throbber
Downloaded from SAE International by Bianca Hamilton, Friday, December 18, 2015
`
`2013-01-1496
`Published 04/08/2013
`Copyright © 2013 SAE International
`doi:10 4271/2013-01-1496
`saepcmech saejournals org
`
`Refrigerant and Lubricant Distribution in MAC System
`Shenghan Jin and Pega Hrnjak
`Creative Thermal Solutions and ACRC,UIUC
`
`ABSTRACT
`This paper presents experimental results for refrigerant and lubricant mass distribution in a typical automotive A/C
`(MAC) system.
`Experiments were conducted by closing valves located at the inlet and outlet of each component after reaching steady
`state, isolating the refrigerant and lubricant in each component. Refrigerant mass is recovered in a separate vessel using
`liquid nitrogen to reduce refrigerant vapor pressure to near vacuum. The overall weight is determined within ±1% after the
`separation of refrigerant and lubricant. The mass of lubricant is determined by using three different techniques: Remove
`and Weigh, Mix and Sample, and Flushing. The total mass of lubricant in the system is determined with ±2.5% uncertainty
`on average. R134a and R1234yf are used with PAG 46 oil as working fluid at different Oil Circulation Ratio (OCR),
`ranging from 2% to 4%. Experiments are conducted in two standard testing conditions: I35 and L35 (SAE Standard J2765)
`[11].
`R134a and R1234yf exhibit similar results in terms of refrigerant and lubricant retention. Higher mass flow rate does
`not significantly change the refrigerant distribution, but a lower lubricant retention in the evaporator is observed. It is
`found that only about a quarter of the total mass of lubricant resides in the compressor.
`
`CITATION: Jin, S. and Hrnjak, P., "Refrigerant and Lubricant Distribution in MAC System," SAE Int. J. Passeng. Cars -
`Mech. Syst. 6(2):2013, doi:10.4271/2013-01-1496.
`____________________________________
`
`INTRODUCTION
`In a vapor compression refrigeration system oil is crucial
`to provide sealing and lubricating for the compressor. In an
`automotive A/C system where an oil separator is integrated
`into the compressor if at all present, oil is inevitably mixed
`with refrigerant and travels throughout the system due to a
`separation efficiency of less than 1. The circulating oil
`appears in the form of mist, droplets, a thin oil rich film, or a
`fairly homogeneous liquid mixture with refrigerant depending
`on its location and the system configuration. The presence of
`oil can significantly change the properties of the working
`fluid, degrade heat transfer, and increase pressure drop. A
`large amount of oil retention outside the compressor can
`cause compressor failure due to insufficient lubrication. As a
`result, the amount of oil in circulation and oil retention has a
`direct influence on the system performance and compressor
`reliability [14].
`In the literature, experimental techniques used to measure
`a refrigerant and lubricant mass inventory can be grouped by
`whether the method is intrusive or not. By using the intrusive
`method, Hoehne and Hrnjak [1] were able to measure
`refrigerant mass in less than 0.1 g uncertainty in each section
`of a low charge (<150g) hydrocarbon (propane) refrigerant
`
`system. Peuker and Hrnjak [2] measured refrigerant mass
`distribution in an automotive A/C system with orifice tube
`(OT) and low side accumulator in transient and steady state.
`A measurement uncertainty of 0.4%
`regarding
`total
`refrigerant mass was achieved by using liquid nitrogen as the
`recovery coolant. Björk [3] used an expansion tank where
`refrigerant can reach a superheat thermodynamic equilibrium.
`Using the p-v-T relationship and internal volume, refrigerant
`mass can be calculated. According to the comparison, the
`difference between Peuker's and Björk's procedures is small,
`ranging from 1% to 5%. The non-intrusive measuring
`technique, also known as On-Line Measuring Technique,
`weighs a section directly while the system is still running.
`According to Miller's [4] result on a 3-ton R22 split-system
`air-to-air heat pump, the accuracy for the weighing system is
`about 0.05 kg.
`Various authors have reported lubricant retention results
`using intrusive measuring technique. Crompton et al [5]
`employed a Remove and Weigh technique to investigate oil
`retention in smooth and micro-fin tubes. Similar to the
`intrusive method mentioned previously for refrigerant, valves
`at both ends of
`the section of
`interest were closed
`simultaneously. After refrigerant was slowly released, the
`section was removed from the test loop and weighed so that
`
`1013
`
`Page 1 of 8
`
`Arkema Exhibit 1102
`
`

