throbber
ASHRAE Guideline 3-1996
`(Supersedes ASHRAE Guideline 3-1990)
`
`Reducing Emission
`of Halogenated
`Refrigerants in
`Refrigeration and
`Air-Conditioning
`Equipment and
`Systems
`
`Approved by the ASHRAE Standards Committee
`June 21, 1996, and by the ASHRAE Board of
`Directors June 27, 1996.
`
`ASHRAE Guidelines are updated on a five-year
`cycle; the date following the Guideline number
`is the year of ASHRAE Board of Directors
`approval. The latest copies may be purchased
`from ASHRAE Customer Service, 1791 Tullie
`Circle, NE, Atlanta, GA 30329.
`
`©1996 American Society of Heating, Refrigerat-
`ing and Air-Conditioning Engineers, Inc. All
`rights reserved.
`
`ISSN 1049-894X
`
`p
`
`
`
`
`
`
`
`
`
`
`
`6
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
` N
`
` p
`
`
`
`b
`
` p
`
` D
`
`b
`
`
`
`
`
` b
`
`
`
`
`
`
`
`
`
`Arkema Exhibit 1106
`
`Page 1 of 20
`
`

`
`ASHRAE STANDARD PROJECT COMMITTEE 147P FOR GUIDELINE 3-1996
`Cognizant TC: TC 3.8, Refrigerant Containment
`Standards Project Committee Liaison: Michael R. Bilderbeck
`
`Warren L. Beeton, Chair
`Van D. Baxter,* Secretary
`John G. Blackmon
`Joshua Donald Costell
`William S. de Laurier
`Richard J. Denny
`Jeff Dickson*
`Warren H. Dillenbeck
`Bryan Franklin
`Herbert T. Gi key
`Jeff S. James
`Henry A. Johnson
`Philip C. Landes
`Dean E. Lewis
`
`Debbie Ottinger*
`Jude A. Pauli
`Christopher M. Powers
`Robert Joseph Roth*
`Stephen V. Santoro*
`Amy L. Savage
`James I. Sheridan
`Sam P. Soling
`Leonard J. Swatkowski*
`William Vestal
`Ricardo Valles Vicuna*
`Richard Bowman Wimsatt*
`Robert W. Yost
`
`*Denotes members of voting status when Guideline 3-1990R was approved for publication.
`
`ASHRAE STANDARDS COMMITTEE 1995-96
`
`Max H. Sherman, Chair
`Sally A. Hooks, Vice-Chair
`Richard L. Beck, Jr.
`Herman F. Behls
`W. David Bevirt
`Michael R. Bilderbeck
`George F. Carscallen
`Gordon F. Clyde
`Thomas A. Gilbertson
`Allen J. Hanley
`Peter J. Hoey
`
`Daniel Int-Hout
`Merle F. McBride
`William E. Murphy
`Bjarne Olesen
`Elizabeth A. Parke
`William V. Richards
`Gaylon Richardson
`Ganesan Sundaresan
`Michael W. Woodford
`George S. Yamamoto
`Grenville K. Yuill
`Donald G. Colliver, ExO
`James E. Wolf, CO
`
`Jim L. Heldenbrand, Manager of Standards
`SPECIAL NOTE
`
`This Guideline was developed under the auspices of the American Society of Heating, Refrigerating and Air-Conditioning Engineers
`(ASHRAE). ASHRAE Guidelines are developed under a review process, identifying a guideline for the design, testing, application, or evalua-
`tion of a specific product, concept, or practice. As a guideline it is not definitive but encompasses areas where there may be a variety of
`approaches, none of which must be precisely correct. ASHRAE Guidelines are written to assist professionals in the area of concern and exper-
`tise of ASHRAE’s Technical Committees and Task Groups.
`ASHRAE Guidelines are prepared by project committees appointed specifically for the purpose of writing Guidelines. The project
`committee chair and vice-chair must be members of ASHRAE; while other members of the project committee may or may not be ASHRAE
`members, all must be technically qualified in the subject area of the Guideline.
`Development of ASHRAE Guidelines follows procedures similar to those for ASHRAE Standards except that (a) committee balance
`is desired but not required, (b) an effort is made to achieve consensus but consensus is not required, (c) guidelines are not appealable, and (d)
`guidelines are not submitted to ANSI for approval.
`The Manager of Standards of ASHRAE should be contacted for:
`a. interpretation of the contents of this Guideline,
`b. participation in the next review of the Guideline,
`c. offering constructive criticism for improving the Guideline,
`d. permission to reprint portions of the Guideline.
`
`ASHRAE INDUSTRIAL ADVERTISING POLICY ON STANDARDS
`
`ASHRAE Standards and Guidelines are established to assist industry and the public by offering a uniform method of testing for rating
`purposes, by suggesting safe practices in designing and installing equipment, by providing proper definitions of this equipment, and by
`providing other information that may serve to guide the industry. The creation of ASHRAE Standards and Guidelines is determined by the
`need for them, and conformance to them is completely voluntary.
`In referring to this Standard or Guideline and in marking of equipment and in advertising, no claim shall be made, either stated or
`implied, that the product has been approved by ASHRAE.
`
`ASHRAE uses its best efforts to promulgate Standards and Guidelines for the benefit of the public in light of available information and
`accepted industry practices. However, ASHRAE does not guarantee, certify, or assure the safety or performance of any products,
`components, or systems tested, installed, or operated in accordance wi h ASHRAE’s Standards or Guidelines or that any tests conducted
`under its Standards or Guidelines will be nonhazardous or free from risk.
`
`DISCLAIMER
`
`p
`
`
`
`
`
`
`
`
`
`
`
`6
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
` N
`
` p
`
`
`
`b
`
` p
`
` D
`
`b
`
`
`
`
`
` b
`
`
`
`
`
`
`
`
`
`Page 2 of 20
`
`

