which refrigerant is circulated for
`the purpose of extracting, then rejecting, heat. (See Section 5
`for classification of refrigerating systems by type.)
`
`refrigerating system classification: refrigerating systems are
`classified according to the degree of probability, low or high,
`that leaked refrigerant from a failed connection, seal, or com-
`ponent could enter an occupied area. The distinction is based
`on the basic design or location of the components. (See Sec-
`tion 5 for classification of refrigerating systems by type.)
`
`refrigerating system, direct: see Section 5.1.1.
`
`refrigerating system, indirect: see Section 5.1.2.
`
`rupture member: a device that will rupture and release refrig-
`erant to relieve pressure.
`
`saturation pressure: the pressure at which vapor and liquid
`exist in equilibrium at a given temperature.
`
`sealed ammonia/water absorption system: an absorption sys-
`tem where ammonia (R-717) is the refrigerant and water (R-
`718) is the absorbent and all refrigerant-containing parts are
`made permanently tight by welding or brazing.
`
`secondary coolant: any liquid used for the transmission of
`heat, without vaporization.
`
`self-contained system: a complete, factory-assembled and
`factory-tested system that is shipped in one or more sections
`and has no refrigerant-containing parts that are joined in the
`field by other than companion or block valves.
`
`set pressure: the pressure at which a pressure-relief device or
`pressure control is set to operate.
`
`shall (shall not): used in this standard when a provision is (or
`is not) mandatory.
`
`soldered joint: a gas-tight joint formed by joining metal parts
`with alloys that melt at temperatures not exceeding 800°F
`(426.5°C) and above 400°F (204.5°C).
`
`specified: explicitly stated in detail. Specified limits or pre-
`scriptions are mandatory.
`
`stop valve: a device used to shut off the flow of refrigerant.
`
`three-way valve: a service valve for dual pressure-relief
`devices that allows using one device while isolating the other
`from the system, maintaining one valve in operation at all
`times.
`threshold limit value time-weighted average (TLV-TWA†):
`the refrigerant concentration in air for a normal eight-hour
`workday and a 40-hour workweek to which repeated expo-
`sure, day after day, will not cause an adverse effect in most
`persons.
`
`ultimate strength: the stress at which rupture occurs.
`
`unit system: see self-contained system.
`
`unprotected tubing: tubing that is unenclosed and therefore
`exposed to crushing, abrasion, puncture, or similar damage
`after installation.
`
`zeotropic: refers to blends comprising multiple components
`of different volatility that, when used in refrigeration cycles,
`change volumetric composition and saturation temperatures
`as they evaporate (boil) or condense at constant pressure. The
`word is derived from the Greek words zein (to boil) and tro-
`pos (to change).
`
`4. OCCUPANCY CLASSIFICATION
`
`4.1 Locations of refrigerating systems are described by occu-
`pancy classifications that consider the ability of people to
`respond to potential exposure to refrigerant as follows.
`4.1.1 Institutional occupancy is a premise or that portion of
`a premise from which, because they are disabled, debilitated,
`or confined, occupants cannot readily leave without the assis-
`tance of others. Institutional occupancies include, among oth-
`ers, hospitals, nursing homes, asylums, and spaces containing
`locked cells.
`4.1.2 Public assembly occupancy is a premise or that por-
`tion of a premise where large numbers of people congregate
`and from which occupants cannot quickly vacate the space.
`Public assembly occupancies include, among others, auditori-
`ums, ballrooms, classrooms, passenger depots, restaurants,
`and theaters.
`4.1.3 Residential occupancy is a premise or that portion of
`a premise that provides the occupants with complete indepen-
`dent living facilities, including permanent provisions for liv-
`ing, sleeping, eating, cooking, and sanitation. Residential
`occupancies include, among others, dormitories, hotels,
`multi-unit apartments, and private residences.
`4.1.4 Commercial occupancy is a premise or that portion of
`a premise where people transact business, receive personal
`service, or purchase food and other goods. Commercial occu-
`pancies include, among others, office and professional build-
`ings, markets (but not large mercantile occupancies), and
`work or storage areas that do not qualify as industrial occu-
`pancies

This document is available on Docket Alarm but you must sign up to view it.


Or .

Accessing this document will incur an additional charge of $.

After purchase, you can access this document again without charge.

Accept $ Charge
throbber

Still Working On It

This document is taking longer than usual to download. This can happen if we need to contact the court directly to obtain the document and their servers are running slowly.

Give it another minute or two to complete, and then try the refresh button.

throbber

A few More Minutes ... Still Working

It can take up to 5 minutes for us to download a document if the court servers are running slowly.

Thank you for your continued patience.

This document could not be displayed.

We could not find this document within its docket. Please go back to the docket page and check the link. If that does not work, go back to the docket and refresh it to pull the newest information.

Your account does not support viewing this document.

You need a Paid Account to view this document. Click here to change your account type.

Your account does not support viewing this document.

Set your membership status to view this document.

With a Docket Alarm membership, you'll get a whole lot more, including:

  • Up-to-date information for this case.
  • Email alerts whenever there is an update.
  • Full text search for other cases.
  • Get email alerts whenever a new case matches your search.

Become a Member

One Moment Please

The filing “” is large (MB) and is being downloaded.

Please refresh this page in a few minutes to see if the filing has been downloaded. The filing will also be emailed to you when the download completes.

Your document is on its way!

If you do not receive the document in five minutes, contact support at support@docketalarm.com.

Sealed Document

We are unable to display this document, it may be under a court ordered seal.

If you have proper credentials to access the file, you may proceed directly to the court's system using your government issued username and password.


Access Government Site

We are redirecting you
to a mobile optimized page.





Document Unreadable or Corrupt

Refresh this Document
Go to the Docket

We are unable to display this document.

Refresh this Document
Go to the Docket