`
`Downloaded from SAE International by Bianca Hamilton, Friday, December 18, 2015
`
`Jin et al / SAE Int. J. Passeng. Cars - Mech. Syst. / Volume 6, Issue 2(July 2013)
`
`oil retention is determined. The average uncertainty was
`4.9%. Zoellick and Hrnjak [6] and Sethi and Hrnjak [7]
`employed a similar method to measure oil retention in suction
`lines. The uncertainties reported by the two authors were
`0.5% and 2%, respectively. Except for remove and weigh
`technique, Peuker and Hrnjak [2] developed Flushing
`technique and Mix and Sample technique. Using these three
`methods, Peuker and Hrnjak [2] were able to determine oil
`amount totals within 2%. As for the non-intrusive method,
`Lee [8] used an injection-extraction method to investigate oil
`retention in a vertical suction line. Oil was injected at the
`bottom of a pure refrigerant suction line and was separated at
`the top by using oil separators. The oil retention was the
`difference between mass of oil injected and that of oil
`extracted. This method was later used to measure oil retention
`in each part of a CO2/PAG 46 A/C system by Lee [9] in 2003
`and that of a residential A/C system by Cremaschi [10] in
`2004. Cremaschi [10] estimated 12% relative error.
`EXPERIMENT SETUP
`In the facility the system components are located at the
`same relative heights as they are in the original vehicle. The
`compressor is a piston-cylinder reciprocating compressor
`with fixed displacement. No oil separator is installed. A
`micro-channel condenser with 48 tubes and a plate and fin
`evaporator with 19 plates are used in the facility, as shown in
`Figure 3 and 4. The condenser does not have a separate pass
`for subcooling. An external receiver is installed after the
`condenser, with an internal diameter of 13.08 mm and a
`length of 560 mm. A thermal expansion valve (TXV) is used
`as throttling device. The schematic of the facility and details
`of the system and components is shown in Figure 1 and 2.
`Due to the large size of the environment chambers, longer
`tubes than in the real system are used to connect the
`components. As a result, the experimental system volume is
`larger than original system and the largest difference in
`tubing length is from condenser to evaporator, or liquid line.
`Two methods are used to measure the system volume: one
`is based on combining the volume calculated from tube
`geometry with the internal volumes of components provided
`by manufacturers; the second is to charge a known amount of
`gas and calculate volume based on density, also referred to as
`the isothermal gas method.
`To avoid the diffusion of gas, lubricant is removed from
`the system by flushing with soluble refrigerant before using
`the isothermal gas method. Each section is then evacuated
`and charged with a certain amount of the designated gas, the
`weight of which is measured by the scale. Gas with higher
`density is preferred since the scale will have better accuracy
`if the charged mass is larger. Carbon dioxide, with a stated
`purity of 99.9% as supplied, is selected. Equilibrium
`temperature and pressure are measured to calculate density
`and the saturation temperature is also calculated to make sure
`the gas is superheated.
`
`The internal volumes calculated using two methods agree
`with each other, as shown in Table 1. The isothermal gas
`method has a consistent but slightly larger value than
`geometrical method as expected, due to the “inactive
`volume” such as pressure taps and charge ports. Since the
`inactive volume can hold refrigerant mass as well, the values
`of isothermal gas method are used.
`The operation condition is mainly focused on idle
`condition, i.e. minimum compressor speed. So the I35-dry
`condition from SAE J2765 [11] is investigated as the design
`condition. Charge tests are performed at this condition to
`determine the refrigerant charge for maximized COP for both
`R134a and R1234yf. The same type of lubricant (PAG 46) is
`used in all tests but varying charge amounts are employed to
`change the OCR. Since the lubricant used in this study is
`essentially oil, the term “lubricant” and “oil” are used
`interchangeably. The system is also operated at higher
`compressor speeds (L35) to investigate the effect of higher
`mass flux.
`
`Figure 1. Schematic of test facility
`
`Figure 2. Schematic of TXV-Receiver system
`
`1014
`
`Page 2 of 8
`
`