`
`TABLE OF CONTENTS
`ASHRAE Guideline 3-1996, Reducing Emission of Halogenated
`Refrigerants in Refrigeration and Air-Conditioning Equipment and Systems
`
`Page
`Section
`Foreword . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
`
`1. Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
`
`2. Scope. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
`
`3. Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
`
`4. Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
`4.1 General Topics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
`4.2 Appliance Specific Topics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
`4.3 Unitary System Specific Topics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
`4.4 Large Equipment Specific Topics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
`
`5. Product Development . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
`5.1 Refrigerant Recovery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
`5.2 System Cleanliness. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
`5.3 Vibration Tests. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
`
`6. Manufacture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
`6.1 Evacuation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
`6.2 Holding Charges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
`6.3 Cleanliness of Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
`6.4 Factory Leak Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
`6.5 Operating Test Gas Recovery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
`
`7.
`
`Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
`7.1 Installation of Field-Erected Equipment and Systems. . . . . . . . . . . . . . . . . . . . . . 7
`7.2 Pressure Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
`7.3 Leak Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
`7.4 Evacuation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
`7.5 Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
`
`8. Service/Operation/Maintenance/Decommissioning . . . . . . . . . . . . . . . . . . . . . . . . . . .8
`8.1 General Topics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
`8.2 Appliance Specific Topics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
`8.3 Large Equipment Specific Topics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
`
`9. Refrigerant Recovery, Reuse, and Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
`9.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
`9.2 Refrigerant Disposition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
`9.3 Refrigerant Transfer, Transport, and Storage . . . . . . . . . . . . . . . . . . . . . . . . . . .12
`9.4 Disposal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
`9.5 Appliance Specific Topics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
`
`10. Training of Personnel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
`
`11. Handling and Storage of Refrigerants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
`11.1 System Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
`11.2 Recovery Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
`11.3 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
`11.4 Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
`
`12. References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
`
`Annex A, Training of Personnel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
`
`Annex B, Bibliography . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
`
`p
`
`
`
`
`
`
`
`
`
`
`
`6
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
` N
`
` p
`
`
`
`b
`
` p
`
` D
`
`b
`
`
`
`
`
` b
`
`
`
`
`
`
`
`
`
`Page 3 of 20
`
`