`
`Downloaded from SAE International by Bianca Hamilton, Friday, December 18, 2015
`
`Jin et al / SAE Int. J. Passeng. Cars - Mech. Syst. / Volume 6, Issue 2(July 2013)
`
`(1)
`
`(2)
`The enthalpies are calculated based on temperature and
`pressure measurements. However, refrigerant is usually two
`phase at the exit of the TXV so the enthalpy at the inlet of the
`evaporator is calculated assuming an isenthalpic throttling
`process. The air side and refrigerant side heat balance are
`within ±5% error with their average, respectively, as shown
`in Figure 5 and Figure 6.
`
`Figure 3. Micro-channel condenser
`
`Figure 5. Comparison of indoor heat balance
`
`Figure 4. Plate and fin evaporator
`
`Table 1. Internal volume of TXV system
`
`UNCERTAINTY ANALYSIS
`Applicable standards require at least two independent
`energy balances to experimentally determine steady-state
`system performances. The test facility for this system has a
`refrigerant-side energy balance (Qref) and an air-side energy
`balance (Qair) for both indoor and outdoor chambers,
`according to SAE J2765 [11] and ASHRAE 41.2 [12]. The
`two energy balances are measured and calculated as
`following:
`
`Figure 6. Comparison of outdoor heat balance
`
`in measuring oil
`involved
`Two uncertainties are
`distribution. One is the uncertainty from the instrumentation
`as listed in the Appendix. Both the accuracy of property data
`and the mass flow measurement affect the uncertainty of the
`system performance. In addition, the accuracy of the scale
`can directly influence the results of measured mass retention.
`Another uncertainty lies on the time lag of closing the
`valves simultaneously. The valves are operated manually by
`
`1015
`
`Page 3 of 8
`
`

`
`Downloaded from SAE International by Bianca Hamilton, Friday, December 18, 2015
`
`Jin et al / SAE Int. J. Passeng. Cars - Mech. Syst. / Volume 6, Issue 2(July 2013)
`
`using the chamber lights as the signal. Since each individual
`has a different reaction time, there is inevitably a time lag in
`closing the valves. It was reported that the average reaction
`time of a university student exposed to light stimuli is 0.24
`seconds [13]. So an uncertainty of 0.3 seconds is used to
`estimate the uncertainty of closing valves as following:
`
`Additionally, subcooling at the outlet of condenser and
`superheat at the of evaporator outlet are calculated from
`Equation 8 and 9.
`
`(8)
`
`(9)
`Figure 7 and Figure 8 present air side cooling capacity,
`the COP, the apparent degree of subcooling at condenser
`outlet, and the apparent degree of superheat at evaporator
`outlet for the TXV system. Both COP and cooling capacity
`reach maximums at the refrigerant charge of 1350 g for
`R134a and 1435 g for R1234yf, which is regarded as the
`optimum charge for the TXV-Receiver system. At their
`optimum charge, R1234yf has higher subcooling than R134a,
`which results in the larger amount of charge. During the tests,
`TXV setting remained the same for both refrigerants at 15 °C.
`
`Figure 7. Charge test with R134a
`
`(3)
`
`(4)
`The combined standard uncertainty is calculated from the
`propagation rule as indicated by Equation 5 and results are
`presented in Figure 9 and 10.
`
`(5)
`
`RESULTS AND DISCUSSION
`The refrigerant charge is one of the factors that affect
`system performance. In the current study, all experimental
`data are taken at the refrigerant charge to maximize the
`Coefficient of Performance (COP).
`The charging process starts with a low charge, which is
`indicated by a high superheat at the outlet of the evaporator.
`A small amount of refrigerant is added in steps at the inlet of
`the evaporator. After the system is stabilized, system
`performance is recorded.
`Since the system is undercharged at first, the refrigerant
`flow through the mass flow meter is not single-phase at all
`times. The mass flow measurement is not accurate for two
`phase flow, so the cooling capacity is determined based on air
`side measurement, as indicated by Equation 6.
`
`(6)
`The air mass flow rate is calculated based on calibrated
`nozzle curve and air enthalpies are calculated based on dry-
`bulb temperature, pressure, and dew point temperature. COP
`is calculated as the ratio of cooling capacity and compressor
`shaft power. Other powered equipment, such as air blowers,
`are not included.
`
`(7)
`Compressor work was determined by measuring torque
`and speed directly on the compressor shaft, between the
`compressor and the drive belt pulley.
`
`With the refrigerant charge determined from charge test,
`three amounts of oil charge, 145g, 175g and 205g, are used
`for both R134a and R1234yf. For each of the charges, the
`mass of refrigerant and lubricant distribution are measured at
`
`Figure 8. Charge test with R1234yf
`
`1016
`
`Page 4 of 8
`
`