`
`(This foreword is not part of this guideline but is provided
`for information only.)
`
`FOREWORD
`
`When the potential for depletion of stratospheric ozone
`as a result of atmospheric release of chlorofluorocarbons
`(CFCs) was first discussed, ASHRAE appointed a task group
`to study the issue and to develop appropriate policy and pro-
`gram recommendations to the Board of Directors.
`In response, a comprehensive action program was initi-
`ated. It included research, education, communication, and
`training directed toward the various aspects of the CFC issue.
`A part of this program was the development of a guideline for
`reducing CFC refrigerant emission. This was published as
`ASHRAE Guideline 3-1990.
`Since that date, it has been determined that all chlorine-
`containing refrigerants, HCFCs as well as CFCs, are detri-
`mental to the ozone layer and their emission should be mini-
`mized.10 Guideline 3 has been revised to reflect this more
`stringent policy.
`This guideline recommends practices and procedures
`that will reduce emission into the atmosphere of halogenated
`refrigerants used in refrigeration and air-conditioning. As a
`guideline, this does not constitute a technical design docu-
`ment. It should be used in conjunction with other standards
`and codes or practice already in existence.
`Reducing emission of all halogenated refrigerants,
`including CFCs, HCFCs, and HFCs, may have a positive
`effect with respect to other environmental concerns such as
`global warming. In addition to environmental benefits, sav-
`ings from reduced refrigerant losses can be expected by
`applying this guideline to equipment and systems that use
`other refrigerants.
`
`Organization
`
`In Clauses 4, 8, and 9 of this guideline, measures that are
`generally applicable to all types of equipment are presented
`first. Then some measures are presented that are applicable to
`specific types of equipment. The text distinguishes between
`three types of equipment: appliances (household refrigera-
`tors, room air conditioners, etc.), unitary equipment, and
`large equipment. Provisions for one specific type of equip-
`ment may not apply to other types.
`
`Acknowledgments
`
`In the preparation of this guideline, use has been made of
`the recommendations contained in the “Code of Good Prac-
`tice” issued by the Commission of the European Communi-
`ties, Report EUR 9509 EN. Additionally, recommendations
`described by other organizations and appropriate provisions
`of various standards have been important sources of informa-
`tion presented in this guideline.
`
`1. PURPOSE
`
`This guideline recommends practices and procedures
`that will reduce inadvertent release of halogenated refriger-
`ants.
`
`2. SCOPE
`
`The practices and procedures in this guideline cover
`emission reduction of halogenated hydrocarbon and haloge-
`nated ether refrigerants:
`(a)
`from stationary refrigeration, air-conditioning, and
`heat pump equipment and systems;
`during manufacture, installation, testing, operation,
`maintenance, and disposal of equipment and systems.
`
`(b)
`
`3. TERMINOLOGY
`
`Although the following terms may have broader interpre-
`tations elsewhere in the industry, their specific meanings as
`used in this guideline are as follows.
`
`CFC: a fully halogenated (no hydrogen remaining) halocar-
`bon containing chlorine, fluorine, and carbon atoms.
`HCFC: a halocarbon that contains fluorine, chlorine, carbon,
`and hydrogen.
`HFC: a halocarbon that contains only fluorine, carbon, and
`hydrogen.
`joint, brazed: a gas-tight joint obtained by joining metal parts
`with alloys that melt at temperatures higher than 800°F
`(426°C) but less than the melting temperatures of the joined
`parts.
`joint, mechanical: a gas-tight joint obtained by the joining of
`metal parts through a positive holding mechanical construc-
`tion (such as a flanged joint, screwed joint, or flared joint).
`joint, soldered: a gas-tight joint obtained by joining metal
`parts with metallic mixtures or alloys that melt at temperatures
`above 400°F (204°C) but not exceeding 800°F (426°C).
`joint, welded: a gas-tight joint obtained by the joining of metal
`parts in the plastic or molten state.
`pressure, design: the maximum allowable working pressure
`for which a specific part of a system is designed.
`pressure, maximum working: (see pressure, design).
`pressure, operating: the pressure occurring at a reference
`point in a refrigerating system when the system is in operation.
`pressure-relief device: a valve or rupture member designed to
`relieve excessive pressure automatically.
`prevention-of-vacuum system: a refrigerant pressure control
`that prevents refrigerant loss and infiltration into idle low-
`pressure chillers; it is also used to pressurize for leak testing
`without the use of noncondensables.
`purging: removal of noncondensable gases from the system.
`purging device: an automatic, semi-automatic, or hand-oper-
`ated device that collects noncondensable gas from the con-
`denser or receiver.
`receiver: a vessel in the refrigerating system designed to
`ensure the availability of adequate liquid refrigerant for proper
`functioning of the system and to store the liquid refrigerant
`when the system is pumped down.
`reclaim: to process used refrigerant to new product specifica-
`tions.
`recover: to remove refrigerant in any condition from a system
`and store it in an external container.
`recycle: to reduce contaminants in used refrigerants by sepa-
`rating oil, removing noncondensables, and using devices such
`as filter dryers to reduce moisture, acidity, and particles.
`
`ASHRAE Guideline 3-1996
`
`1
`
`p
`
`
`
`
`
`
`
`
`
`
`
`6
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
` N
`
` p
`
`
`
`b
`
` p
`
` D
`
`b
`
`
`
`
`
` b
`
`
`
`
`
`
`
`
`
`Page 4 of 20
`
`

`
`rupture disc: a safety device that will rupture at a predeter-
`mined pressure.
`small, hermetically sealed system: a factory-charged refriger-
`ating system using less than 2.3 kg (5 lb) of refrigerant that is
`welded, brazed, soldered, or otherwise joined together in such
`a manner as to create a sealed system typically capable of
`operating for 25 years without maintenance or repair.
`vacuum, deep (high vacuum): a vacuum of 130 Pa (1000
`microns) or less of absolute pressure.
`valve, pressure-relief: a pressure-actuated valve held closed
`by a spring or other means and designed to automatically
`relieve pressure in excess of its setting.
`valve, purge: a device to allow noncondensable gases to flow
`out of the system.
`
`4. DESIGN
`
`This clause deals with the design of air-conditioning and
`refrigerating systems and components and identifies possible
`sources of loss of refrigerants to the atmosphere. The under-
`standing and application of established techniques in both the
`design and construction of refrigerating systems provide a
`good foundation for the prevention of refrigerant release to
`the atmosphere.
`Instructions that will instruct field personnel to install,
`operate, and service the equipment to minimize refrigerant
`emission shall be provided.
`
`4.1 General Topics
`4.1.1 Compressors. Leaks associated with compressors
`may be related to the design of the compressor or to the asso-
`ciated equipment fitted to it, e.g., gauge and cut-out connec-
`tions, relief valves, and connected piping.
`4.1.1.1 Shaft Seals. Shaft seals are required on open-
`style compressors and can be a source of refrigerant leakage.
`Seals should be designed recognizing that in operation the
`refrigerant and oil to which they will be exposed may contain
`contaminants.
`Shaft-seal designs that do not rely on the commonly used
`carbon faces are available. Double-faced seals and single-car-
`bon seals with improved features to keep the carbon in a wet
`state have been found to be effective and are recommended.
`The design and installation of the shaft-seal assembly
`should minimize external oil loss and prevent direct refriger-
`ant loss. Lack of lubrication during shutdown periods can
`cause mating faces of the seal to dry out and adhere together.
`On large systems, a separate oil pump to lubricate the seal
`prior to starting the compressor is recommended.
`Open compressors typically have carbon-face seals that
`require positive pressure in order to function properly. Since
`these are not two-way seals, leakage may occur during evac-
`uation. To prevent leakage, temporary sealing measures such
`as shaft caps or clay-like weather stripping around the protru-
`sion of the shaft should be used.
`The motor-compressor alignment is critical in limiting
`refrigerant leakage and is affected by the style of the coupling
`and the speed and power of the motor. Refrigeration machin-
`ery requires stringent alignment to accommodate thermal
`growth over the load and temperature ranges.
`
`Shutdown and start-up procedures should ensure that oil
`is present to wet the seal faces. It may be necessary to run the
`oil pump and rotate the shaft periodically during long shut-
`down periods. If this is not possible, the seals should be
`inspected and lubricated before starting the system.
`4.1.1.2 Vibration. Vibration
`from gas-pressure
`pulses and moving parts can cause leaks. Some improvement
`can be achieved by placing the compressor on an adequate
`solid foundation and providing resilient mountings.
`For those compressors that are spring mounted, vibration
`elimination should be provided in the suction and discharge
`lines. When piping vibration eliminators are used, they should
`be parallel with the shaft of the compressor and anchored
`firmly at the upstream end in the suction line and at the down-
`stream end in the discharge line.
`Vibrations from gas pulses are best handled by a good
`muffler placed as close as possible to the compressor.
`Adequate support of piping connections to the compres-
`sor is important to avoid stresses that could lead to leakage.
`(See also 4.1.3.4.)
`4.1.1.3
`Isolation. Adequate isolation of system com-
`ponents, such as gauges, operating controls, and compressors,
`should be provided to minimize refrigerant loss during servic-
`ing or replacement in accordance with ASHRAE Standard
`15.1
`
`Compressor isolation valves should be provided on both
`the suction and discharge sides of the compressor to minimize
`release of refrigerant during service work. Isolation capability
`should be provided for any other compressor connections. If
`the connection size is greater than 150 mm (6 in.), the provi-
`sion of isolation valves is not necessary but pump-out capa-
`bility should be provided or readily available for system
`servicing. (See also 4.1.4.)
`4.1.2 Condensers and Evaporators. Properly designed
`and manufactured condensers and evaporators normally have
`few leakage problems. However, the following points require
`consideration and appropriate action.
`(a) Refrigerant circuits should not leak.
`(b) Connections, such as refrigerant gauges and liquid
`level gauge glasses, are a potential source of leakage.
`Isolation valves are recommended to minimize leak-
`age in accordance with ASHRAE Standard 15.1
`4.1.2.1 Air-Cooled Condensers and Evaporators
`4.1.2.1.1 Excessive vibration from compressors or
`other equipment can cause tube failure. This effect may be
`eliminated by the use of anti-vibration mountings and vibra-
`tion eliminators. (See also 4.1.1.2.)
`4.1.2.1.2 Equipment should be designed to with-
`stand anticipated stress, vibration, and galvanic corrosion.
`Tubing supports should be constructed to minimize vibration
`and to provide protection against abrasion due to movement
`(see also 4.1.3.4) and must allow for thermal expansion.
`4.1.2.1.3 Construction materials and methods of
`design should be selected to preclude emissions of refrigerant
`as a result of leakage during normal operation.
`
`2
`
`ASHRAE Guideline 3-1996
`
`p
`
`
`
`
`
`
`
`
`
`
`
`6
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
` N
`
` p
`
`
`
`b
`
` p
`
` D
`
`b
`
`
`
`
`
` b
`
`
`
`
`
`
`
`
`
`Page 5 of 20
`
`