`
`Downloaded from SAE International by Bianca Hamilton, Friday, December 18, 2015
`
`Jin et al / SAE Int. J. Passeng. Cars - Mech. Syst. / Volume 6, Issue 2(July 2013)
`
`the I-35 condition in the TXV-receiver system. During the
`measurement, the system is first running at steady state and
`operating parameters are recorded. Temperature, pressure and
`mass flow rate are measured to calculate heat balance
`between refrigerant side and air side. Valves are closed
`simultaneously and the system is shut off. The measuring
`technique developed by Peuker and Hrnjak [2] is employed to
`measure refrigerant and oil mass trapped in each component.
`Since the volume of liquid line in the experimental system is
`6 times larger than the original system and the volume is
`taken by single phase liquid. A factor of 1/6 is taken for both
`refrigerant and oil mass in liquid tube due to the extra
`volume. The results are shown in Figure 9 and 10.
`
`with R134a then with R1234yf, but with both refrigerants, the
`compressor oil mass is less than 25% of the total oil charge.
`In the TXV system, oil distribution in each component
`seems to be in proportion with total oil charge. However, this
`is a different scenario compared with the result in the OT
`(with an internal diameter of 1.823mm) system. As concluded
`by Peuker and Hrnjak [5], in the OT system with the same
`components except for an extra accumulator, increasing
`refrigerant charge while holding total oil charge constant
`results in shifting oil from other components into the
`accumulator. To make comparison between these two
`systems, the total oil and refrigerant charge is normalized as
`the ratio of total oil in the system. Oil mass distribution in
`percentages is listed in Tables 2 and 3. In comparison, as
`charge ratio decreases, oil tends to shift into accumulator in
`OT system; while in the TXV system oil does not exhibit an
`obvious trend of shifting.
`
`Table 2. OT system oil mass distribution in percentage at
`different charge ratio for fixed oil charge
`
`Figure 9. Mass distributions of refrigerant and lubricant
`in TXV system with R134a
`
`Table 3. TXV system oil mass distribution in percentage
`at different charge ratio for fixed refrigerant charge
`
`Figure 10. Mass distributions of refrigerant and
`lubricant in TXV system with R1234yf
`
`According to Figures 9 and 10, both refrigerants exhibit
`similar
`trends
`in
`terms of
`refrigerant and
`lubricant
`distribution. Oil mass in each component increases with total
`oil charge. However, this increasing oil mass has a minor
`effect on refrigerant distribution, as refrigerant mass remains
`nearly the same in each component. The amount of oil in the
`compressor is slightly higher when the system is operating
`
`the comparison between mass
`Figure 11 presents
`distribution in the OT and TXV systems. The components
`compared are identical. The corresponding system operation
`conditions are listed in Table 4. In the TXV system, more
`liquid refrigerant is retained in the condenser than in the OT
`system as indicated by the much higher apparent subcooling
`at the condenser outlet. As a result, more oil is held in the
`condenser in TXV system. Another difference is the much
`higher oil retention in the evaporator in TXV system. This
`might have been caused by the higher superheat which leads
`to a lower refrigerant solubility with oil in the evaporator
`superheated region. The oil return mechanism in this region is
`primarily due to the shear stress of refrigerant vapor [7]. As
`
`1017
`
`Page 5 of 8
`
`