`
`4.1.2.1.4 Condensers and evaporators should be
`designed to keep the refrigerant volume (charge) as small as
`possible.
`4.1.2.1.5 Air-cooled condensers and evaporators
`should be constructed with the fewest practicable number of
`joints and return bends. Brazing is the preferred method of
`joining (see also 4.1.3.2).
`4.1.2.2 Water-Cooled Condensers and Evaporators
`4.1.2.2.1 Excessive vibration can cause failure of
`shell-and-tube heat exchangers. Vibration from any of several
`sources can cause tube failure:
`(a) The boiling action in flooded evaporators can cause
`vibration at the natural frequency of the tubes, creat-
`ing excessive wear at tube supports and possible fail-
`ure. This problem can be avoided with properly
`spaced and sized tube supports.
`(b) Excessive fluid velocity in condensers and evapora-
`tors can set up vibrations that will cause premature
`tube failure. Precautions similar to those described in
`4.1.2.2.1(a) can minimize the problem.
`4.1.2.2.2 Excessive fluid velocity in water-cooled
`condensers and evaporators can lead to premature failure by
`erosion. As velocities increase, the potential for premature
`failure increases as the square of the velocity. Care must be
`taken that design velocities are within good practice for the
`material selected. Pluggage, especially in condensers, can
`result in increased velocities above design for normal flow
`through the heat exchanger. The potential for damage will be
`reduced by limiting velocities.
`4.1.2.2.3 The characteristics of fluids used in liquid
`chillers and liquid-cooled condensers vary widely and can
`lead to premature failure of tubes. Selection of tube materials
`and the tube wall thickness must be suitable for the fluids to
`be used in the system. In applications where fouled condenser
`water can lead to premature tube failure, the use of smooth-
`bore tubes is recommended. Proper filtration can reduce ero-
`sion caused by foreign particles in the fluid. Proper chemical
`treatment can minimize the effects of corrosive elements in
`the fluid.
`4.1.2.2.4 Reduced or suspended water flow can also
`lead to serious corrosion problems. Seawater-cooled systems
`are especially susceptible to corrosion, as are some systems
`using water containing traces of ammonia or microbiological
`organisms. These contaminants will attack the tubes and may
`also attack tube sheets and heat exchanger heads, leading to
`leakage. Facilities for routine flushing and inspection are
`advisable. Special linings and special tube materials may be
`required to minimize attack on these surfaces.
`4.1.2.2.5 Any of several conditions can lead to
`freeze-up that can cause severe damage and rupture of tubes.
`To prevent freeze-up, interlocked safety controls for pressure,
`temperature, and flow should be provided.
`4.1.3 Piping, Tubing, and Connections
`4.1.3.1 Pipe and fittings should be in accordance with
`requirements of ASME B31.52 or SAE J513.3 All design and
`installation of systems should be done in such a manner as to
`
`reduce the number of fittings and connections as much as
`practicable.
`Tapered pipe threads are not recommended for fittings in
`refrigerant circuits. Particularly in sizes of 25 mm (1 in.) or
`larger, they should be avoided. SAE 45-degree flare fittings
`and short radius elbows are not extremely reliable. Their use
`is discouraged.
`4.1.3.2 Because of increased resistance to pressure,
`temperature, and vibration stresses, flanged joints, welding,
`and brazing are the preferred methods of joining pipe to fit-
`tings, valves, and other components. Soft solder is not a rec-
`ommended alternative to brazing.
`4.1.3.3 All flanged joints should be in accordance
`with the requirements of ASME B31.5.2 Special care should
`be taken to ensure that gasketing materials are compatible
`with both the refrigerant and refrigerant oils.
`4.1.3.4 All pipe supports should be designed and
`installed to minimize vibration. All pipe supports should meet
`the requirements of ASME B31.52 regarding calculations of
`strength, movement, load, and standard components. Sup-
`ports should be designed to guard against electrolytic corro-
`sion and also to provide for protection of tubing components
`against external abrasion due to movement.
`4.1.3.5 Strainers, filters, and dryers should be utilized
`to control moisture and minimize damage to moving parts and
`avoid plugging of refrigerant circuits caused by contaminants
`in the system.
`4.1.3.6 Strainers, filters, and dryers should be isolated
`with valves to permit proper servicing of equipment.
`4.1.3.7 Corrosion protection should be used to pre-
`vent rusting of exposed steel components, particularly in the
`low-temperature section of systems.
`4.1.3.8
`In refrigerant piping design, any line that can
`be filled with refrigerant liquid should not have two stop
`valves, or a stop valve and solenoid valve in series, unless pro-
`vided with a relief. If liquid is trapped between two valves, it
`can experience thermal expansion and rupture the connecting
`tubing.
`4.1.4
`Isolation Valves
`4.1.4.1
`Isolation valves should have retained or cap-
`tive spindles and facilities for tightening or replacement of the
`gland packing under line pressure. All manual valves should
`be provided with gasketed seal caps made of nonferrous metal
`to fit over the stem and be threaded to the valve body. Seal
`caps should be attached to the valve body by a strap or chain
`to avoid losing them in service.
`4.1.4.2 For pipe sizes in excess of 20 mm (3/4 in.)
`nominal diameter, flanged, welded, or brazed ends should be
`utilized for all valves. Threaded valves are acceptable if the
`threads are backwelded.
`4.1.5 Access Valves for Charging, Evacuation, or Both
`4.1.5.1 Access valves should be provided for evacua-
`tion and liquid charging of refrigeration systems. Valves
`should be provided in systems for liquid drainage and vapor
`extraction. At a minimum, every refrigerant circuit should be
`provided with a vapor access valve and a liquid access valve.
`
`ASHRAE Guideline 3-1996
`
`3
`
`p
`
`
`
`
`
`
`
`
`
`
`
`6
`
`
`
`
`
`
`
`
`
`
`
`
`
`
`
` N
`
` p
`
`
`
`b
`
` p
`
` D
`
`b
`
`
`
`
`
` b
`
`
`
`
`
`
`
`
`
`Page 6 of 20
`
`