`
`Downloaded from SAE International by Bianca Hamilton, Friday, December 18, 2015
`
`Jin et al / SAE Int. J. Passeng. Cars - Mech. Syst. / Volume 6, Issue 2(July 2013)
`
`oil concentration becomes greater, the liquid film would be
`much more viscous leading to higher oil retention.
`
`Figure 11. Comparison of mass distribution in the same
`components of different system configurations
`
`Table 4. Systems operation condition
`
`Figure 12. Mass distribution at different compressor
`speed with R1234yf
`
`Figure 12 presents the mass distribution results at low
`compressor speed (I35) and high compressor speed (L35).
`According to the results, at higher compressor speed the
`increased mass flow rate has a very minor effect on
`refrigerant mass distribution; however it significantly affects
`oil retention in the evaporator and suction line. Oil retention
`decreases by 20% in the evaporator and 79% in the suction
`line. A higher mass flow rate may have a strong “wash-out”
`
`2.
`
`effect on the superheated region. As observed by Sethi and
`Hrnjak [7], in the horizontal suction line, higher mass flux
`leads to lower oil retention.
`SUMMARY/CONCLUSIONS
`Refrigerant and lubricant mass distribution in a typical
`automotive A/C (MAC) system is experimentally measured
`at steady state. The two tested refrigerant, R134a and
`R1234yf, exhibit similar results in terms of refrigerant and
`lubricant retention. Slightly higher oil retention is found in
`the compressor with R134a but for both refrigerants, less than
`a quarter of the total mass of lubricant resides in compressor.
`Refrigerant distribution has more significant effect on oil
`distribution than oil on refrigerant. In the condenser, oil
`retention is a strong function of liquid refrigerant charge. In
`the evaporator, where the refrigerant charge is about the
`same, oil retention is much higher when the system operates
`with higher superheat.
`A higher mass flow rate does not significantly change the
`refrigerant distribution, but lower lubricant retention in the
`evaporator is observed.
`REFERENCES
`1. Hoehne M. R. and Hrnjak P. S.. “Charge minimization in systems and
`components using hydrocarbons as a refrigerant”. Technical Report
`ACRC TR-224, University of Illinois at Urbana-Champaign, 2004.
`Peuker S. and Hrnjak P.S.. “Experimental and analytical investigation of
`refrigerant and lubricant”. Technical Report ACRC TR-277, Air
`Conditioning and Refrigeration Center, University of Illinois at Urbana-
`Champaign, Urbana, IL, 2010.
`3. Björk E.. “A simple technique for refrigerant mass measurement”.
`Applied Thermal Engineering, 25(8-9):1115-1125, 2005.
`4. Miller W. A.. “The laboratory evaluation of the heating mode part-load
`operation of an air-to-air heat pump”. ASHRAE Transactions, 91(2B):
`524-536, 1985.
`5. Crompton J. A., Newell T. A., and Chato J. C.. “Experimental
`measurement and modeling of oil holdup”. Technical Report ACRC
`TR-226, University of Illinois at Urbana-Champaign, 2004.
`6. Zoellick K.F., and Hrnjak P.S., “Oil retention and pressure drop in
`horizontal and vertical suction lines with R410A/POE”, Technical
`Report ACRC TR-271, Air Conditioning and Refrigeration Center,
`University of Illinois at Urbana-Champaign, Urbana, IL, 2010.
`Sethi A., and Hrnjak P.S., “Oil retention and pressure drop of R1234yf
`and R134a with POE ISO 32 in suction lines”, Technical Report ACRC-
`TR 281, Air Conditioning and Refrigeration Center, University of
`Illinois at Urbana-Champaign, Urbana, IL, 2011.
`8. Lee J.P., Hwang Y., Radermacher R., and Mehendale S. S.,
`“Experimental investigations on oil accumulation characteristics in a
`vertical suction line”, In Proc. of ASME IMECE 2001, Vol. 3, AES
`23607, New York, NY, 2001.
`9. Lee J.P., “experimental and theoretical investigation of oil retention in
`carbon dioxide air-conditioning system”, Ph.D. Thesis, CEEE,
`University of Maryland, College Park, MD, 2002.
`10. Cremaschi L., “Experimental and theoretical investigation of oil
`retention
`in vapor compression systems”, Ph.D. Thesis, CEEE,
`University of Maryland, College Park, MD, 2004.
`11. SAE International Surface Vehicle Standard, “Procedure for Measuring
`System COP [Coefficient of Performance] of a Mobile Air Conditioning
`System on a Test Bench,” SAE Standard J2765, Issued Oct. 2008.
`12. ANSI/ASHRAE Standard 41.2-1987 (RA92). Standard methods for
`laboratory airflow measurement. American Society of Heating,
`Refrigeration and Air-Conditioning Engineers, 1992.
`13. Gupta S.. “Simple visual reaction time, personality and strength of the
`nervous system: A signal-detection theory approach”. Personality and
`Individual Differences, 6(4):461-469, 1985.
`14. Gordon, T., Eustice, H., and Brooks, W., “Automotive AC System Oil
`Migration HFO-1234yf Vs. R134a,” SAE Technical Paper
`2011-01-1173, 2011, doi:10.4271/2011- 01-1173.
`
`7.
`
`1018
`
`Page 6 of 8
`
`