`
`(b)
`
`4.1.5.2
` Access valves should be located where pres-
`sure readings should be taken. They should be provided with
`caps as in 4.1.4.1 and should be used for vapor and liquid
`charging to minimize potential leak sources.
`4.1.6 Relief Devices. The intent of this subclause is to
`recommend the use of relief devices that minimize refrigerant
`loss to the atmosphere. Relief devices for refrigerating sys-
`tems are prescribed in ASHRAE Standard 15.1
`4.1.6.1 Normal practice is to provide separate relief
`devices for the high and low sides; however, high-side pres-
`sure-relief devices may be piped so as to discharge into the
`low side of the system provided
`(a)
`they are of a type not appreciably affected by back
`pressure, and
`the low side is equipped with a pressure-relief device
`of sufficient capacity as specified in ASHRAE Stan-
`dard 151 to protect all connected vessels, compres-
`sors, and pumps subjected
`to excess pressure
`simultaneously.
`In centrifugal machines where the condenser cannot be
`isolated from the evaporator, a single pressure-relief device
`will suffice to protect the system in accordance with
`ASHRAE Standard 15.1
`4.1.6.2 Where a relief valve is used, a rupture disc
`should be installed upstream of the valve to protect the valve
`from corrosion or inadvertent leakage. An indicator should be
`installed between the rupture disc and the relief valve to indi-
`cate that the disc has ruptured. The rupture disc should be a
`nonshattering type. Once the rupture disc has burst, it should
`be replaced as soon as possible. It may be necessary to remove
`the remaining refrigerant charge before replacing the disc.
`Note: When pressure-relief devices are installed in
`series, provisions of Section 8 of the ASME Unfired
`Pressure Vessel Code4 should be observed.
`
`4.2 Appliance Specific Topics
`4.2.1
`It must be recognized that any piercing of the
`refrigerating system presents a potential refrigerant leak
`source. Therefore, any provision herein relating to accesso-
`ries, devices, or connections is not intended to suggest that
`such accessories, devices, or connections should be included
`in a specific product or system.
`4.2.2 Valves in a refrigerating system are also potential
`leak sources. Consequently, except as 4.1.5 provides for a sin-
`gle access point or equally effective design feature, valves
`should generally not be included in factory-charged, hermet-
`ically sealed systems.
`4.2.3 Factory-charged, hermetically sealed systems that
`are listed by a nationally recognized testing agency should be
`considered to comply with provisions of 4.1.3.1 and 4.1.3.3.
`4.2.4 For factory-sealed systems, soldering, epoxy join-
`ing, or any other method demonstrated to maintain the her-
`metic nature of the system is acceptable as an alternative to
`brazing.
`4.2.5 Access valves for charging, evacuation, or both
`should be installed except as otherwise provided therein (i.e.,
`equally effective design feature).
`
`4.2.6 On factory-charged, hermetically sealed systems
`with a refrigerant charge of less than 2.3 kg (5 lb), a servicing
`aperture or equally effective design feature (e.g., process tube
`or stub) that will facilitate the recovery of refrigerant during
`service and repair or disposal is acceptable
`4.2.7 Factory-charged, hermetically sealed systems that
`are listed by a nationally recognized testing laboratory should
`be considered to comply with the provisions of 4.1.6.
`
`4.3 Unitary System Specific Topics
`Unitary air conditioners and heat pumps are manufac-
`tured, sold, and installed with little or no provision for preven-
`tive maintenance on
`the sealed refrigerating system.
`Accordingly, the only service involvement in the refrigerating
`system is when the home or building owner notices the sys-
`tem’s inability to provide comfort. Quite often, refrigerant
`leaks are the reason for the system’s loss of performance. It is,
`therefore, recommended that unitary systems be designed to
`facilitate their manufacture, transport, and installation with
`minimum probability for leaks during 15- or 20-year life
`cycles. It is industry practice that unitary systems meet the
`requirements and bear the seal(s) of approval of one or more
`nationally recognized testing agencies.
`4.3.1 Compressors. Most unitary system compressors
`are hermetic. Process tubes extending from the compressor
`should be pinched and soldered or brazed as approved by a
`nationally recognized testing agency. Suction and discharge