`
`Downloaded from SAE International by Bianca Hamilton, Friday, December 18, 2015
`
`Jin et al / SAE Int. J. Passeng. Cars - Mech. Syst. / Volume 6, Issue 2(July 2013)
`
`ACKNOWLEDGMENTS
`The authors thankfully acknowledge the support provided
`by the Air Conditioning and Refrigeration Center at the
`University of Illinois at Urbana-Champaign.
`
`ABBREVIATIONS
`MAC - Automotive A/C system
`Mr - mass flow rate, g/s
`OCR - Oir Circulation Rate
`ρ - Density, kg/m3
`cond - Condenser
`comp - Compressor
`evap - Evaporator
`OT - Orifice tube
`PAG - polyalkelene glycol oil
`TXV - Thermal Expansion Valve
`ref - Refrigerant
`sat - Saturated
`SC - Subcooling, °C
`SH - Superheat, °C
`tot - Total
`
`1019
`
`Page 7 of 8
`
`

`
`Downloaded from SAE International by Bianca Hamilton, Friday, December 18, 2015
`
`Jin et al / SAE Int. J. Passeng. Cars - Mech. Syst. / Volume 6, Issue 2(July 2013)
`
`APPENDIX
`
`Instrument specification
`
`1020
`
`Page 8 of 8

This document is available on Docket Alarm but you must sign up to view it.


Or .

Accessing this document will incur an additional charge of $.

After purchase, you can access this document again without charge.

Accept $ Charge
throbber

Still Working On It

This document is taking longer than usual to download. This can happen if we need to contact the court directly to obtain the document and their servers are running slowly.

Give it another minute or two to complete, and then try the refresh button.

throbber

A few More Minutes ... Still Working

It can take up to 5 minutes for us to download a document if the court servers are running slowly.

Thank you for your continued patience.

This document could not be displayed.

We could not find this document within its docket. Please go back to the docket page and check the link. If that does not work, go back to the docket and refresh it to pull the newest information.

Your account does not support viewing this document.

You need a Paid Account to view this document. Click here to change your account type.

Your account does not support viewing this document.

Set your membership status to view this document.

With a Docket Alarm membership, you'll get a whole lot more, including:

  • Up-to-date information for this case.
  • Email alerts whenever there is an update.
  • Full text search for other cases.
  • Get email alerts whenever a new case matches your search.

Become a Member

One Moment Please

The filing “” is large (MB) and is being downloaded.

Please refresh this page in a few minutes to see if the filing has been downloaded. The filing will also be emailed to you when the download completes.

Your document is on its way!

If you do not receive the document in five minutes, contact support at support@docketalarm.com.

Sealed Document

We are unable to display this document, it may be under a court ordered seal.

If you have proper credentials to access the file, you may proceed directly to the court's system using your government issued username and password.


Access Government Site

We are redirecting you
to a mobile optimized page.





Document Unreadable or Corrupt

Refresh this Document
Go to the Docket

We are unable to display this document.

Refresh this Document
Go to the Docket