This document is available on Docket Alarm but you must sign up to view it.


Or .

Accessing this document will incur an additional charge of $.

After purchase, you can access this document again without charge.

Accept $ Charge
throbber

Still Working On It

This document is taking longer than usual to download. This can happen if we need to contact the court directly to obtain the document and their servers are running slowly.

Give it another minute or two to complete, and then try the refresh button.

throbber

A few More Minutes ... Still Working

It can take up to 5 minutes for us to download a document if the court servers are running slowly.

Thank you for your continued patience.

This document could not be displayed.

We could not find this document within its docket. Please go back to the docket page and check the link. If that does not work, go back to the docket and refresh it to pull the newest information.

Your account does not support viewing this document.

You need a Paid Account to view this document. Click here to change your account type.

Your account does not support viewing this document.

Set your membership status to view this document.

With a Docket Alarm membership, you'll get a whole lot more, including:

  • Up-to-date information for this case.
  • Email alerts whenever there is an update.
  • Full text search for other cases.
  • Get email alerts whenever a new case matches your search.

Become a Member

One Moment Please

The filing “” is large (MB) and is being downloaded.

Please refresh this page in a few minutes to see if the filing has been downloaded. The filing will also be emailed to you when the download completes.

Your document is on its way!

If you do not receive the document in five minutes, contact support at support@docketalarm.com.

Sealed Document

We are unable to display this document, it may be under a court ordered seal.

If you have proper credentials to access the file, you may proceed directly to the court's system using your government issued username and password.


Access Government Site

We are redirecting you
to a mobile optimized page.





Document Unreadable or Corrupt

Refresh this Document
Go to the Docket

We are unable to display this document.

Refresh this Document
Go to the Docket